Danfoss VLT 3000 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and maintenance troubleshooting procedures for legacy Danfoss VLT® Series 3000 drives (VLT 3002–3250). Search or filter through the complete diagnostic directory below.
Power Range
0.75 – 250 kW (1 – 350 HP)
Supply Voltage
200–240V / 380–500V AC
Control Modes
VVC (Voltage Vector) & U/f
Operator Interface
Integrated Keypad / LED Display
Complete Danfoss VLT 3000 Drive Fault Code Directory
Use the search box in the table below to quickly find your alarm code or text (e.g., type Trip, Alarm 13, Ground Fault, or Overvoltage).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
Inverter fault (INVERTER FAULT) Fault code 1 A fault in the VLT frequency converter's power section. | Cause: Internal failure within the power section of the drive. Remedy:
|
Overvoltage (OVER VOLTAGE) Fault code 2 The intermediate circuit voltage (DC link) is above the inverter's overvoltage limit. | Cause: The intermediate circuit voltage is too high. This can happen if:
Remedy:
|
Undervoltage (UNDER VOLTAGE) Fault code 3 The intermediate circuit voltage is below the inverter's undervoltage limit. | Cause: The intermediate circuit voltage is too low.
Remedy:
|
Overcurrent (OVER CURRENT) Fault code 4 The inverter's peak current limit (approx. 250% of rated current) has been exceeded for more than 7-11 seconds. | Cause:
Remedy:
|
Earth fault (GROUND FAULT) Fault code 5 Discharge from the output phases to earth. | Cause: Leakage current detected either in the cable between the VLT frequency converter and the motor, or within the motor itself. Remedy:
|
Overtemperature (OVER TEMP.) Fault code 6 An excess temperature has been measured inside the VLT frequency converter. | Cause: Internal overheating. This may be due to ambient temperature being too high or fan failure. Remedy:
|
Inverter overloaded (OVER LOAD) Fault code 7 The electronic thermal inverter protection reports that the drive has cut out due to overload. | Cause: Excessive current for too long. The protection counter reached 100%. Remedy:
|
Motor overloaded (MOTOR TRIP) Fault code 8 and 15 According to the electronic thermal motor protection, the motor is too hot. | Cause: Motor is drawing high current for an extended period, or low speed operation without sufficient cooling. Remedy:
|
Current limit (CURRENT LIMIT) Fault code 9 The motor current has exceeded the value in parameter 209 for longer than permitted in parameter 310. | Cause: Mechanical overload or incorrect current limit settings. Remedy:
|
Auto optimization fault (TUNING. FAULT) Fault code 13 Failure during the Adaptive Motor Tuning (AMT) process. | Cause:
Remedy:
|
Reference faults (REF. FAULT) Warning Fault to the analogue input signal (terminal 53 or 60) with "live zero" selected. | Cause: Signal level is below half of the zero level (e.g., below 2mA on a 4-20mA signal). Remedy:
|
No motor (NO MOTOR) Warning The motor check function (parameter 313) detects that no motor is connected. | Cause: Missing motor connection on the output phases. Remedy:
|
EEPROM fault (EEPROM ERROR) Warning/Error EEPROM fault detected. | Cause: Data changes are not saved when mains voltage is switched off. Remedy:
|
24 V fault (NO 24 VOLT) Warning 24 V voltage supply from power section to control card is absent. | Cause: Internal power supply failure. Remedy:
|
Key Disabled (KEY DISABLED) Error Message Keypad interaction attempted but keys are locked. | Cause: Factory setup is active, or keys disabled via parameters 006-009, or Lock switch is open. Remedy:
|
| Inverter fault The VLT power section is defective. | Cause: Defect in the power section. Remedy:
|
| Overvoltage The voltage of the VLT frequency converter's intermediate circuit (DC-voltage) is too high. | Cause: Line voltage too high, transients on the line voltage, or regenerative motor operation. Remedy:
|
| Undervoltage The voltage of the VLT frequency converter's intermediate circuit (DC-voltage) is too low. | Cause: Line voltage too low or defect in the VLT frequency converter's charging circuit/rectifier. Remedy:
|
| Overcurrent The peak current limit of the inverter has been reached. | Cause: This may be due to a short-circuit in the output of the VLT frequency converter or ground failure. Remedy:
|
| Ground fault Ground failure on the VLT frequency converter output. | Cause: Earth leakage or the motor cable is too long. Remedy:
|
| Over-temp The temperature inside the VLT frequency converter is too high. | Cause: Ambient temperature is too high (max. 40/45 °C), cooling ribs are covered, or the fan is defective. Remedy:
|
| Overload The electronic VLT protection is active. The motor has consumed more than 105% of rated current for too long. | Cause: Motor has consumed excessive current for an extended period. Remedy:
|
| Motor trip The electronic motor protection is active. Current consumed at low speed has been too high for too long. | Cause: The motor has been loaded excessively at low speed. Remedy:
|
How to Clear & Reset Danfoss VLT 3000 Drive Faults
- Keypad Reset: Press the red [Reset] key on the front control panel keypad once the fault source is cleared. If set to local control mode, press the [Start] key to restart motor modulation.
- Digital Input Reset (DI): If configured in digital input parameters (parameters 405 or 406), momentary 24V DC excitation on the designated terminal (such as Terminal 16, 17, 27, or 29) clears non-latching alarms.
- Automatic Fault Reset: If programmed via parameter 316 (Automatic fault reset), the drive will automatically attempt to restart after a trip up to the configured retry count (1 to 10 retries or continuous).
- Serial Bus Reset (RS-485): Transmit an alarm acknowledge/reset telegram via the built-in RS-485 communication line (terminals 68 and 69) using the Danfoss FC serial protocol or optional Profibus DP module.
- Power Cycle (Trip Lock Clearance): For severe “Trip Locked” faults (e.g., direct short circuit or overcurrent latch), completely disconnect 3-phase mains AC power. Wait for the DC bus capacitors to discharge fully (LEDs dark) before reapplying power.
⚠️ High-Voltage Electrical Safety Warning:
Danfoss VLT 3000 series frequency converters contain lethal DC bus charges that remain dangerous after mains disconnect. Always wait at least 4 minutes for models VLT 3002–3052 or at least 14 minutes for models VLT 3060–3250. Confirm with a calibrated DC voltmeter that voltage across intermediate terminals [+UDC] and [-UDC] is below 50VDC before inspecting internal hardware or touching motor terminals 96 (U), 97 (V), and 98 (W).