Danfoss VLT 8000 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step diagnostic procedures for the Danfoss VLT® 8000 AQUA / HVAC drive series. Search or filter through the complete diagnostic directory below.
Power Range
1.1 – 400 kW (1.5 – 550 HP)
Supply Voltage
200–240V / 380–480V / 525–600V AC
Control Modes
VVCplus & U/f (Special Motor Mode)
Operator Interface
Alphanumeric LCP 2 Control Panel
Complete Danfoss VLT 8000 Drive Fault Code Directory
Use the search box in the table below to quickly find your alarm code or text (e.g., type Alarm 13, Alarm 14, Overcurrent, or Earth Fault).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| WARNING 1 Under 10 V (10 VOLT LOW) | Cause: The 10 V voltage from terminal 50 on the control card is below 10 V. The 10 Volts supply is overloaded. Remedy:
|
| WARNING/ALARM 2 Live zero fault (LIVE ZERO ERROR) | Cause: The current or voltage signal on terminal 53, 54 or 60 is below 50% of the value preset in parameter 309, 312 and 315 (Terminal, min. scaling). |
| WARNING/ALARM 4 Mains imbalance (MAINS IMBALANCE) | Cause: High imbalance or phase missing on the supply side. Remedy:
|
| WARNING 5 Voltage warning high (DC LINK VOLTAGE HIGH) | Cause: The intermediate circuit voltage (DC) is higher than the Voltage warning high limit. The controls of the frequency converter are still enabled. |
| WARNING 6 Voltage warning low (DC LINK VOLTAGE LOW) | Cause: The intermediate circuit voltage (DC) is lower than the Voltage warning low limit. The controls of the frequency converter are still enabled. |
| WARNING/ALARM 7 Overvoltage (DC LINK OVERVOLT) | Cause: The intermediate circuit voltage (DC) is higher than the Overvoltage limit of the inverter. The frequency converter will trip after a fixed period. Remedy:
|
| WARNING/ALARM 8 Undervoltage (DC LINK UNDERVOLT) | Cause: The intermediate circuit voltage (DC) drops below the undervoltage limit of the inverter. The frequency converter will trip after a fixed period. Remedy:
|
| WARNING/ALARM 9 Inverter overload (INVERTER TIME) | Cause: The electronic, thermal inverter protection reports that the AFD is about to cut out because of an overload (too high current for too long). Details:
|
| WARNING/ALARM 10 Motor overtemperature (MOTOR TIME) | Cause: According to the electronic thermal protection (ETR), the motor is too hot. The motor is overloaded by more than 100% of the preset rated motor current for too long. Remedy:
|
| WARNING/ALARM 11 Motor thermistor (MOTOR THERMISTOR) | Cause: The thermistor or the thermistor connection has been disconnected. Remedy:
|
| WARNING/ALARM 12 Current limit (CURRENT LIMIT) | Cause: The current is higher than the value in parameter 215 (Current limit ILIM). The converter trips after the time set in parameter 412 has passed. |
| WARNING/ALARM 13 Overcurrent (OVER CURRENT) | Cause: The inverter peak current limit (approx. 200% of the rated current) has been exceeded. Remedy:
|
| ALARM 14 Ground fault (GROUND FAULT) | Cause: There is a discharge from the output phases to ground, either in the cable between the AFD and the motor or in the motor itself. Remedy:
|
| ALARM 15 Switch mode fault (SWITCH MODE FAULT) | Cause: Fault in the switch mode power supply (internal ± 15 V supply). Remedy:
|
| ALARM 16 Short-circuiting (CURR. SHORT CIRCUIT) | Cause: There is short-circuiting on the motor terminals or in the motor itself. Remedy:
|
| WARNING/ALARM 17 Serial communication timeout (STD BUSTIMEOUT) | Cause: There is no serial communication with the frequency converter. Remedy:
|
| WARNING/ALARM 18 HPFB bus timeout (HPFB TIMEOUT) | Cause: There is no serial communication with the communication option card of the frequency converter. Remedy:
|
| WARNING 19 Fault in the EEprom on the power card (EE ERROR POWER) | Cause: There is a fault on the power card EEPROM. The frequency converter will continue to function, but is likely to fail at the next power-up. Remedy:
|
| WARNING 20 Fault in the EEprom on the control card (EE ERROR CONTROL) | Cause: There is a fault in the EEPROM on the control card. The frequency converter will continue to function, but is likely to fail at the next power-up. Remedy:
|
| ALARM 22 Auto-optimisation not OK (AMA FAULT) | Cause: A fault has been found during automatic motor adaptation. The display indicates the specific sub-code: CHECK 103, 105 [0] Parameter 103 or 105 has a wrong setting. Correct setting and restart AMA. LOW P.105 [1] Motor is too small for AMA. Param 105 must be > 35% of rated output current. ASYMMETRICAL IMPEDANCE [2] Asymmetrical impedance detected in motor system. Motor could be defective. MOTOR TOO BIG [3] Motor is too big for AMA to be carried out. Check setting in parameter 102. MOTOR TOO SMALL [4] Motor is too small for AMA to be carried out. Check setting in parameter 102. TIME OUT [5] AMA fails because of noisy measuring signals. Try starting AMA again. Note: Repeated AMA runs may heat motor. INTERRUPTED BY USER [6] AMA has been interrupted by the user. INTERNAL FAULT [7] Internal fault in frequency converter. Contact Danfoss supplier. LIMIT VALUE FAULT [8] Parameter values found for the motor are outside acceptable range. MOTOR ROTATES [9] The motor shaft rotates. Ensure load cannot make motor rotate, then restart AMA. |
