Danfoss FC280 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Danfoss VLT® Midi Drive FC 280 compact industrial series. Search or filter through the complete alarm directory below.
Power Range
0.37 – 22 kW (0.5 – 30 HP)
Supply Voltage
200–240V / 380–480V AC
Control Modes
VVC+ & U/f (Induction & PM)
Operator Interface
Numeric LCP 21 / Graphical LCP 102
Complete Danfoss FC280 Drive Fault Code Directory
Use the search box in the table below to quickly find your alarm code (e.g., type Alarm 13, Alarm 16, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 2 Live zero error | Cause: Signal on terminal 53 or 54 is less than 50% of value set in parameter 6-10 Terminal 53 Low Voltage, parameter 6-12 Terminal 53 Low Current, parameter 6-20 Terminal 54 Low Voltage, and parameter 6-22 Terminal 54 Low Current. Remedy:
|
| 3 No motor | Cause: No motor has been connected to the output of the drive. Remedy:
|
| 4 Mains phase loss | Cause: Missing phase on the supply side, or the voltage imbalance is too high. This can also indicate a fault in the input rectifier. Remedy:
|
| 7 DC overvoltage | Cause: DC-link voltage exceeds the limit. Remedy:
|
| 8 DC undervoltage | Cause: DC-link voltage drops below the voltage warning low limit. Remedy:
|
| 9 Inverter overloaded | Cause: More than 100% load for too long. Remedy:
|
| 10 Motor ETR overtemperature | Cause: The motor is too hot due to more than 100% load for too long. Remedy:
|
| 11 Motor thermistor overtemperature | Cause: Thermistor or thermistor connection is disconnected, or the motor is too hot. Remedy:
|
| 12 Torque limit | Cause: Torque exceeds value set in either parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode. Remedy:
|
| 13 Overcurrent | Cause: Inverter peak current limit is exceeded. If this alarm occurs on power-up, check whether power cables are mistakenly connected to the motor terminals. Remedy:
|
| 14 Ground fault | Cause: Discharge from output phases to ground, either in the cable or the motor. Remedy:
|
| 16 Short circuit | Cause: Short circuit in the motor or on motor terminals. Remedy:
|
| 17 Control word timeout | Cause: No communication to the drive. Remedy:
|
| 25 Brake resistor short-circuited | Cause: Brake resistor is short-circuited, thus the brake function is disconnected. Remedy:
|
| 26 Brake overload | Cause: The power transmitted to the brake resistor over the last 120 s exceeds the limit. Remedy:
|
| 27 Brake IGBT/Brake chopper short-circuited | Cause: Brake transistor is short-circuited, thus the brake function is disconnected. Remedy:
|
| 28 Brake check | Cause: The brake resistor is not connected or not working. Remedy:
|
| 30 U phase loss | Cause: Motor phase U is missing. Remedy:
|
| 31 V phase loss | Cause: Motor phase V is missing. Remedy:
|
| 32 W phase loss | Cause: Motor phase W is missing. Remedy:
|
| 34 Fieldbus fault | Cause: Fieldbus communication issues have occurred. Remedy:
|
| 35 Option fault | Cause: Fieldbus detects internal faults. Remedy:
|
| 36 Mains failure | Cause: This warning/alarm is only active if the supply voltage to the drive is less than the value set in parameter 14-11 Mains Fault Voltage Level, and parameter 14-10 Mains Failure is NOT set to No Function. Remedy:
|
| 38 Internal fault | Cause: An internal fault has occurred. Remedy:
|
| 40 Overload T27 | Cause: Check the load connected to terminal 27 or remove short-circuit connection. Remedy:
|
| 46 Gate drive voltage fault | Cause: Internal power supply issue. Remedy:
|
| 47 24 V supply low | Cause: 24 V DC may be overloaded. Remedy:
|
| 49 Speed limit | Cause: The motor speed is below the specified limit in parameter 1-87 Trip Speed Low [Hz]. Remedy:
|
| 50 AMA calibration failed | Cause: A calibration error has occurred. Remedy:
|
| 51 AMA check Unom and Inom | Cause: Wrong setting for motor voltage and/or motor current. Remedy:
|
| 52 AMA low Inom | Cause: Motor current is too low. Remedy:
|
| 53 AMA big motor | Cause: The power size of the motor is too large for the AMA to operate. Remedy:
