Allen-Bradley PowerFlex 400 drive

Home / Allen-Bradley / Allen-Bradley PowerFlex 400 drive

Allen-Bradley PowerFlex 400 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, HVAC fan and pump trip alarms, root causes, and troubleshooting procedures for Rockwell Automation Allen-Bradley PowerFlex 400 drives. Search or filter through the complete fault directory below.

Fan & Pump HVAC Drive Power: 2.2 to 250 kW (3.0 to 350 HP) Embedded Modbus RTU / Metasys N2 / P1
Power Range 2.2 – 250 kW (3 – 350 HP)
Supply Voltage 200–240V / 380–480V AC (3-Phase)
Control Modes V/Hz (Custom Variable Torque)
Operator Interface Multi-Line Alphanumeric LCD Keypad

Complete Allen-Bradley PowerFlex 400 Fault Code Directory

Use the search box in the table below to quickly find your fault code (e.g., search F004, F005, F012, or OverCurrent).

Fault CodesCause & Solutions
F2
Auxiliary
Input
Cause : Auxiliary input interlock is open.

Solution:

- Check remote wiring.
- Verify communications programming for intentional fault.
F3
Power Loss
Cause: Excessive DC Bus voltage ripple.

Solution:

- Monitor the incoming AC line for low voltage or line power interruption.
- Check input fuses.
- Reduce load.
F4
UnderVoltage
Cause: DC bus voltage fell below the min value.

Solution: Monitor the incoming AC line for low voltage or line power interruption.
F5
OverVoltage
Cause: DC bus voltage exceeded max value.

Solution:

- Monitor the AC line for high line voltage or transient conditions.
- Bus overvoltage can also be caused by motor regeneration.
- Extend the decel time or install dynamic brake option.
F6
Motor
Stalled
Cause: Drive is unable to accelerate or decelerate motor.

Solution:

- Increase P039...A147 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A179 [Current Limit 1].
- Check for overhauling load.
F7
Motor
Overload
Cause: Internal electronic overload trip.

Solution:

- An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current].
- Verify A170 [Boost Select] setting.
F8
Heatsink
OvrTmp
Cause: Heatsink/Power Module temperature exceeds a predefined value.

Solution:

- Check for blocked or dirty heatsink fins. Verify that ambient temperature has not exceeded the rated ambient temperature.
- Check fan.
F12
HW
OverCurrent
Cause: The drive output current has exceeded the hardware current limit.

Solution:

- Check programming.
- Check for excess load, improper A170 [Boost Select] setting, DC brake volts set too high or other causes of excess current.
F13
Ground
Fault
Cause: A current path to earth ground has been detected at one or more of the drive output terminals.

Solution:

- Check the motor and external wiring to the drive output terminals for a grounded condition.
F15
Load Loss
Cause: Output current has dropped below the level set in A184 [Load Loss Level].

Solution:

- Check for load loss (i.e., a broken belt).
F17
Input Phase
Loss
Cause: Excessive DC bus ripple voltage detected. See d329 [DC Bus Ripple V].

Solution:

- Check incoming power for a missing phase or blown fuse. If drive is used intentionally with single phase input, apply output derating to 35% actual drive rating.
F29
Analog Input
Loss
Cause: An analog input is configured to fault on signal loss. A signal loss has occurred.
- Configure with T072 [Anlalog In Loss].

Solution:

- Check parameters.
- Check for broken/loose connections at inputs.
F32
Fan Fdbck
Loss
Cause: A loss of cooling fan feedback has been detected. (Frames E and F only)

Solution:

- Make sure cooling fans are clear of debris and spinning freely. Replace fan if necessary.
F33
Auto Rstrt
Tries
Cause: Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of A163 [Auto Rstrt Tries].

Solution:

- Correct the cause of the fault and manually clear.
F38
Phase U
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F39
Phase V
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F40
Phase W
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F41
Phase
UV Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F42
Phase
UW Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F43
Phase
VW Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F48
Params
Defaulted
Cause: The drive was commanded to write default values to EEPROM.

Solution:

- Clear the fault or cycle power to the drive.
- Program the drive parameters as needed.
F63
SW
OverCurrent
Cause: Programmed A183 [SW Current Trip] has been exceeded.

Solution:

- Check load requirements and A183 [SW Current Trip] setting.
F64
Drive
Overload
Cause: Drive rating of 110% for 1 minute or 150% for 3 seconds has been exceeded.

Solution: Reduce load or extend Accel Time.
F70
Power Unit
Cause: Failure has been detected in the drive power section.

Solution:

- Check that max ambient temperature has not been exceeded.
- Cycle power.
- Replace drive if fault cannot be cleared.
F71
Net Loss
Cause: The communication network has faulted.

Solution:

- Cycle power.
- Check communications cabling.
- Check network adapter setting.
- Check external network status.
F81
Comm Loss
Cause: RS485 (DSI) port stopped communicating.

Solution:

- Check RS485 wiring connection.
- Check if a communications adapter or HIM was disconnected.
- Increase C106 [Comm Loss Time] to an appropriate time for application.
- Change C105 [Comm Loss Action] to a value other than “0” (fault), if appropriate for the application.
F94
Function
Loss
Cause: P036 [Start Source] is set to setting 6.
- The input to terminal 01 has been opened.

Solution:

- Close input to terminal 01 and re- start the drive.
F100
Parameter
Chksum
Cause: The checksum read from the board does not match the checksum calculated.

Solution: Set P041 [Reset To Defalts] to option 1 “Reset Defaults”.
F122
I/O Board
Fail
Cause: Failure has been detected in the drive control and I/O section.

Solution:

- Cycle power.
- Replace drive if fault cannot be cleared.

How to Clear & Reset Allen-Bradley PowerFlex 400 Faults

  1. Keypad Reset: Press the red Stop / Reset key on the multi-line LCD control panel. Ensure the run command from BAS/HVAC controls is removed if parameter P037 [Stop Mode] requires a stop cycle before restart.
  2. Digital Input Reset: If one of the digital inputs (terminals 05 through 08, configured in parameters A051 – A054) is set to Option 7 “Clear Fault”, momentary contact closure to digital common (terminal 04) will reset active faults.
  3. Building Automation System (BAS) Reset: Clear faults remotely by setting the Fault Reset command bit in the control word via embedded RS-485 protocols (Modbus RTU, Johnson Controls Metasys N2, or Siemens FLN P1).
  4. Connected Components Workbench (CCW): Connect via the RJ45 DSI communication port using a 1203-USB serial converter, launch CCW or DriveExplorer, and select “Clear Faults” in the online diagnostics menu.
  5. Main AC Power Cycle: Disconnect the incoming 3-phase mains disconnect switch. Wait for the LCD screen backlight and all status LEDs to extinguish completely (allow at least 5 minutes for bus capacitors to discharge), then restore power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous electrical energy remains stored in the intermediate DC bus capacitors after line power is disconnected. Using a calibrated digital multimeter set to 1000V DC, verify that voltage across terminals +DC and -DC measures strictly below 50 VDC before servicing power wiring, motor leads, or internal drive assemblies.