Allen-Bradley PowerFlex 700 drive

Home / Allen-Bradley / Allen-Bradley PowerFlex 700 drive

Allen-Bradley PowerFlex 700 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Allen-Bradley PowerFlex 700 architecture-class AC drive series. Search or filter through the complete fault code directory below.

Architecture-Class AC Drive Power: 0.37 to 132 kW (0.5 to 200 HP) Vector Control with FORCE™ Technology
Power Range 0.37 – 132 kW (0.5 – 200 HP)
Supply Voltage 200–690V AC (3-Phase)
Control Modes V/Hz, Sensorless Vector & FORCE™ Vector
Operator Interface LCD HIM / CCW / DPI Network

Complete Allen-Bradley PowerFlex 700 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F3, F12, F24, or Overcurrent).

Fault CodesCause & Solutions
F2
Auxiliary
Input
Cause : Auxiliary input interlock is open.

Solution:

- Check remote wiring.
- Verify communications programming for intentional fault.
F3
Power Loss
Cause: Excessive DC Bus voltage ripple.

Solution:

- Monitor the incoming AC line for low voltage or line power interruption.
- Check input fuses.
- Reduce load.
F4
UnderVoltage
Cause: DC bus voltage fell below the min value.

Solution: Monitor the incoming AC line for low voltage or line power interruption.
F5
OverVoltage
Cause: DC bus voltage exceeded max value.

Solution:

- Monitor the AC line for high line voltage or transient conditions.
- Bus overvoltage can also be caused by motor regeneration.
- Extend the decel time or install dynamic brake option.
F7
Motor
OverLoad
Cause:

- Internal electronic overload trip.
- Enable/Disable with [Fault Config 1].

Solution:

- An excessive motor load exists.
- Reduce load so drive output current does not exceed the current set by [Motor NP FLA].
F8
Heatsink
OvrTmp
Cause: Heatsink/Power Module temperature exceeds a predefined value.

Solution:

- Check for blocked or dirty heatsink fins. Verify that ambient temperature has not exceeded the rated ambient temperature.
- Check fan.
F9
Trnsistr
OvrTemp
Cause: Output transistors have exceeded their maximum operating temperature.

Solution:

- Verify that maximum ambient temperature has not been exceeded.
- Check fan.
- Check for excessive load.
F12
HW
OverCurrent
Cause: The drive output current has exceeded the hardware current limit.

Solution:

- Check output of drive or motor for shorts.
- Check programming.
- Check for excess load, improper DC boost setting, DC brake volts set too high, or other causes of excess current.
F13
Ground
Fault
Cause: A current path to earth ground has been detected at one or more of the drive output terminals.

Solution:

- Check the motor and external wiring to the drive output terminals for a grounded condition.
F15
Load Loss
Cause: Drive output torque current is below [Load Loss Level] for a time period greater than [Load Loss time].

Solution:

- Verify connections between motor and load.
- Verify level and time requirements.
F16
Motor
Thermistor
Cause: Thermistor output is out of range.

Solution:

- Verify that thermistor is connected.
- Motor is overheated. Reduce load.
F17
Input Phase
Loss
Cause: The DC bus ripple has exceeded a preset level.

Solution:

- Check incoming power for a missing phase/blown fuse.
F20
TorqPrv
Spd Band
Cause: Difference between [Commanded Speed] and [Encoder Speed] has exceeded the level set in [Spd Dev Band] for a time period greater than [Spd Band Integrat].

Solution:

- Check wiring between drive and motor.
- Check release of mechanical brake.
F21
Output
PhaseLoss
Cause: Current in one or more phases has been lost or remains below a preset level.

Solution:

- Check the drive and motor wiring.
- Check for phase-to-phase continuity at the motor terminals.
- Check for disconnected motor leads.
F24
Decel Inhibit
Cause: The drive is not following a commanded acceleration or deceleration because it is attempting to limit bus voltage.

Solution:

- Verify that input voltage is within drive specified limits.
- Verify that system ground impedance follows proper grounding techniques.
- Disable bus regulation and/or add dynamic brake resistor and/or extend deceleration time.
F25
OverSpeed
Limit
Cause: Functions such as Slip Compensation or Bus Regulation have attempted to add an output frequency adjustment greater than that programmed in [Overspeed Limit].

Solution:

- Remove excessive load or overhauling conditions or increase [Overspeed Limit].
F29
Analog
In Loss
Cause: An analog input is configured to fault on signal loss. A signal loss has occurred.
- Configure with [Anlg In 1, 2 Loss].

