Danfoss VACON 20 Cold Plate Drive Fault Codes & Diagnostic Guide
Complete fault code directory, trip alarm diagnoses, and reset procedures for the Danfoss VACON® 20 Cold Plate compact drive series. Search or filter through the complete diagnostic database below.
Power Range
0.75 – 7.5 kW (1.0 – 10 HP)
Supply Voltage
208–240V / 380–480V (1/3-Phase)
Control Modes
Sensorless Vector & U/f Control
Operator Interface
Handheld Keypad / VACON Live PC
Complete Danfoss VACON 20 Cold Plate Drive Fault Code Directory
Use the search box in the table below to quickly find your fault code (e.g., type Fault 1, Fault 2, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 1 Overcurrent | Cause: Frequency converter has detected too high a current (>4*In) in the motor cable:
Remedy:
|
| 2 Overvoltage | Cause: The DC-link voltage has exceeded the internal safety limit:
Remedy:
|
| 3 Earth fault | Cause: Current measurement has detected extra leakage current at start:
Remedy:
|
| 8 System fault | Cause:
Remedy:
|
| 9 Under voltage | Cause: The DC-link voltage has gone below the internal safety limit. Most probable cause: supply voltage is too low; frequency converter internal fault; Power outages. Remedy:
|
| 10 Input phase fault | Cause: Input phase is missing. Remedy:
|
| 11 Output phase fault | Cause: Current measurement has detected that there is no current in one motor phase. Remedy:
|
| 13 Frequency converter under temperature | Cause: Heat sink temperature is under -10 °C. Remedy:
|
| 14 Frequency converter over temperature | Cause: Heat sink is overheated. Remedy:
|
| 15 Motor stalled | Cause: Motor stall protection has tripped. Remedy:
|
| 16 Motor over temperature | Cause: Motor overheating has been detected by frequency converter motor temperature model. Motor is overloaded. Remedy:
|
| 17 Motor underload | Cause: Motor underload protection has tripped. Remedy:
|
| 22 EEPROM checksum fault | Cause: Parameter save fault:
Remedy:
|
| 25 Microcontroller watchdog fault | Cause:
Remedy:
|
| 27 Back EMF protection | Cause: Drive has detected that the magnetized motor is running in start situation.
Remedy:
|
| 29 Thermistor fault | Cause: The thermistor input of option board has detected increase of the motor temperature. Remedy:
|
| 34 Internal bus communication | Cause: Ambient interference or defective hardware. Remedy:
|
| 35 Application fault | Cause: Application is not working properly. Remedy:
|
| 41 IGBT Overtemperature | Cause: Overtemperature alarm is issued when the IGBT switch temperature exceeds 110 °C. Remedy:
|
| 50 Analog input select 20% - 100% | Cause: Current at the analogue input is < 4mA; Voltage at the analogue input is < 2 V.
Remedy:
|
| 51 External fault | Cause: Digital input fault. Digital input has been programmed as external fault input and this input is active. Remedy:
|
| 52 Door Panel fault | Cause: Control place is keypad, but door panel has been disconnected. Remedy:
|
| 53 Fieldbus fault | Cause: The data connection between the fieldbus Master and the fieldbus of the drive has broken. Remedy:
|
| 54 Slot fault | Cause: The connection between optional board and API has been broken. Remedy:
|
| 55 Wrong run fault (FWD/REV conflict) | Cause: Run forward and backward are high at the same time. Remedy:
|
| 57 Identification fault | Cause: Identification run has failed. Remedy:
|
| 111 Temperature fault | Cause: Over low or over high temperature. Remedy:
|
How to Clear & Reset Danfoss VACON 20 Cold Plate Faults
- Keypad Reset: Press and hold the [Back/Reset] button on the connected handheld or magnetic alphanumeric text keypad for at least 2 seconds.
- Digital Input Reset (DI): If assigned in parameter settings (e.g., Parameter P2.2.1.2 – Fault Reset), toggle the designated digital input terminal with a 24VDC control pulse.
- VACON Live PC Tool: Connect your PC via serial communication interface (RS-485 / USB adapter), launch VACON Live, and click “Fault Reset” in the online control toolbar.
- Fieldbus Control Word: Assert Bit 7 (Fault Reset) in the Fieldbus Control Word (FB Control Word) via Modbus RTU, Profibus DP, DeviceNet, or CANopen networks.
- Power Cycle: Disconnect input mains power, wait until all LED indicators are completely unlit, and wait at least 5 minutes for intermediate circuit capacitors to discharge before reapplying power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] or motor output terminals U/T1, V/T2, and W/T3 before servicing cabling, removing covers, or unmounting the Danfoss VACON 20 Cold Plate unit from its heatsink.