Allen-Bradley PowerFlex 70 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step diagnostic procedures for Allen-Bradley PowerFlex 70 AC drives. Search or filter through the complete diagnostic directory below.

FORCE™ Technology Vector Control Power: 0.37 to 37 kW (0.5 to 50 HP) DriveGuard Safe Torque Off (STO)
Power Range 0.37 – 37 kW (0.5 – 50 HP)
Supply Voltage 200–600V (3-Phase)
Control Modes V/Hz, Sensorless & FORCE™ Vector
Operator Interface LCD HIM / DPI / CCW Software

Complete Allen-Bradley PowerFlex 70 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F2, F3, F4, or OverCurrent).

Fault CodesCause & Solutions
F2
Auxiliary
Input
Cause : Auxiliary input interlock is open.

Solution:

- Check remote wiring.
- Verify communications programming for intentional fault.
F3
Power Loss
Cause: Excessive DC Bus voltage ripple.

Solution:

- Monitor the incoming AC line for low voltage or line power interruption.
- Check input fuses.
- Reduce load.
F4
UnderVoltage
Cause: DC bus voltage fell below the min value.

Solution: Monitor the incoming AC line for low voltage or line power interruption.
F5
OverVoltage
Cause: DC bus voltage exceeded max value.

Solution:

- Monitor the AC line for high line voltage or transient conditions.
- Bus overvoltage can also be caused by motor regeneration.
- Extend the decel time or install dynamic brake option.
F7
Motor
OverLoad
Cause:

- Internal electronic overload trip.
- Enable/Disable with [Fault Config 1].

Solution:

- An excessive motor load exists.
- Reduce load so drive output current does not exceed the current set by [Motor NP FLA]. If enabled, check level of flux braking in parameter P549 [Flux Braking %].
F8
Heatsink
OvrTmp
Cause: Heatsink/Power Module temperature exceeds a predefined value.

Solution:

- Check for blocked or dirty heatsink fins. Verify that ambient temperature has not exceeded the rated ambient temperature.
- Check fan.
F9
Trnsistr
OvrTemp
Cause: Output transistors have exceeded their maximum operating temperature.

Solution:

- Verify that maximum ambient temperature has not been exceeded.
- Check fan.
- Check for excessive load.
F10
Heatsink
LowTemp
Cause: Annunciates a too low temperature case or an open NTC (heatsink temperature sensing device) circuit.

Solution:

- Verify ambient temperature.
- In cold ambient temperatures, add space heaters.
- Check connections to NTC.
F12
HW
OverCurrent
Cause: The drive output current has exceeded the hardware current limit.

Solution:

- Check output of drive or motor for shorts.
- Check programming.
- Check for excess load, improper DC boost setting, DC brake volts set too high, or other causes of excess current.
F13
Ground
Fault
Cause: A current path to earth ground has been detected at one or more of the drive output terminals.

Solution:

- Check the motor and external wiring to the drive output terminals for a grounded condition.
F15
Load Loss
Cause: Drive output torque current is below [Load Loss Level] for a time period greater than [Load Loss time].

Solution:

- Verify connections between motor and load.
- Verify level and time requirements.
F16
Motor
Thermistor
Cause: Thermistor output is out of range.

Solution:

- Verify that thermistor is connected.
- Motor is overheated. Reduce load.
F17
Input Phase
Loss
Cause: The DC bus ripple has exceeded a preset level.

Solution:

- Check incoming power for a missing phase/blown fuse.
F24
Decel Inhibit
Cause: The drive is not following a commanded acceleration or deceleration because it is attempting to limit bus voltage.

Solution:

- Verify that input voltage is within drive specified limits.
- Verify that system ground impedance follows proper grounding techniques.
- Disable bus regulation and/or add dynamic brake resistor and/or extend deceleration time.
F25
Overspeed
Limit
Cause: Functions such as Slip Compensation or Bus Regulation have attempted to add an output frequency adjustment greater than that programmed in [Overspeed Limit].

Solution: Remove excessive load or overhauling conditions or increase [Overspeed Limit].
F29
Analog
In Loss
Cause: An analog input is configured to fault on signal loss. A signal loss has occurred.
- Configure with [Anlg In X Loss].

