Danfoss VLT 5000 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Danfoss VLT 5000 industrial drive series. Search or filter through the complete diagnostic database below.
Power Range
0.75 – 500 kW (1 – 650 HP)
Supply Voltage
200–240V / 380–500V / 525–600V
Control Modes
VVCplus & Flux Vector Control
Operator Interface
LCP 2 Alphanumeric Control Panel
Complete Danfoss VLT 5000 Fault Code Directory
Use the search box in the table below to quickly find your alarm code (e.g., type Alarm 13, Alarm 14, Alarm 16, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| WARNING 1 Under 10 Volts (10 VOLT LOW) | Cause: The 10 Volts voltage from terminal 50 on the control card is below 10 Volts. The 10 Volts supply is overloaded. Remedy:
|
| WARNING/ALARM 2 Live zero fault (LIVE ZERO ERROR) | Cause: The current signal on terminal 60 is less than 50% of the value set in parameter 315 Terminal 60, min. scaling. Remedy:
|
| WARNING/ALARM 3 No motor (NO MOTOR) | Cause: The motor check function (parameter 122) indicates that no motor has been connected to the output of the frequency converter. Remedy:
|
| WARNING/ALARM 4 Phase fault (MAINS PHASE LOSS) | Cause: A phase is missing on the supply side, the mains voltage imbalance is too high, or there is a fault in the input rectifier on the frequency converter. Remedy:
|
| WARNING 5 Voltage warning high (DC LINK VOLTAGE HIGH) | Cause: The intermediate circuit voltage (DC) is higher than the overvoltage limit of the control system. The frequency converter is still active. Remedy:
|
| WARNING 6 Voltage warning low (DC LINK VOLTAGE LOW) | Cause: The intermediate circuit voltage (DC) is below the undervoltage limit of the control system. The frequency converter is still active. Remedy:
|
| WARNING/ALARM 7 Overvoltage (DC LINK OVERVOLT) | Cause: The intermediate circuit voltage (DC) exceeds the inverter overvoltage limit. Remedy:
|
| WARNING/ALARM 8 Undervoltage (DC LINK UNDERVOLT) | Cause: The intermediate circuit voltage (DC) drops below the inverter lower voltage limit. Remedy:
|
| WARNING/ALARM 9 Inverter overload (INVERTER TIME) | Cause: The electronic, thermal inverter protection reports that the frequency converter is about to cut out because of an overload (too high current for too long). Remedy:
|
| WARNING/ALARM 10 Motor overtemperature (MOTOR TIME) | Cause: According to the electronic thermal protection (ETR), the motor is too hot. The counter has reached 100%. Remedy:
|
| WARNING/ALARM 11 Motor thermistor (MOTOR THERMISTOR) | Cause: The thermistor or the thermistor connection has been disconnected. Remedy:
|
| WARNING/ALARM 12 Torque limit (TORQUE LIMIT) | Cause: The torque is higher than the value in parameter 221 (in motor operation) or the torque is higher than the value in parameter 222 (in regenerative operation). Remedy:
|
| WARNING/ALARM 13 Overcurrent (OVERCURRENT) | Cause: The inverter peak current limit (approx. 200% of the rated current) has been exceeded. Remedy:
|
| ALARM: 14 Earth fault (Earth fault) | Cause: There is a discharge from the output phases to earth, either in the cable between the frequency converter and the motor or in the motor itself. Remedy:
|
| ALARM: 15 Switch mode fault (SWITCH MODE FAULT) | Cause: Fault in the switch mode power supply (internal ± 15 V supply). Remedy:
|
| ALARM: 16 Short-circuiting (CURR.SHORT CIRCUIT) | Cause: There is short-circuiting on the motor terminals or in the motor itself. Remedy:
|
| WARNING/ALARM 17 Standard bus timeout (STD BUS TIMEOUT) | Cause: There is no communication to the frequency converter. Only active if parameter 514 is not OFF. Remedy:
|
| WARNING/ALARM 18 HPFB bus timeout (HPFB BUS TIMEOUT) | Cause: There is no communication with the frequency converter. Only active if parameter 804 is not OFF. Remedy:
|
| WARNING 19 Fault in the EEprom on the power card (EE ERROR POWER CARD) | Cause: There is a fault on the power card EEPROM. The frequency converter will likely fail at the next power-up. Remedy:
|
| WARNING 20 Fault in the EEprom on the control card (EE ERROR CTRL CARD) | Cause: There is a fault in the EEPROM on the control card. The frequency converter will likely fail at the next power-up. Remedy:
|
| ALARM 21 Auto-optimisation OK (AUTO MOTOR ADAPT OK) | Cause: The automatic motor tuning is OK and the frequency converter is now ready for operation. Remedy:
|
| ALARM 22 Auto-optimisation not OK (AUTO MOT ADAPT FAIL) | Cause: A fault has been found during automatic motor adaptation (AMA). The figure in brackets [] indicates the specific fault code: [0]: CHECK P.103,105 [1]: LOW P.105 [2]: ASYMMETRICAL IMPEDANCE [3]: MOTOR TOO BIG [4]: MOTOR TOO SMALL [5]: TIME OUT [6]: INTERRUPTED BY USER [7]: INTERNAL FAULT [8]: LIMIT VALUE FAULT [9]: MOTOR ROTATES Remedy:
|
| WARNING/ALARM 23 Fault during brake test (BRAKE TEST FAILED) | Cause: The brake test (run after power-up) found a fault. Possible reasons: - No brake resistor connected. - Fault in the connections. - Defective brake resistor or defective brake transistor. Remedy:
|
