Danfoss MSD510 Servo Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and diagnostic procedures for the Danfoss VLT® Multiaxis Servo Drive MSD 510 system (PSM 510, SDM 511, SDM 512). Search or filter through the complete diagnostic directory below.

VLT® FlexMotion™ System Power: Up to 30 kW (Parallel to 60 kW) Integrated Safe Torque Off (STO)
Power Range Up to 30 kW (1.5–30 A RMS/axis)
Supply Voltage 400–480V AC / 600V DC Link
Control Modes Field Oriented Control (FOC Servo)
Communication EtherCAT / POWERLINK / PROFINET IRT

Complete Danfoss MSD510 Drive Fault Code Directory

Use the search box in the table below to quickly find your servo alarm or warning (e.g., type AL01, AL03, Overcurrent, or Feedback).

Fault Code and MeaningCause and Remedy
0x1000 / 0x100

Generic application error

Cause:


Generic application error.



Remedy:



  • Check application settings and logs.

  • Restart the system.


0x2310 / 0x101

Overcurrent on output

Cause:


Overcurrent on output.



Remedy:



  • Check motor cables for short circuits.

  • Check motor insulation.

  • Check if the motor load is too high.


0x2311 / 0x15F

High current overload

Cause:


High current overload error.



Remedy:



  • Reduce load on the motor.

  • Check drive sizing relative to the load.


0x2312 / 0x160

I²T current overload

Cause:


I²T current overload error. The motor or drive thermal limit has been reached.



Remedy:



  • Allow the system to cool down.

  • Check ventilation and ambient temperature.

  • Reduce continuous load.


0x2313 / 0x161

High power overload

Cause:


High power overload error.



Remedy:



  • Check system power requirements.

  • Verify power supply stability.


0x2314 / 0x162

PT power overload

Cause:


PT power overload error.



Remedy:



  • Check power supply module load.


0x2320 / 0x163

Short circuit

Cause:


DC overcurrent short circuit error.



Remedy:



  • Check cabling for short circuits.

  • Inspect motor windings.

  • Check internal drive components.


0x2330 / 0x151

Earth leakage

Cause:


Current leaking to earth.



Remedy:



  • Check motor and cable insulation.

  • Check for ground faults in the installation.


0x2391 / 0x125

AUX overcurrent

Cause:


Current on the AUX line has reached the overcurrent limit.



Remedy:



  • Check 24V/AUX supply wiring.

  • Check for short circuits on AUX lines.


0x2393 / 0x127

AUX user limit current

Cause:


Current on the AUX line has reached the user-defined limit for fault.



Remedy:



  • Check load on AUX supply.

  • Adjust user-defined limits if appropriate.


0x2394 / 0x128

AUX user limit current warning

Cause:


Current on the AUX line has reached the user-defined limit for warning.



Remedy:



  • Reduce load on AUX supply to prevent tripping.


0x2395 / 0x129

AUX fuse failure

Cause:


Fuse failure. Current or voltage is above the limit on the AUX line.



Remedy:



  • Check and replace the AUX fuse.

  • Investigate cause of high current/voltage before replacing.


0x2396 / 0x15C

DC Overcurrent trip

Cause:


DC overcurrent trip.



Remedy:



  • Check DC link connections.

  • Check for short circuits in the DC bus.


0x2397 / 0x12B

Output power trip

Cause:


The peak output power of the device is exceeded.



Remedy:



  • Reduce dynamic load peaks.

  • Check acceleration ramps.


0x239B / 0x102

I²T overload motor

Cause:


I²T overload motor error.



Remedy:



  • Motor is overheating or calculated thermal load is too high.

  • Check motor cooling.


0x3130 / 0x12F

Mains phase loss

Cause:


Mains phase loss detected. This occurs when a phase on mains is missing, or when the mains is imbalanced.



Remedy:



  • Check mains supply fuses.

  • Check mains voltage balance.

  • Check input wiring.


0x3210 / 0x103

DC link overvoltage

Cause:


DC-link voltage exceeds limit.



Remedy:



  • Check for regenerative energy from the motor (braking).

  • Check if braking resistor is connected/functioning.

  • Check mains voltage level.