Solution:

- Check the parameters.
- Check for broken/loose connections at inputs.
F33
Auto Rstrt
Tries
Cause: Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of [Flt RstRun Tries].
- Enable/Disable with [Fault Config 1].

Solution:

- Correct the cause of the fault and manually clear.
F36
SW
OverCurrent
Cause: Drive output current has exceeded the 1 ms current rating.
- This rating is greater than the 3-second current rating and less than the hardware overcurrent fault level.
- It is typically 200…250% of the drive continuous rating.

Solution:

- Check for excess load, improper DC boost setting. DC brake volts set too high.
- If enabled, check level of flux braking in parameter P549 [Flux Braking %].
F38
Phase U
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F39
Phase V
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F40
Phase W
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F41
Phase
UV Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F42
Phase
UW Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F43
Phase
VW Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F48
Params
Defaulted
Cause: The drive was commanded to write default values to EEPROM.

Solution:

- Clear the fault or cycle power to the drive.
- Program the drive parameters as needed.
F49
Drive
Powerup
No fault is displayed. Used as a Powe r Up Marker in the Fault Queue indicating that the drive power has been cycled.
F51
Flt
QueueCleared
No fault displayed. Used as a marker in the Fault Queue indicating that the clear queue function was performed.
F52
Faults
Cleared
No fault displayed. Used as a marker in the Fault Queue indicating that the fault clear function was performed.
F55
Cntl Bd
Overtemp
Cause: The temperature sensor on the Main Control Board detected excessive heat.

Solution:

- Check Main Control Board fan.
- Check surrounding air temperature.
- Verify proper mounting/ cooling.
F63
Shear Pin
Cause: Programmed [Current Lmt Val] has been exceeded. Enable/Disable with [Fault Config 1].

Solution: Check load requirements and [Current Lmt Val] setting.
F64
Drive
Overload
Cause: Drive rating of 110% for 1 minute or 150% for 3 seconds has been exceeded.

Solution: Reduce load or extend Accel Time.
F69
DB
Resistance
Cause: The resistance of the internal DB unit is out of range.

Solution:

- Replace the resistor.
F70
Power Unit
Cause: One or more of the output transistors were operating in the active region instead of desaturation. This can be caused by excessive transistor current or insufficient base drive voltage.

Solution:

- Check for damaged output transistors.
- Replace drive.
F71…F75
Port 1…5
Adapter
Cause: The communications card has a fault.

Solution:

- Check DPI device event queue and corresponding fault information for the device.
F77
IR Volts
Range
Cause: “Calculate” is the autotune default and the value that is determined by the autotune procedure for IR Drop Volts is not in the range of acceptable values.

Solution:

- Re-enter motor nameplate data.
F78
FluxAmpsRef
Rang
Cause: The value for flux amps determined by the Autotune procedure exceeds the programmed [Motor NP FLA].

Solution:

- Reprogram [Motor NP FLA] with the correct motor nameplate value.
- Repeat Autotune.
F79
Excessive
Load
Cause: Motor did not come up to speed in the allotted time during autotune.

Solution:

- Uncouple load from motor.
- Repeat Autotune.
F80
AutoTune
Aborted
Cause: Autotune function was canceled by the user or a fault occurred.

Solution:

- Restart the procedure.
Port 1…6
DPI Loss
F81…F86
Cause:

- DPI port stopped communicating.
- A SCANport device was connected to a drive operating DPI devices at 500k baud.

Solution:

- If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters, Main Control Board, or complete drive as required.
- Check HIM connection.
- If an adapter was intentionally disconnected and the [Logic Mask] bit for that adapter is set to “1”, this fault occurs. To disable this fault, set the [Logic Mask] bit for the adapter to “0.”
F87
IXo
VoltageRange
Cause: Voltage calculated for motor inductive impedance exceeds 25% of [Motor NP Volts].

Solution:

- Check for proper motor sizing.
- Check for correct programming of [Motor NP Volts], parameter 41.
- Additional output impedance can be required.
F90
Encoder
Quad Err
Cause: Both encoder channels changed state within one clock cycle.

