Fuji Alpha 5 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, alarm causes, and step-by-step troubleshooting procedures for the Fuji Electric Alpha 5 and Alpha 5 Smart AC servo drive series. Search or filter through the complete alarm code directory below.
Power Range
0.05 – 7.0 kW (50W – 7 kW)
Supply Voltage
1-ph / 3-ph 200–230V AC
Control Modes
Position / Speed / Torque Control
Operator Interface
7-Segment LED / Alpha 5 PC Loader
Complete Fuji Alpha 5 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type oC1, oL1, Et, or Encoder).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
oC1, oC2 Overcurrent The output current of the servo amplifier exceeds the rated value. oC1: Direct detection by internal transistor. oC2: Indirect detection with software. | Cause: Wrong servomotor output wiring Remedy: Correct the wiring of power cables (U, V and W). Cause: Short circuit or grounding fault in servomotor output wiring Remedy: Check cables visually or through continuity check and replace the defective cable. Cause: Servomotor insulation fault Remedy: Measure the insulation resistance. (Several MΩ or over to ground). Cause: Failure of servomotor Remedy: Measure the resistance across cables. (Several Ω between cables). Cause: Incorrect resistance of regenerative resistor Remedy: Replace with the regenerative resistor within the rating. Cause: Current imbalance caused by an encoder fault Remedy: Replace the servomotor. Cause: Unconnected grounding cable Remedy: Connect the grounding cable. |
oS Overspeed The rotation speed of the servomotor exceeds 1.1 times the maximum speed. | Cause: Wrong servomotor output wiring Remedy: Correct the wiring of power cables (U, V and W). Cause: The rotation speed of the servomotor overshoots. Remedy: Check the speed waveform during acceleration with the PC Loader or similar and take the following countermeasures:
|
Hu Overvoltage The DC voltage inside the servo amplifier exceeds the upper limit. (Approx over 420 V). | Cause: The source voltage is too high (immediately after power-on). Remedy:
Cause: Unconnected external regenerative resistor or wrong wiring Remedy:
Cause: Broken regenerative transistor Remedy: Replace the servo amplifier. |
Et1, Et2 Encoder Trouble There is a fault in the encoder built in the servomotor. Et1: Single revolution position detection fault. Et2: Encoder memory data reading fault. | Cause: Fault in data sent from encoder Remedy: Use shielded cables to eliminate noise effects. Cause: Failure of encoder Remedy: Replace the servomotor. |
ct Circuit Trouble There is a fault in the source control power voltage inside the servo amplifier. There may be a failure in the internal circuit. | Cause: Failure of servo amplifier Remedy: Turn the power off then on again. If restoration is not obtained, replace the servo amplifier. |
dE Memory Error The parameter data stored in the servo amplifier is damaged. | Cause: Failure of stored data Remedy:
Cause: The parameter overwriting frequency has exceeded 100,000 cycles. Remedy: Replace the servo amplifier. (Store frequently overwritten parameters to RAM). |
Fb Fuse Blown The fuse in the servo amplifier main circuit is disconnected. | Cause: The fuse is disconnected. Remedy: Replace the servo amplifier. Note: Customers are not allowed to replace the fuse. Contact us before turning on the power. |
cE Motor Combination Error The capacity and model of the servo amplifier do not agree with those of the connected servomotor. | Cause: The capacity and model of the servo amplifier do not agree with those of the servomotor. Remedy: Check the capacity and model of the servomotor and those of the servo amplifier. |
tH Regenerative Resistor Overheat The regeneration handling transistor built in the servo amplifier is overheated. | Cause: High source voltage (immediately after power-on) Remedy:
Cause: Too large regeneration power Remedy:
|
Ec Encoder Communication Error Communications with the internal encoder of the servomotor fails. | Cause: Error in encoder serial communications Remedy: Check cables visually and through continuity check and correct faults. Cause: Broken wire or poor contact Remedy:
|
ctE Cont (Control signal) Error There is duplication in allocation of sequence input terminals of the servo amplifier. | Cause: The same input signal is allocated to two or more terminals. Remedy: Do not specify the same number among CONT signal settings. |
oL1, oL2 Overload oL1: Alarm that detects failures such as a locked shaft instantaneously. oL2: The effective torque exceeds the allowable limit of the servomotor. | Cause: The servomotor fails to rotate mechanically. Remedy:
Cause: The mechanical system is too heavy against the servomotor capacity. Remedy:
Cause: The acceleration/deceleration frequency and operation frequency are too high. Remedy: Increase the cycle time and decrease the operation frequency. Cause: Servo amplifier is damaged. Remedy: Replace the servo amplifier. |
LuP Main Power Undervoltage The power supplied to the servo amplifier falls below the minimum specification voltage limit. | Cause: The source voltage drops due to momentary power failure or similar. Remedy:
|
rH1 Internal Regenerative Resistor Overheat The power consumption of the regenerative resistor built in the servo amplifier exceeds the upper limit. | Cause:
Remedy:
|
rH2 External Regenerative Resistor Overheat The external regenerative resistor overheat signal (normally closed contact signal) has worked (was open). | Cause:
Remedy:
|
rH3 Regenerative Transistor Error The regeneration handling transistor built in the servo amplifier is damaged. | Cause: The regenerative transistor is short circuited or damaged. Remedy:
|
rH4 Inrush Current Suppression Circuit Trouble The circuit inside the servo amplifier which suppresses the inrush current generated at power-on may be broken. | Cause:
Remedy:
|
oF Deviation Overflow A position deviation amount equivalent to servomotor revolutions specified in PA2_69 is accumulated inside the servo amplifier. | Cause:
Remedy:
|
AH Amplifier Overheat The temperature of the servo amplifier has exceeded the allowable limit. | Cause:
Remedy:
|
EH Encoder Overheat The encoder inside the servomotor is overheated exceeding the allowable temperature. | Cause:
Remedy:
|
dL1 dL2 dL3 Absolute Data Lost The absolute data of the encoder is lost. | Cause:
Remedy:
|
AF Multi-turn Data Over Flow Rotation of the output shaft of the servomotor exceeds the range between -32766 and 32765. | Cause: Excessive servomotor revolutions. Remedy:
|
iE Initial Error The initial position inside the encoder is not established. | Cause:
Remedy:
|
How to Clear & Reset Fuji Alpha 5 Drive Faults
- Keypad Reset: Press and hold the reset / navigation key on the built-in front keypad (or optional handheld servo operator). Ensure the servo-on (S-ON) input signal is turned OFF before resetting.
- Digital Input Reset (RST): Momentarily close the digital input allocated to the alarm reset signal (RST) on connector CN1 to clear latching alarms.
- Alpha 5 PC Loader: Connect a PC via USB or RS-485 interface, launch the Fuji Alpha 5 Loader software suite, and click “Alarm Reset” on the real-time status monitor.
- Fieldbus / Modbus RTU: Send an alarm reset command across Modbus RTU or SX-bus motion network by toggling the dedicated reset control bit from
0to1. - Power Cycle: Switch off the main circuit power supply (L1, L2, L3) and control power (L1C, L2C). Wait until the 7-segment display and CHARGE LED turn off completely (approx. 5 minutes) before turning power back on.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated DC voltmeter that the intermediate DC bus voltage measures strictly below 25V DC across main circuit terminals [P(+)] and [N(-)] before inspecting servo motor power leads, encoder wiring, or terminal blocks U, V, and W on the Fuji Alpha 5 servo amplifier.