0x3210 / 0x103 (SW)

Overcurrent trip SW

Cause:


DC-link voltage exceeds limit (Software trip).



Remedy:



  • See remedies for DC link overvoltage.


0x3220 / 0x104

DC link undervoltage

Cause:


DC-link voltage below limit in "Operation enabled" state.



Remedy:



  • Check mains supply voltage.

  • Check input fuses.

  • Verify pre-charging circuit.


0x3230 / 0x152

UDC charging error

Cause:


The maximum time limit to charge the DC-link has been exceeded.



Remedy:



  • Check for short circuit in DC link.

  • Check DC link capacitance.


0x3280 / 0x153

DC Link Voltage unbalanced

Cause:


DC-link voltage unbalanced.



Remedy:



  • Check supply phases.

  • Check DC bus connections between modules.


0x3291 / 0x132

UAUX high voltage

Cause:


UAUX above warning limit.



Remedy:



  • Check auxiliary power supply voltage.


0x3292 / 0x133

UAUX overvoltage

Cause:


UAUX above overvoltage limit.



Remedy:



  • Check auxiliary power supply immediately.


0x3293 / 0x134

UAUX low voltage

Cause:


UAUX below warning limit.



Remedy:



  • Check auxiliary power supply load and connections.


0x3294 / 0x135

UAUX undervoltage

Cause:


UAUX below undervoltage limit.



Remedy:



  • Check auxiliary power supply source.


0x3295 / 0x136

UDC high voltage

Cause:


The DC-link voltage is higher than the high-voltage warning limit.



Remedy:



  • Monitor DC bus voltage.

  • Check braking settings.


0x3296 / 0x137

UDC low voltage

Cause:


The DC-link voltage is lower than the low-voltage warning limit.



Remedy:



  • Monitor mains supply stability.


0x3297 / 0x154

UAUX charging error

Cause:


Load error when UAUX is charging. The maximum time limit to charge the AUX line has been exceeded.



Remedy:



  • Disconnect load on AUX line and retry.

  • Check for shorts on AUX line.


0x3298 / 0x165

UDC shutdown error

Cause:


Error when UDC is in shutdown phase.



Remedy:



  • Cycle power to the drive.

  • Contact Danfoss service if persists.


0x3299 / 0x155

UAUX shutdown error

Cause: Error when UAUX is in shut down phase.

Severity: Error | LCP Name: UAUX shtdwn err




Remedy:

  • Check UAUX supply status.


0x329A / 0x156

UAUX undervoltage hardware

Cause: UAUX undervoltage detected by hardware circuit.

Severity: Error | Valid for: PSM 510, DAM 510, ACM 510




Remedy:

  • Check auxiliary voltage supply.

  • Check hardware connections.


0x329B / 0x168

Automated fault reset failure

Cause: Too many auto fault resets have been executed in the intended time interval.

Severity: Trip lock | LCP Name: afr failure




Remedy:

  • Investigate the underlying recurring fault causing the resets.

  • Cycle power to reset the trip lock.


0x4210 / 0x157

Device overtemperature

Cause: Triggered when the maximum temperature of the main device component is exceeded.

PSM: Thyristor rectifier module.

DAM: Maximum temperature of both high side and low side IGBTs.

Severity: Warning, Error | LCP Name: overtemp device




Remedy:

  • Check cooling system and fans.

  • Check for overload conditions.

  • Check ambient temperature.


0x4220 / 0x138

Too low temperature

Cause: The device is too cold to operate.

Severity: Error | LCP Name: low temp device




Remedy:

  • Ensure ambient temperature is within specified operating range.


0x4290 / 0x105

Overtemperature: Power module

Cause: Overtemperature on power module.

Severity: Error | Valid for: SDM 511/SDM 512




Remedy:

  • Check power module cooling.


0x4291 / 0x106

Overtemperature: Control card

Cause: Maximum temperature of control card exceeded.

Severity: Error | LCP Name: overtemp CC




Remedy:

  • Check control cabinet ventilation.


0x4292 / 0x107

Overtemperature: Power card

Cause: Maximum temperature of power card exceeded.

Severity: Warning, error | LCP Name: overtemp PC




Remedy:

  • Check device cooling.