Solution:

- Check the parameters.
- Check for broken/loose connections at inputs.
F33
Auto Rstrt
Tries
Cause: Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of [Flt RstRun Tries].
- Enable/Disable with [Fault Config 1].

Solution:

- Correct the cause of the fault and manually clear.
F36
SW
OverCurrent
Cause: Drive output current has exceeded the 1 ms current rating.
- This rating is greater than the 3-second current rating and less than the hardware overcurrent fault level.
- It is typically 200…250% of the drive continuous rating.

Solution:

- Check for excess load, improper DC boost setting. DC brake volts set too high.
- If enabled, check level of flux braking in parameter P549 [Flux Braking %].
F38
Phase U
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F39
Phase V
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F40
Phase W
to Gnd
Cause: A phase to ground fault has been detected between the drive and motor in this phase.

Solution:

- Check the wiring between the drive and motor.
- Check motor for grounded phase.
- Replace drive if fault cannot be cleared.
F41
Phase
UV Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F42
Phase
UW Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F43
Phase
VW Short
Cause: Excessive current has been detected between these two output terminals.

Solution:

- Check the motor and drive output terminal wiring for a shorted condition.
- Replace drive if fault cannot be cleared.
F48
Params
Defaulted
Cause: The drive was commanded to write default values to EEPROM.

Solution:

- Clear the fault or cycle power to the drive.
- Program the drive parameters as needed.
F49
Drive
Powerup
No fault is displayed. Used as a Powe r Up Marker in the Fault Queue indicating that the drive power has been cycled.
F51
Flt
QueueCleared
No fault displayed. Used as a marker in the Fault Queue indicating that the clear queue function was performed.
F52
Faults
Cleared
No fault displayed. Used as a marker in the Fault Queue indicating that the fault clear function was performed.
F55
Cntl Bd
Overtemp
Cause: The temperature sensor on the Main Control Board detected excessive heat.

Solution:

- Check Main Control Board fan.
- Check surrounding air temperature.
- Verify proper mounting/ cooling.
F63
Shear Pin
Cause: Programmed [Current Lmt Val] has been exceeded. Enable/Disable with [Fault Config 1].

Solution: Check load requirements and [Current Lmt Val] setting.
F64
Drive
Overload
Cause: Drive rating of 110% for 1 minute or 150% for 3 seconds has been exceeded.

Solution: Reduce load or extend Accel Time.
F69
DB
Resistance
Cause: The resistance of the internal DB unit is out of range.

Solution:

- Replace the resistor.
F70
Power Unit
Cause: One or more of the output transistors were operating in the active region instead of desaturation. This can be caused by excessive transistor current or insufficient base drive voltage.

Solution:

- Check for damaged output transistors.
- Replace drive.
F71…F75
Port 1…5
Adapter
Cause: The communications card has a fault.

Solution:

- Check DPI device event queue and corresponding fault information for the device.
F77
IR Volts
Range
Cause: “Calculate” is the autotune default and the value that is determined by the autotune procedure for IR Drop Volts is not in the range of acceptable values.

Solution:

- Re-enter motor nameplate data.
F78
FluxAmpsRef
Rang
Cause: The value for flux amps determined by the Autotune procedure exceeds the programmed [Motor NP FLA].

Solution:

- Reprogram [Motor NP FLA] with the correct motor nameplate value.
- Repeat Autotune.
F79
Excessive
Load
Cause: Motor did not come up to speed in the allotted time during autotune.

Solution:

- Uncouple load from motor.
- Repeat Autotune.
F80
AutoTune
Aborted
Cause: Autotune function was canceled by the user or a fault occurred.

Solution:

- Restart the procedure.
Port 1…5
DPI Loss
F81…F85
Cause:

- DPI port stopped communicating.
- A SCANport device was connected to a drive operating DPI devices at 500k baud.

Solution:

- If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters, Main Control Board, or complete drive as required.
- Check HIM connection.
- If an adapter was intentionally disconnected and the [Logic Mask] bit for that adapter is set to “1”, this fault occurs. To disable this fault, set the [Logic Mask] bit for the adapter to “0.”
F87
IXo
VoltageRange
Cause: Voltage calculated for motor inductive impedance exceeds 25% of [Motor NP Volts].

Solution:

- Check for proper motor sizing.
- Check for correct programming of [Motor NP Volts], parameter 41.
- Additional output impedance can be required.
F88
Software
Fault
Cause: Microprocessor handshake error.

Solution:

- Replace Main Control Board.
F89
Software
Fault
Cause: Microprocessor handshake error.

Solution:

- Replace Main Control Board.
F90
Encoder
Quad Err
Cause: Both encoder channels changed state within one clock cycle.

