Danfoss

Home / Danfoss

Danfoss Drives Fault Codes & Troubleshooting

Complete diagnostic database for 23 Danfoss & VACON drive series. Browse fault codes, alarms, causes, and step-by-step fixes for AC & servo drives. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.

8 VLT Series 5 VACON Series 9 Legacy & Specialty 1 Servo Motion Series

VLT Series AC Drives

8 Models

VACON Series Drives

5 Models

Legacy & Specialty Drives

9 Models

Servo & Motion Drives

1 Model

Most Common Danfoss & VACON Drive Fault Codes

Diagnostic Quick Reference
Danfoss Alarm VACON Code Fault Name Common Root Cause
Alarm 13 F1 Overcurrent Drive peak current limit exceeded due to motor short circuit, mechanical binding, or abrupt acceleration ramp.
Alarm 7 F2 DC Link Overvoltage Regenerative kinetic energy fed back during motor deceleration; verify ramp-down time or braking resistor circuit.
Alarm 8 F9 DC Link Undervoltage Line voltage dip, open circuit on incoming mains supply, or damaged intermediate pre-charge contactor.
Alarm 14 F3 Ground / Earth Fault Current leakage from motor phases to earth; inspect motor cable shielding, terminal dampness, or stator insulation.
Alarm 9 F11 Inverter Overload Continuous operation exceeding 100% rated thermal capacity; verify load sizing and parameter group 14 derating.
Alarm 4 F10 Mains Phase Loss Missing phase, blown line-side fuse, or severe phase supply imbalance (>3%) on incoming terminals L1, L2, L3.

How to Clear & Reset Danfoss & VACON Faults

  1. LCP Keypad Reset: Press the yellow or red [Reset] key directly on the Local Control Panel (or [Back/Reset] on VACON keypads).
  2. Digital Input Pulse: Send a 24VDC pulse to the digital input configured for Reset (default Terminal 27 or Terminal 19, Parameter 5-1x).
  3. Setup Software Interface: Connect via USB or Fieldbus and trigger the fault acknowledge button inside Danfoss MCT 10 or VACON Live.
  4. Mains Power Cycle: Power down the 3-phase line supply, wait until the control panel display goes completely blank (minimum 4–15 minutes depending on frame size), and reapply power.
⚠️ High-Voltage Safety Warning: Intermediate circuit DC bus capacitors remain charged at fatal voltage levels after mains disconnection. Wait at least 4 to 15 minutes (or 20 minutes for high-power frames D, E, and F) and verify with a calibrated DC voltmeter across DC bus terminals (+/-) that the voltage is under 50VDC before handling internal connections.