| WARNING 25 Brake resistor fault (BRAKE RESISTOR FAULT) | Cause: The brake resistor is monitored during operation and if it short-circuits, the brake function is disconnected. Remedy:
|
| ALARM/WARNING 26 Brake resistor power 100% (BRAKE PWR WARN 100%) | Cause: The power transmitted to the brake resistor (calculated as a percentage mean over 120s) is higher than 100%. Remedy:
|
| WARNING 27 Brake transistor fault (BRAKE IGBT FAULT) | Cause: The brake transistor is short-circuited. Substantial power will be transmitted to the brake resistor, even if inactive. Remedy:
|
| ALARM: 29 Heat sink temperature too high (HEAT SINK OVER TEMP.) | Cause: The cut-out temperature of the heat-sink has been exceeded (90°C for IP 00/20, 80°C for IP 54). The fault cannot be reset until the temperature is below 60°C. The fault could be:
|
| ALARM: 30 Motor phase U missing (MISSING MOT.PHASE U) | Cause: Motor phase U between frequency converter and motor is missing. Remedy:
|
| ALARM: 31 Motor phase V missing (MISSING MOT.PHASE V) | Cause: Motor phase V between frequency converter and motor is missing. Remedy:
|
| ALARM: 32 Motor phase W missing (MISSING MOT.PHASE W) | Cause: Motor phase W between frequency converter and motor is missing. Remedy:
|
| ALARM: 33 Quick discharge not OK (QUICK DISCHARGE NOT OK) | Remedy:
|
| WARNING/ALARM: 34 Fieldbus communication fault (FIELDBUS COMMUNICATION FAULT) | Cause: The fieldbus on the communication option card is not working. |
| WARNING: 35 Out of frequency range (OUT OF FREQUENCY RANGE) | Cause: This warning is active if the output frequency has reached its Output frequency low limit (parameter 201) or Output frequency high limit (parameter 202). Note: If in Process control, closed loop, bit 008000 will be active in extended status word, but there will be no warning in the display. |
| WARNING/ALARM: 36 Mains failure (MAINS FAILURE) | Cause: Supply voltage to the frequency converter is lost and parameter 407 is set to a value other than OFF. Remedy:
|
| ALARM: 37 Inverter fault (Inverter fault) | Cause: IGBT or the power card is defective. Remedy: Contact your Danfoss supplier. Auto-optimisation warnings: AMA has stopped, likely due to wrong parameters or motor size mismatch. Remedy:
|
| WARNING: 39 CHECK P.104, 106 | Cause: The setting of parameter 102, 104 or 106 is probably wrong. Remedy:
|
| WARNING: 40 CHECK P.103, 105 | Cause: The setting of parameter 102, 103 or 105 is probably wrong. Remedy:
|
| WARNING: 41 MOTOR TOO BIG | Cause: The motor used is probably too big for AMA to be carried out. The setting in parameter 102 may not match the motor. Remedy:
|
| WARNING: 42 MOTOR TOO SMALL | Cause: The motor used is probably too small for AMA to be carried out. The setting in parameter 102 may not match the motor. Remedy:
|
| ALARM: 43 Brake fault (BRAKE FAULT) | Cause: A fault has arisen on the brake. See specific sub-faults below: [0] Brake check failed: Brake disconnected.
[1] Brake resistor short-circuited:
[2] Brake IGBT short-circuited: Unit is unable to stop the brake; resistor is constantly energized. |
| WARNING/ALARM: 44 Encoder loss (ENCODER FAULT) | Cause: The encoder signal is interrupted from terminal 32 or 33. Remedy:
|
| WARNING/ALARM: 57 Overcurrent (OVERCURRENT) | Cause: As warning/alarm 13, but in this case the warning/alarm occurs together with a quick stop. |
| ALARM: 60 Safety stop (EXTERNAL FAULT) | Cause: Terminal 27 (parameter 304 Digital Inputs) has been programmed for a safety interlock [3] and is a logic '0'. |
How to Clear & Reset Danfoss VLT 5000 Drive Faults
- Keypad Reset: Press the yellow [Reset] key on the LCP 2 control panel. If the drive is locked in a Trip Lock alarm condition, the root fault cause must be cleared before the keypad acknowledges the reset.
- Digital Input Reset: Activate the digital input programmed for reset (default Terminal 27 configured via parameter 304 Digital Input set to [1] Reset).
- Automatic Reset: Configure parameter 400 (Reset Function) to select 1 to 10 automatic reset retries or continuous auto-reset, setting the delay interval in parameter 401 (Re-start Time).
- Serial Communication (Fieldbus): Write Bit 7 (Fault Reset) from `0` to `1` in the Control Word (CTW) via standard RS-485 FC protocol or installed option boards (Profibus, LonWorks, DeviceNet).
- Power Cycle: Disconnect the incoming AC line power, wait until the LCP display is completely blank and internal capacitors discharge (4 to 20 minutes depending on power rating), then reapply mains.
⚠️ High-Voltage Electrical Safety Warning:
Intermediate DC-bus capacitors retain lethal voltages after the AC mains supply is removed. Always wait at least 4 minutes for units up to 11 kW (VLT 5001–5011), 15 minutes for units up to 45 kW (VLT 5016–5062), and 20 to 30 minutes for higher ratings (VLT 5072–5500). Always measure with a calibrated voltmeter between intermediate DC bus terminals (+DC / -DC or terminals 04 / 45) to verify voltage is strictly below 50 V DC before servicing motor terminals U, V, and W.