Complete alarm, warning, and fault code reference directory, trip causes, and step-by-step troubleshooting procedures for the Danfoss VLT® 2800 compact inverter series. Search or filter through the complete diagnostic list below.

Compact Industrial Drive Power: 0.37 to 18.5 kW (0.5 to 25 HP) Integrated VVCplus Control & RS-485
Power Range 0.37 – 18.5 kW (0.5 – 25 HP)
Supply Voltage 200–240V / 380–480V AC
Control Modes VVCplus & U/f (Scalar)
Operator Interface Integrated LCP / 7-Segment Display

Complete Danfoss VLT 2800 Alarm & Warning Directory

Use the search box in the table below to quickly find your alarm or warning (e.g., type Alarm 13, Alarm 14, Overcurrent, or Earth Fault).

Fault Code and MeaningCause and Remedy
WARNING/ALARM 2

Live zero fault

Cause:

The voltage or current signal on terminal 53 or 60 is below 50% of the preset value in parameter 309 or 315 Terminal, min. scaling.



Remedy:

Check the signal connections and parameter settings (309 or 315).
WARNING/ALARM 4

AC line phase fault

Cause:

Missing phase on AC line supply side. This fault is only active in 3-phase AC line.



Remedy:

Check the supply voltage to the adjustable frequency drive.
WARNING 5

Voltage warning high

Cause:

The DC bus voltage (VDC) is higher than the Voltage warning high limit.



Remedy:


  • Check whether the supply voltage matches the rating of the adjustable frequency drive.

  • Check if motor frequency is reduced too quickly (ramp down time too short).


WARNING 6

Voltage warning low

Cause:

The DC bus voltage (VDC) is lower than the Voltage warn low limit.



Remedy:

Check whether the supply voltage matches the rating of the adjustable frequency drive.
WARNING/ALARM 7

Overvoltage

Cause:

The DC bus voltage (VDC) is higher than the inverter's Overvoltage limit. Can occur if motor frequency is reduced too quickly.



Remedy:


  • Check supply voltage.

  • Increase ramp-down time.


WARNING/ALARM 8

Undervoltage

Cause:

The DC bus voltage is lower than the inverter's Undervoltage limit.



Remedy:

Check whether the supply voltage fits the adjustable frequency drive (See Technical data).
WARNING/ALARM 9

Inverter overload

Cause:

Electronic thermal inverter protection indicates that the drive is close to disconnecting due to overloading (output current too high for too long).



Remedy:

Remove the overload condition to the drive. The drive cannot be reset until the counter is below 90%.
WARNING/ALARM 10

Motor overloaded

Cause:

The motor is too hot according to the electronic thermal inverter protection. The motor is being overloaded by more than 100% for too long.



Remedy:

Check that motor parameters 102–106 are set correctly.
WARNING/ALARM 11

Motor thermistor

Cause:

The motor is too hot or the thermistor/thermistor connection is cut off.



Remedy:

Check that the PTC thermistor has been correctly connected between terminal 18, 19, 27 or 29 (digital input) and terminal 50 (+10 V supply).
WARNING/ALARM 12

Current limit

Cause:

The output current is greater than the value in parameter 221 Current Limit I_LIM.



Remedy:

Check load conditions. The drive will trip after a set period (parameter 409).
WARNING/ALARM 13

Overcurrent

Cause:

The inverter’s peak current limit (approx. 200% of rated output current) has been exceeded.



Remedy:

Switch off the drive and check that the motor shaft can be turned and that the motor size fits the drive.
ALARM 14

Ground fault

Cause:

There is a discharge from the output phases to ground, either in the cable between the drive and the motor, or in the motor.



Remedy:

Turn off the adjustable frequency drive and remove the ground fault.
ALARM 15

Switch mode fault

Cause:

Fault in switch mode power supply (internal supply).



Remedy:

Contact your Danfoss supplier.
ALARM 16

Short-circuit

Cause:

There is a short-circuit on the motor terminals or in the motor.



Remedy:

Disconnect the AC line supply to the adjustable frequency drive and remove the short-circuit.
WARNING/ALARM 17

Serial communication timeout

Cause:

There is no serial communication to the adjustable frequency drive.



Remedy:

Parameter 513 Bus time interval could possibly be increased.
WARNING/ALARM 18

HPFB bus timeout

Cause:

There is no serial communication to the adjustable frequency drive’s communication option card.



Remedy:

Parameter 803 Bus time interval could possibly be increased.
WARNING 33

Out of frequency range

Cause:

The output frequency has reached Output frequency low limit (parameter 201) or Output frequency high limit (parameter 202).



Remedy:

Check process regulation/closed loop settings.
WARNING/ALARM 34

HPFB communication fault

Cause:

Communication fault only occurs in Profibus versions.