0x4293 / 0x13C

Inrush overtemperature: DC link

Cause: Inrush fault. Too many transitions into state "Operation enabled" in a short time period.

Severity: Error | LCP Name: inrush UDC




Remedy:

  • Limit the frequency of enabling operation.

  • Check DC link connections.


0x4294 / 0x13D

Inrush overtemperature AUX line

Cause: Inrush fault. Too many power-ups of the AUX voltage have occurred within a short time period.

Severity: Error | Valid for: DAM 510




Remedy:

  • Reduce frequency of AUX voltage power cycles.


0x4310 / 0x108

Overtemperature: Motor

Cause: Overtemperature on motor.

Severity: Error | LCP Name: overtemp motor




Remedy:

  • Check motor cooling.

  • Check motor load (overload).

  • Check thermal sensor connection.


0x5112 / 0x109

UAUX undervoltage

Cause: Undervoltage on auxiliary voltage.

Severity: Error, trip lock | Valid for: SDM 511/SDM 512




Remedy:

  • Check auxiliary power supply.


0x5121 / 0x158

Charge switch failure voltage

Cause: Indicates a malfunction of the internal charge circuit.

Severity: Trip lock | LCP Name: Chg switch fail




Remedy:

  • Contact service/support (Internal hardware fault).


0x5530 / 0x10A

EE Checksum Error (parameter missing)

Cause: Missing parameter in internal device configuration.

Severity: Trip lock | LCP Name: config err




Remedy:

  • Re-download configuration or firmware.

  • Contact service if error persists.


0x6320 / 0x10B

Parameter error

Cause: A parameter has an invalid value.

Severity: Trip lock | LCP Name: param err




Remedy:

  • Check parameter settings.

  • Reset parameters to factory default if necessary.


0x6382 / 0x15D

Configuration parameters version error

Cause: Configuration parameter set version mismatch: parameter set is not valid for this device.

Severity: Trip lock | LCP Name: conf par ver




Remedy:

  • Ensure correct parameter set is loaded for the device version.


0x6383 / 0x164

Configuration parameters limits error

Cause: ≥1 parameter in the configuration parameter set is out of limits: the parameter set is not valid for this device.

Severity: Trip lock | LCP Name: conf par lim




Remedy:

  • Check parameter values against allowed limits.


0x6384 / 0x166

Power EEprom configuration error

Cause: The power device Eeprom is corrupt or incompatible with this control board.

Severity: Trip lock | LCP Name: conf par EEPROM




Remedy:

  • Contact service/support (Hardware incompatibility or corruption).


0x7111 / 0x141

Brake chopper failure

Cause: The brake chopper is monitored during operation. A brake failure has been detected by the brake check function.

Severity: Warning, error | Valid for: PSM 510




Remedy:

  • Check brake chopper circuit.

  • Check brake resistor connection.


0x7112 / 0x167

Brake chopper overcurrent

Cause: The brake chopper current exceeds the limit.

Severity: Trip lock | LCP Name: brake ch overcurr




Remedy:

  • Check for short circuit in brake resistor or cable.

  • Check brake resistor resistance value.


0x7181 / 0x142

Brake resistor maximum power limit

Cause: The brake resistor maximum power limit is exceeded.

Severity: Warning, error | LCP Name: brake pwr lim




Remedy:

  • Check application regeneration requirements.

  • Verify brake resistor sizing.


0x7182 / 0x143

Brake resistor user power limit

Cause: The brake resistor power limit is exceeded.

The power transmitted to the brake resistor is calculated as an average value over the last 300 s of run time.

Calculation is based on DC-link voltage and brake resistor value set in parameter 2-16.

Severity: Warning, error | LCP Name: brake usr pwr lim




Remedy:

  • Check load cycle and braking duty.

  • Check parameter 2-16 settings.


0x7183 / 0x159

Brake mains voltage too high

Cause: The brake resistor mains voltage is too high.

Severity: Warning | LCP Name: brake volt high




Remedy:

  • Check mains supply voltage.


0x7320 / 0x10C

Internal position sensor error

Cause: Absolute position sensor error.

Severity: Trip lock | LCP Name: int sensor err




Remedy:

  • Check internal sensor connections (if accessible).