| ALARM 29 Heat sink temperature too high (HEAT SINK OVER TEMP.) | Cause: The cut-out temperature of the heat-sink has been reached (90°C or 80°C depending on enclosure). Remedy: The fault could be the following:
|
| ALARM 30 Motor phase U missing (MISSING MOT.PHASE U) | Cause: Motor phase U between frequency converter and motor is missing. Remedy:
|
| ALARM: 31 Motor phase V missing (MISSING MOT.PHASE V) | Cause: Motor phase V between frequency converter and motor is missing. Remedy:
|
| ALARM: 32 Motor phase W missing (MISSING MOT.PHASE U) | Cause: Motor phase W between frequency converter and motor is missing. Remedy:
|
| WARNING/ALARM: 34 HPFB communication fault (HPFB COMM. FAULT) | Cause: The serial communication on the communication option card is not working. |
| ALARM: 37 Inverter fault (GATE DRIVE FAULT) | Cause: IGBT or the power card is defective. Remedy:
|
| WARNING: 39 CHECK PAR. 104, 106 | Cause: Parameters 104 Motor frequency fM,N, or 106 Rated motor speed nM,N, have probably not been set correctly. Remedy:
|
| WARNING: 40 CHECK PAR. 103, 105 | Cause: Parameter 103 Motor voltage, UM,N or 105 Motor current, IM,N has not been set correctly. Remedy:
|
| WARNING: 41 MOTOR TOO BIG (MOTOR TOO BIG) | Cause: The motor used is probably too big for AMA to be carried out. The setting in parameter 102 Motor power, PM,N may not match the motor. Remedy:
|
| WARNING: 42 MOTOR TOO SMALL (MOTOR TOO SMALL) | Cause: The motor used is probably too small for AMA to be carried out. The setting in parameter 102 Motor power, PM,N may not match the motor. Remedy:
|
| ALARM: 60 Safety stop (EXTERNAL FAULT) | Cause: Terminal 27 (parameter 304 Digital inputs) has been programmed for a Safety interlock [3] and is a logic "0". |
| WARNING: 61 Output frequency low (FOUT < FLOW) | Cause: The output frequency is lower than parameter 223 Warning: Low frequency, fLOW. |
| WARNING: 62 Output frequency high (FOUT > FHIGH) | Cause: The output frequency is higher than parameter 224 Warning: High frequency, fHIGH. |
| WARNING/ALARM: 63 Output current low (I MOTOR < I LOW) | Cause: The output current is lower than parameter 221 Warning: Low current, ILOW. Remedy:
|
| WARNING: 64 Output current high (I MOTOR > I HIGH) | Cause: The output current is higher than parameter 222 Warning: High current, IHIGH. |
| WARNING: 65 Feedback low (FEEDBACK < FDB LOW) | Cause: The resulting feedback value is lower than parameter 227 Warning: Low feedback, FBLOW. |
| WARNING: 66 Feedback high (FEEDBACK > FDB HIGH) | Cause: The resulting feedback value is higher than parameter 228 Warning: High feedback, FBHIGH. |
| WARNING: 67 Remote reference low (REF. < REF LOW) | Cause: The remote reference is lower than parameter 225 Warning: Low reference, REFLOW. |
| WARNING: 68 Remote reference high (REF. > REF HIGH) | Cause: The remote reference is higher than parameter 226 Warning:High reference, REFHIGH. |
| WARNING: 69 Temperature auto derate (TEMP.AUTO DERATE) | Cause: The heat sink temperature has exceeded the maximum value and the auto derating function (par. 411) is active. |
| WARNING: 99 Unknown fault (UNKNOWN ALARM) | Cause: An unknown fault has occurred that cannot be processed by the software. Remedy:
|
How to Clear & Reset Danfoss VLT 8000 Drive Faults
- Keypad Reset: Press the red [Reset] key on the LCP 2 control panel once the fault condition has resolved. Press [Auto On] or [Hand On] to restore modulation.
- Digital Input Reset (DI): If assigned in parameter group 300 (Inputs/Outputs)—such as parameter 302, 303, or 304 set to `[1] Reset`—apply a momentary 24V DC pulse to the configured digital input terminal (e.g., Terminal 18, 19, or 27).
- Automatic Fault Reset: Parameter 400 (Reset function) can be configured for automatic restart attempts (1 to 10 retries or infinite) with programmable restart time intervals (parameter 401).
- Serial Bus Reset (RS-485 / Fieldbus): Send a fault acknowledgment telegram via the built-in RS-485 serial port (terminals 68 and 69) using the Danfoss FC protocol, Modbus RTU, Metasys N2, or optional LonWorks/Profibus. Bit 7 of the control word triggers fault reset.
- Power Cycle (Trip Lock Clearance): For severe “Trip Locked” faults (e.g., short circuit or persistent earth fault), switch off main AC supply. Wait until the display goes completely dark and internal capacitors discharge before reapplying power.
⚠️ High-Voltage Electrical Safety Warning:
Danfoss VLT 8000 frequency converters retain dangerous intermediate DC-link voltages even after line power is turned off. Always wait at least 4 minutes (for 1.1–7.5 kW) or 15 minutes (for 11–400 kW). Confirm with a calibrated DC voltmeter that voltage across terminals [+UDC] and [-UDC] is below 50VDC before inspecting internal hardware or touching motor output terminals 96 (U), 97 (V), and 98 (W).