Remedy:

Check Profibus communication.
ALARM 35

Inrush fault

Cause:

The drive has been connected to the AC line supply too many times within 1 minute.



Remedy:

Limit the frequency of AC line power cycling.
WARNING/ALARM 36

Overtemperature

Cause:

Heatsink temperature is above limit (75°C - 85°C or 167°F - 185°F depending on unit). Trip occurs at 92°C - 100°C.

Potential causes:

  • Ambient temperature too high.

  • Motor cable too long.

  • AC line voltage too high.





Remedy:

Ensure ambient temperature is within limits and check installation conditions (cable length, voltage).
ALARM 37

Internal fault number 0

Cause:

Communication fault between control card and BMC2.



Remedy:

Carry out a power cycle. If fault persists, contact supplier.
ALARM 38

Internal fault number 1

Cause:

Flash EEPROM fault on control card.



Remedy:

Carry out a power cycle. If fault persists, contact supplier.
ALARM 39

Internal fault number 2

Cause:

RAM fault on control card.



Remedy:

Carry out a power cycle. If fault persists, contact supplier.
ALARM 40

Internal fault number 3

Cause:

Calibration constant error in EEPROM.



Remedy:

Carry out a power cycle. If fault persists, contact supplier.
ALARM 41

Internal fault number 4

Cause:

Data values error in EEPROM.



Remedy:

Carry out a power cycle. If fault persists, contact supplier.
ALARM 42

Internal fault number 5

Cause:

Fault in motor parameter database.



Remedy:

Carry out a power cycle. If fault persists, contact supplier.
ALARM 43

Internal fault number 6

Cause:

General power card fault.



Remedy:

Carry out a power cycle. If fault persists, contact supplier.
ALARM 44

Internal fault number 7

Cause:

Minimum software version of control card or BMC2.



Remedy:

Carry out a power cycle. If fault persists, contact supplier.
ALARM 45

Internal fault number 8

Cause:

I/O fault (digital input/output, relay or analog input/output).



Remedy:

When restarting after an alarm 38–45, the drive will display alarm 37. In parameter 615 the actual alarm code can be read.
ALARM 50

AMT not possible

Cause:

Possibilities:

  • Calculated Rs value outside permitted limits.

  • Motor current in at least one phase is too low.

  • Motor is too small for AMT calculations.





Remedy:

Check motor selection and connection.
ALARM 51

AMT Fault re. nameplate data

Cause:

There is inconsistency in the registered motor data.



Remedy:

Check the motor data for the relevant setup.
ALARM 52

AMT faulty motor phase

Cause:

The motor current in at least one of the motor phases is too low.



Remedy:

Check motor phases and connections.
ALARM 53

AMT motor too small

Cause:

The motor used is probably too small for the AMT calculations to be carried out.



Remedy:

Verify motor size compatibility.
ALARM 54

AMT incorrect motor

Cause:

AMT cannot be performed on the motor being used.



Remedy:

Check motor type.
ALARM 55

AMT timeout

Cause:

The calculations are taking too long, possibly due to noise in the motor cables.



Remedy:

Check motor cabling and grounding.
ALARM 56

AMT warning during AMT

Cause:

An adjustable frequency drive warning is given while AMT is being performed.



Remedy:

Resolve the underlying warning.
WARNING 99

Locked

Cause:

The control panel functions have been locked via parameter 018.



Remedy:

Unlock via parameter 018.

How to Clear & Reset Danfoss VLT 2800 Faults

  1. Keypad Reset: Press the red [Stop/Reset] key directly on the front-mounted control panel. If a trip-lock condition has occurred, pressing Stop/Reset clears the alarm status.
  2. Digital Input Reset: Program any digital input terminal (terminals 18, 19, 27, 29, or 33 via parameters 302 to 307) to [1] Reset. Apply a momentary 24V DC signal from terminal 12 to clear the trip.
  3. Serial Communication (RS-485): Send a control command via standard RS-485 terminals (68 and 69) with Bit 7 (Trip Reset) set to 1 in the Danfoss FC Profile or Modbus RTU Control Word.
  4. MCT 10 / VLT Set-up Software: Connect via the serial bus to a PC running Danfoss MCT 10 or VLT Dialog software, navigate to the status monitor, and select “Reset Trip”.
  5. Power Cycle (Cold Reset): Turn off main line supply power. Wait at least 4 minutes until the 7-segment display and status LEDs turn completely off to allow intermediate circuit capacitors to discharge, then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning: Danfoss VLT 2800 inverters retain hazardous electrical energy in their DC bus filter capacitors after mains power is switched off. Always disconnect the AC supply and wait a minimum of 4 minutes. Verify with a calibrated DC voltmeter that voltage across brake/DC terminals 81 (-DC) and 82 (+DC) or motor output terminals 96 (U), 97 (V), 98 (W) is strictly below 50V DC before touching any electrical terminals or wiring.