  • Replace unit if hardware failure.


0x7380 / 0x10D

External position sensor error

Cause: External encoder data could not be read.

Severity: Error | LCP Name: ext sensor err




Remedy:

  • Check external encoder connections and cabling.

  • Check encoder power supply.


0x8611 / 0x10E

Following error

Cause: A following error has occurred.

Severity: Warning, error | LCP Name: following err




Remedy:

  • Check control loop tuning.

  • Check for mechanical blocking or high friction.


0x8693 / 0x10F

Homing error on entering homing mode

Cause: Could not enter homing mode (for example velocity not 0).

Severity: Warning | LCP Name: Homing mode fail




Remedy:

  • Ensure motor is stopped before starting homing.


0x8694 / 0x110

Homing error on start homing method

Cause: Could not start homing method (for example drive not in standstill).

Severity: Warning | LCP Name: Homing method fail




Remedy:

  • Ensure drive status allows for homing initiation.


0x8695 (0x111)
Homing error distance

Cause: Homing distance reached.


Remedy:

  • Severity: Warning

  • Check homing parameters and distance settings.

  • LCP Name: Homing distance


0xFF01 (0x112)
Mechanical brake failure

Cause: No brake or wire failure detected.


Remedy:

  • Severity: Trip lock

  • Check mechanical brake wiring.

  • Check brake connection.

  • LCP Name: brake mech fail


0xFF02 (0x113)
Short circuit in mechanical brake control

Cause: Short circuit in brake control.


Remedy:

  • Severity: Trip lock

  • Check for short circuits in the brake cabling.

  • LCP Name: brake mech short


0xFF0A (0x114)
External interface power failure

Cause: External interface power supply failure.


Remedy:

  • Severity: Error

  • Check external power supply connections.

  • LCP Name: ext IF pwr fail


0xFF10 (0x14F)
Communication interrupted

Cause: The fieldbus communication has been interrupted while the device was enabled.


Remedy:

  • Severity: Error

  • Check fieldbus cabling and master.

  • LCP Name: Comm interrupt


0xFF21 (0x145)
Fan feedback inconsistent

Cause: Internal fan fault. Internal fan not running/mounted.


Remedy:

  • Severity: Warning

  • Check if the fan is blocked or disconnected.

  • Replace fan if necessary.

  • LCP Name: fan feedback


0xFF22 (0x15A)
Fan lifetime critical

Cause: The theoretical lifetime of the fan has been exceeded.


Remedy:

  • Severity: Warning

  • Plan to replace the fan.

  • LCP Name: fan lifetime


0xFF60 (0x115)
Timing violation 1

Cause: Internal timing violation detected.


Remedy:

  • Severity: Trip lock

  • Contact Danfoss.

  • LCP Name: timing err 1


0xFF61 (0x116)
Timing violation 2

Cause: Internal timing violation detected.


Remedy:

  • Severity: Trip lock

  • Contact Danfoss.

  • LCP Name: timing err 2


0xFF62 (0x117)
Timing violation 3

Cause: Internal timing violation detected.


Remedy:

  • Severity: Trip lock

  • Contact Danfoss.

  • LCP Name: timing err 3


0xFF63 (0x118)
Timing violation 4

Cause: Internal timing violation detected.


Remedy:

  • Severity: Trip lock

  • Contact Danfoss.

  • LCP Name: timing err 4


0xFF64 (0x119)
Timing violation 5

Cause: Internal timing violation detected.


Remedy:

  • Severity: Trip lock

  • Contact Danfoss.

  • LCP Name: timing err 5


0xFF65 (0x11A)
Timing violation 6

Cause: Internal timing violation detected.


Remedy:

  • Severity: Trip lock

  • Contact Danfoss.

  • LCP Name: timing err 6


0xFF66 (0x168)
Timing violation 7

Cause: Internal timing violation detected.


Remedy:

  • Severity: Trip lock

  • Contact Danfoss.

  • LCP Name: timing err 7


0xFF67 (0x16B)
Timing violation 8

Cause: Internal timing violation detected.


Remedy:

  • Severity: Trip lock

  • Contact Danfoss.

