Danfoss VACON 10 Drive Fault Codes & Diagnostic Guide

Complete fault code list, alarm troubleshooting directory, and step-by-step diagnostic solutions for the compact Danfoss VACON® 10 micro drive series. Search or filter through the complete diagnostic database below.

Compact Machinery Micro Drive Power: 0.18 to 5.5 kW (0.25 to 7.5 HP) DIN Rail & Screw Mountable
Power Range 0.18 – 5.5 kW (0.25 – 7.5 HP)
Supply Voltage 115V / 208–240V / 380–480V (1/3-Ph)
Control Modes U/f Frequency & Open-Loop Vector
Operator Interface Integrated 7-Segment LED Keypad

Complete Danfoss VACON 10 Drive Fault Code Directory

Use the search box in the table below to quickly find your fault code (e.g., type F1, F2, or Overcurrent).

Fault Code and MeaningCause and Remedy
1
Overcurrent

Cause: Frequency converter has detected too high a current (>4*IN) in the motor cable.

  • sudden heavy load increase

  • short circuit in motor cables

  • unsuitable motor




Remedy:

  • Check loading.

  • Check motor size.

  • Check cables.


2
Overvoltage

Cause: The DC-link voltage has exceeded the internal safety limit.

  • deceleration time is too short

  • high overvoltage spikes in mains




Remedy:

  • Increase the deceleration time (Par.4.3 or Par.4.6).


3
Earth fault

Cause: Current measurement has detected extra leakage current at start.

  • insulation failure in cables or motor




Remedy:

  • Check motor cables and motor.


8
System fault

Cause:

  • component failure

  • faulty operation




Remedy:

  • Reset the fault and restart.

  • If the fault re-occurs, contact the distributor near to you.

  • NOTE! If fault F8 occurs, find out the subcode of the fault from the Fault History menu.


9
Undervoltage

Cause: The DC-link voltage has gone below the internal safety limit.

  • most probable cause: supply voltage is too low

  • frequency converter internal fault

  • Power outages




Remedy:

  • In case of temporary supply voltage break reset the fault and restart the frequency converter.

  • Check the supply voltage.

  • If it is adequate, an internal failure has occurred. Contact the distributor near to you.


11
Output phase fault

Cause: Current measurement has detected that there is no current in one motor phase.



Remedy:

  • Check motor cable and motor.


13
Frequency converter undertemperature

Cause: Heat sink temperature is under -10 °C.



Remedy:

  • Check the ambient temperature.


14
Frequency converter overtemperature

Cause: Heat sink is overheated.



Remedy:

  • Check that the cooling air flow is not blocked.

  • Check the ambient temperature.

  • Make sure that the switching frequency is not too high in relation to ambient temperature and motor load.


15
Motor stalled

Cause: Motor stall protection has tripped.



Remedy:

  • Check that the motor is able to rotate freely.


16
Motor overtemperature

Cause: Motor overheating has been detected by frequency converter motor temperature model. Motor is overloaded.



Remedy:

  • Decrease the motor load.

  • If no motor overload exists, check the temperature model parameters.


17
Motor underload

Cause: Motor underload protection has tripped.



Remedy:

  • Check motor and load, e.g. for broken belts or dry pumps.


22
EEPROM check sum fault

Cause: Parameter save fault.

  • faulty operation

  • component failure

  • Note: Alarm 22 is issued for calibration data CRC check.




Remedy:

  • Contact the distributor near to you.


25
Microcontroller watchdog fault

Cause:

  • faulty operation

  • component failure




Remedy:

  • Reset the fault and restart.

  • If the fault re-occurs, contact the distributor near to you.


27
Back EMF protection

Cause: Drive has detected that the magnetized motor is running in start situation.

  • A rotating PM-motor




Remedy:

  • Make sure that there is no rotating PM-motor when the start command is given.


29
Thermistor fault

Cause: The thermistor input of option board has detected increase.



Remedy:

  • Check motor cooling and loading.

  • Check thermistor connection (If thermistor input of the option board is not in use it has to be short circuited).


34
Internal bus communication

Cause: Ambient interference or defective hardware.



Remedy:

  • If the fault re-occurs, contact the distributor near to you.


35
Application fault

Cause: Application is not working properly.



Remedy:

  • Contact the distributor near to you.


41
IGBT Overtemperature

Cause: Over temperature alarm is issued when the IGBT switch temperature exceeds 110 °C.



Remedy:

  • Check loading.

  • Check motor size.

  • Make identification run.


50
Analog input select

Cause: Current at the analogue input is < 4mA; Voltage at the analogue input is < 2 V (selected signal range 4 to 20 mA or 2 to 10 V).

  • control cable is broken or loose.

  • signal source has failed.




Remedy:

  • Check the current loop circuitry.


51
External fault

Cause: Digital input fault. Digital input has been programmed as external fault input and this input is active.



Remedy:

  • Remove the external device fault.


53
Fieldbus fault

Cause: The data connection between the fieldbus Master and the fieldbus of the drive has broken.



Remedy:

  • Check installation.

  • If installation is correct, contact the nearest Vacon distributor.


55
Wrong run fault (FWD/REV conflict)

Cause: Run forward and backward at the same time.



Remedy:

  • Check I/O control single 1 and I/O control single 2.

  • Single 1 should be changed to signal 1, single 2 should be changed to signal 2.


57
Identification fault

Cause: Identification run has failed.



Remedy:

  • Run command was removed before completion of identification run.

  • Motor is not connected to frequency converter.

  • There is load on motor shaft.


111
Temperature fault

Cause: Over low or over high temperature.



Remedy:

  • Check temperature signal from OPTBH board.


How to Clear & Reset Danfoss VACON 10 Faults

  1. Keypad Reset: Press the red [Stop/Reset] key on the integrated 7-segment LED keypad panel. If the drive is locked in a fault state, resolve the underlying problem before resetting.
  2. Digital Input Reset (DI): If assigned in parameter settings (parameter P2.2.1.2 – Fault Reset), pulse the assigned digital input terminal (DIN4 to DIN6) with a +24V DC signal.
  3. VACON Live PC Software: Connect via the serial communication interface adapter (MCA-01 / RS-485 to USB cable), open VACON Live, and click “Fault Reset” in the online monitoring dashboard.
  4. Fieldbus Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in the Fieldbus Control Word via optional embedded Modbus RTU (RS-485 serial interface).
  5. Power Cycle: Disconnect AC line power, wait until the 7-segment display goes completely blank, and wait at least 5 minutes for the internal DC bus capacitors to discharge safely before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] or motor output terminals U/T1, V/T2, and W/T3 before servicing wiring, opening covers, or handling the Danfoss VACON 10 drive unit.