Solution:

- Check for externally induced noise.
- Replace encoder.
F91
Encoder
Loss
Cause: Requires differential encoder. One of the 2 encoder channel signals is missing.

Solution:

- Check Wiring.
- Replace encoder.
F92
Pulse
In Loss
Cause: Z Channel is selected as a pulse input and no signal is present.

Solution:

- Check wiring.
- Replace pulse generator.
F93
Hardware
Fault
Cause: Hardware enable is disabled (jumpered high) but logic pin is still low.

Solution:

- Check jumper.
- Replace Main Control Board.
F100
Parameter
Chksum
Cause: The checksum read from the board does not match the checksum calculated.

Solution:

- Restore defaults.
- Reload User Set if used.
F101
UserSet1
Chksum
Cause: The checksum read from the user set does not match the checksum that is calculated.

Solution:

- Re-save user set.
F102
UserSet2
Chksum
Cause: The checksum read from the user set does not match the checksum that is calculated.

Solution:

- Re-save user set.
F103
UserSet3
Chksum
Cause: The checksum read from the user set does not match the checksum that is calculated.

Solution:

- Re-save user set.
F104
Pwr Brd
Chksum1
Cause: The checksum read from the EEPROM does not match the checksum that is calculated from the EEPROM data.

Solution:

- Clear the fault or cycle power to the drive.
F105
Pwr Brd
Chksum2
Cause: The checksum read from the board does not match the checksum that is calculated.

Solution:

- Cycle power to the drive.
- If problem persists, replace drive.
F106
Incompact
MCB-PB
Cause: Drive rating information that is stored on the power board is incompatible with the main control board.

Solution: Load compatible version files into drive.
F107
Replaced
MCB-PB
Cause: Main Control Board was replaced and parameters were not programmed.

Solution:

- Restore defaults.
- Reprogram parameters.
F108
Anlg Cal
Chksum
Cause: The checksum read from the analog calibration data does not match the checksum that is calculated.

Solution:

- Replace the drive.
F120
I/O
Mismatch
Cause: I/O board configuration not the same from last time drive was powered up.

Solution:

- Verify configuration.
F121
I/O Comm
Loss
Cause: I/O Board lost communications with the Main Control Board.

Solution:

- Check connector.
- Check for induced noise.
- Replace I/O board or Main Control Board.
F122
I/O
Failure
Cause:

- I/O was detected, but failed the powerup sequence.
- I/O Board is separate in Standard & integral in Vector Control.

Solution:

- Replace I/O Board (Standard Control) or Main Control Board (Vector Control).
F130
Hardware
Fault
Cause: Gate array load error.

Solution:

- Cycle power.
- Replace Main Control Board.
F131
Hardware
Fault
Cause: Dual port failure.

Solution:

- Cycle power.
- Replace Main Control Board.
F109
NVS I/O
Checksum
Cause: EEprom checksum error.

Solution:

- Cycle power and repeat function.
- Replace Main Control Board.
F110
NVS I/O
Failure
Cause: EEprom I/O error.

Solution:

- Cycle power and repeat function.
- Replace Main Control Board.

How to Clear & Reset Allen-Bradley PowerFlex 700 Drive Faults

  1. HIM (Keypad) Reset: Press the red Stop button on the full numeric or LCD Human Interface Module (HIM). If the fault condition is no longer active, the drive clears the fault and returns to a “Ready” state.
  2. Digital Input Reset (Clear Fault): Momentarily trigger a control terminal configured to option 4 (“Clear Fault”) via parameters 361–366 [Dig In 1..6 Sel].
  3. Drive Software (CCW / DriveExecutive): Connect via DPI peripheral interface (or 1203-USB converter), open Connected Components Workbench (CCW) or DriveExecutive, open the Diagnostics/Faults view, and select “Clear Fault”.
  4. Network Logic Command Word: Pulse the Fault Reset bit (Bit 3) from `0` to `1` in the Logic Command Word across your active fieldbus communication adapter (EtherNet/IP, ControlNet, DeviceNet, or RIO via 20-COMM).
  5. Auto-Restart Configuration: For non-critical trips, enable parameter 174 [Auto Rstrt Tries] and set parameter 175 [Auto Rstrt Delay] to configure automated fault recovery attempts.
  6. Power Cycle: Disconnect AC line input power to the drive. Wait until the HIM display powers down completely and all internal LED indicators turn off (allow at least 5 minutes for the DC bus capacitors to discharge safely below 50VDC), then re-apply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] before inspecting power connections, servicing dynamic brake resistors, or touching output terminals U/T1, V/T2, and W/T3 on the PowerFlex 700 drive.