  • LCP Name: timing err 8


0xFF68 (0x16C)
Timing violation 9

Cause: Internal timing violation detected.


Remedy:

  • Severity: Trip lock

  • Contact Danfoss.

  • LCP Name: timing err 9


0xFF70 (0x11B)
Firmware: Package description mismatch

Cause: The firmware found does not match the package description.


Remedy:

  • Severity: Trip lock

  • Check firmware version and package.

  • LCP Name: FW pack err


0xFF71 (0x11C)
Firmware: Power cycle needed

Cause: The firmware update transfer is completed but a power cycle is required before the new firmware is active.


Remedy:

  • Severity: Warning, error

  • Perform a power cycle (Power Off/On).

  • LCP Name: need power cycle


0xFF72 (0x11D)
Firmware: Update started

Cause: Firmware update is in progress. Warning changes to error when an attempt is made to enable the device in this state.


Remedy:

  • Severity: Warning, error

  • Wait for update to complete.

  • Do not enable the device.

  • LCP Name: FW update


0xFF73 (0x15B)
Firmware: Update invalid

Cause: Invalid or corrupted firmware package update. Last valid firmware package has been loaded.


Remedy:

  • Severity: Error

  • Retry firmware update with a valid package.

  • LCP Name: FW upd invalid


0xFF80 (0x11E)
STO active while drive enabled

Cause: STO activated while drive was enabled or tried to enable while STO active.


Remedy:

  • Severity: Error

  • Ensure STO signals are correct before enabling drive.

  • LCP Name: STO active


0xFF81 (0x11F)
STO mismatch

Cause: Dual diagnosis of STO voltage not plausible.


Remedy:

  • Severity: Trip lock

  • Check STO wiring and channels.

  • LCP Name: STO mismatch


0xFF85 (0x120)
P_STO error

Cause: P_STO voltage on the power card exceeds the limits.


Remedy:

  • Severity: Trip lock

  • Check power card supply voltages.

  • LCP Name: P_STO error


0xFF90 (0x121)
Guide value reversed

Cause: Position guide value went backwards while the servo drive was in CAM mode.


Remedy:

  • Severity: Error

  • Check CAM profile generation.

  • LCP Name: guide val rev


0xFF91 (0x122)
Guide value implausible

Cause: Increments between succeeding values too large.


Remedy:

  • Severity: Error

  • Check setpoints and guide value generation.

  • LCP Name: guide val impl


0xFF95 (0x14E)
Sign of life error

Cause: Sign of life error detected.


Remedy:

  • Severity: Error

  • Check communication or internal health.

  • LCP Name: SOL error


How to Clear & Reset Danfoss MSD510 Servo Drive Faults

  1. Fieldbus Motion Controller Reset: Command a Fault Reset over the real-time Ethernet bus (EtherCAT, POWERLINK, or PROFINET IRT) by toggling Bit 7 (Fault Reset) from `0` to `1` in the standard CiA 402 servo drive control word.
  2. Danfoss VLT® Servo Toolbox PC Software: Connect via Ethernet to the service interface, launch the Danfoss VLT® Servo Toolbox commissioning tool, review active module diagnostic logs, and click “Fault Reset”.
  3. Safe Torque Off (STO) Reset: If an STO safety event occurred, re-establish nominal 24V DC to both safety input channels (STO 1 and STO 2) on the affected module before sending a software reset command.
  4. Digital Input Reset (DI): If mapped in the drive configuration parameters, pulse the designated 24V DC digital input terminal on the PSM 510 power supply module or SDM axis module.
  5. Power Cycle (Trip Lock Clearance): For critical hardware faults, switch off the 3-phase AC mains supply to the PSM 510 power supply. Wait for the shared DC-link bus capacitors to fully discharge (minimum 5 minutes, status LEDs unlit) before re-energizing the system.
⚠️ High-Voltage Electrical Safety Warning: Danfoss MSD 510 systems share a common high-voltage intermediate DC bus (approx. 565–680V DC) across the multi-axis backplate. Always wait a minimum of 5 minutes after completely removing AC line power and 24V control power. Confirm with a calibrated multimeter that DC voltage across the shared busbars measures strictly below 50VDC before unclipping modules or touching motor power leads (terminals U, V, W).