|
| 54 AMA small motor | Cause: The power size of the motor is too small for the AMA to operate. Remedy:
|
| 55 AMA parameter range | Cause: The parameter values of the motor are outside of the acceptable range. AMA does not run. Remedy:
|
| 56 AMA interrupt | Cause: The AMA is interrupted by the user. Remedy:
|
| 57 AMA timeout | Cause: AMA is taking too long to complete. Remedy:
|
| 58 AMA internal | Cause: Internal fault during AMA. Remedy:
|
| 59 Current limit | Cause: Drive overload. The current is higher than the value in parameter 4-18 Current Limit. Remedy:
|
| 60 External Interlock | Cause: External interlock has been activated. Remedy:
|
| 61 Encoder loss | Cause: The drive is not receiving a signal from the encoder. Remedy:
|
| 63 Mechanical brake low | Cause: Actual motor current has not exceeded release brake current within the start delay time window. Remedy:
|
| 65 Control card temp | Cause: The cutout temperature of the control card has exceeded the upper limit. Remedy:
|
| 67 Option change | Cause: A new option is detected or a mounted option is removed. Remedy:
|
| 68 Safe Torque Off | Cause: STO is activated. Remedy:
|
| 69 Power card temp | Cause: The cutout temperature of the power card has exceeded the upper limit. Remedy:
|
| 80 Drive initialized to default value | Cause: All parameter settings are initialized to default settings. Remedy:
|
| 87 Auto DC brake | Cause: Occurs in IT mains when the drive coasts, and the DC voltage is higher than 830 V for 400 V units and 425 V for 200 V units. The motor consumes energy on the DC link. Remedy:
|
| 88 Option detection | Cause: The option is removed successfully. Remedy:
|
| 95 Broken belt | Cause: A broken belt has been detected. Remedy:
|
| 99 Locked rotor | Cause: Rotor is blocked. Remedy:
|
| 120 Position control fault | Cause: An error has occurred in the position control. Remedy:
|
| 126 Motor rotating | Cause: PM motor is rotating when AMA is performed. Remedy:
|
| 127 Back EMF too high | Cause: The back EMF of the PM motor is too high before starting. Remedy:
|
| 188 STO internal fault | Cause: 24 V DC supply is connected to only 1 of the 2 STO terminals (37 and 38), or a failure in STO channels is detected. Remedy:
|
| nw run Not while running | Cause: Parameters can only be changed when the motor is stopped. Remedy:
|
| Err. A wrong password was entered | Cause: Occurs when using a wrong password for changing a password-protected parameter. Remedy:
|
How to Clear & Reset Danfoss FC280 Drive Faults
- Keypad Reset: Press the red [Off/Reset] button on the Local Control Panel (LCP 21 or LCP 102). Once the fault is cleared, press [Auto On] or [Hand On] to restore motor operation.
- Digital Input Reset (DI): If assigned in parameter group 5-1* (Digital Inputs)—such as parameter 5-12 (Terminal 27) set to `[1] Reset`—momentarily pulse the assigned 24V DC terminal input.
- Danfoss MCT 10 Software: Connect your PC via the integrated USB port on the front panel, launch the Danfoss VLT® Motion Control Tool MCT 10, and click “Fault Reset” in the drive status dashboard.
- Fieldbus Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in the Danfoss standard control word via embedded Modbus RTU or optional communication networks (PROFINET, EtherNet/IP, PROFIBUS, CANopen).
- Power Cycle (Trip Lock Clearance): For severe “Trip Lock” alarms, disconnect the AC line power completely. Wait until the display and DC capacitors are fully discharged (approx. 4 to 15 minutes depending on frame size) before reconnecting power.
⚠️ High-Voltage Electrical Safety Warning:
Danfoss FC 280 intermediate DC-link capacitors retain hazardous electrical energy after power is switched off. Wait a minimum of 4 minutes (for 0.37–7.5 kW) or 15 minutes (for 11–22 kW), and verify with a calibrated digital multimeter that voltage across terminals [+UDC] and [-UDC] measures strictly below 50VDC before inspecting motor cabling or touching terminals U, V, and W.