Solution:

- Check for externally induced noise.
- Replace encoder.
F91
Encoder
Loss
Cause: One or both encoder channel signals is missing.

Solution:

- Check Wiring.
- Replace encoder.
F93
Hardware
Fault
Cause: Hardware enable is disabled (jumpered high) but logic pin is still low.

Solution:

- Check jumper.
- Replace Main Control Board.
F100
Parameter
Chksum
Cause: The checksum read from the board does not match the checksum calculated.

Solution:

- Restore defaults.
- Reload User Set if used.
F101
UserSet1
Chksum
Cause: The checksum read from the user set does not match the checksum that is calculated.

Solution:

- Re-save user set.
F102
UserSet2
Chksum
Cause: The checksum read from the user set does not match the checksum that is calculated.

Solution:

- Re-save user set.
F103
UserSet3
Chksum
Cause: The checksum read from the user set does not match the checksum that is calculated.

Solution:

- Re-save user set.
F104
Pwr Brd
Chksum1
Cause: The checksum read from the EEPROM does not match the checksum that is calculated from the EEPROM data.

Solution:

- Clear the fault or cycle power to the drive.
F105
Pwr Brd
Chksum2
Cause: The checksum read from the board does not match the checksum that is calculated.

Solution:

- Cycle power to the drive.
- If problem persists, replace drive.
F106
Incompact
MCB-PB
Cause: Drive rating information that is stored on the power board is incompatible with the main control board.

Solution: Load compatible version files into drive.
F107
Replaced
MCB-PB
Cause: Main Control Board was replaced and parameters were not programmed.

Solution:

- Restore defaults.
- Reprogram parameters.
F108
Anlg Cal
Chksum
Cause: The checksum read from the analog calibration data does not match the checksum that is calculated.

Solution:

- Replace the drive.
F111
Enable
Hardware
Cause: & solution:

1. Safe-Off board is not installed and pins 3 and 4 of the Safe-Off Connector are not jumpered.
- Install Safe-Off board or jumper pins 3 and 4.

2. If Safe-Off board is installed, verify that the hardware enable jumper is removed.
- Locate and remove the enable jumper on the main control board. Refer to DriveGuard Safe-Off Option (Series B) for PowerFlex 40P and PowerFlex 70 AC Drives, publication PFLEX-UM003, for instructions and location.

3. Safe-Off board has failed.
- Replace Safe-Off board.

4. Hardware enable circuitry failed.
- Replace control board.
F112
Power Down
Csum
Cause: EEPROM data is corrupt on drive powerup.

Solution:

- Clear the fault or cycle power to the drive.
F900…
F930
Fatal Faults
Cause: Diagnostic code indicating a drive malfunction.

Solution:

- Cycle power.
- Replace Main Control Board.
- Contact Tech Support.

How to Clear & Reset Allen-Bradley PowerFlex 70 Drive Faults

  1. Keypad / HIM Reset: Press the red Stop / Reset key on the Human Interface Module (HIM). If the drive is in remote control mode, ensure active start/run signals are de-asserted.
  2. Digital Input Reset (DI): If terminal parameter 361, 362, 363, 364, 365, or 366 [Dig Inx Sel] is set to 1 "Clear Fault", cycle the designated digital input terminal.
  3. Connected Components Workbench (CCW) / DriveExplorer: Connect through the integral DPI communication port using a 1203-USB interface converter, navigate to the fault diagnostics window, and click “Clear Faults”.
  4. Fieldbus Network Control Word: Assert Bit 3 (Clear Faults) of the Logic Command Word through the installed DPI communication adapter (e.g., 20-COMM-E EtherNet/IP, 20-COMM-D DeviceNet).
  5. Mains Power Cycle: Shut off incoming 3-phase line power. Wait at least 5 minutes until the LCD screen completely turns off and the internal DC bus capacitors have fully discharged, then restore line power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] before removing power terminal covers, inspecting motor output terminals U/T1, V/T2, W/T3, or working on PowerFlex 70 drive hardware.