Danfoss VLT AQUA Drive FC 202 Fault Codes & Diagnostic Guide

Complete alarm, warning, and trip code directory for the Danfoss VLT® AQUA Drive FC 202 dedicated water and wastewater inverter series. Diagnose dry-run detection, flow alarms, overcurrent, and power trips with verified troubleshooting steps.

Dedicated Water & Wastewater Drive Power: 0.25 to 1400 kW (0.34 to 1900 HP) Integrated Cascade Controller & STO
Power Range 0.25 – 1400 kW (0.34 – 1900 HP)
Supply Voltage 200–690V AC (1-Phase & 3-Phase)
Control Modes VVC+, PM Motor Control, & Scalar (U/f)
Operator Interface Graphical LCP 102 / Numerical LCP 101

Complete Danfoss VLT AQUA Drive FC 202 Alarm & Warning Directory

Use the search box in the table below to quickly find your alarm or warning (e.g., type Alarm 13, Alarm 14, Dry Run, or Overvoltage).

Fault/Alarm CodeDescription & Troubleshooting
WARNING 1
10 Volts low

Cause: The control card voltage is less than 10 V from terminal 50. The 10 V supply is overloaded. A short circuit in a connected potentiometer or incorrect wiring can cause this condition.

Remedy:
  • Remove the wiring from terminal 50. If the warning clears, the problem is with the wiring. If the warning does not clear, replace the control card.

WARNING/ALARM 2
Live zero error

Cause: The signal on one of the analog inputs is less than 50% of the minimum value programmed. Broken wiring or a faulty device can cause this.

Remedy:
  • Check connections on all analog mains terminals.
  • Check that drive programming and switch settings match the analog signal type.
  • Perform an input terminal signal test.

WARNING/ALARM 3
No motor

Cause: No motor has been connected to the output of the drive. Appears only if programmed in parameter 1-80.

Remedy:
  • Check the connection between the drive and the motor.

WARNING/ALARM 4
Mains phase loss

Cause: A phase is missing on the supply side, or the mains voltage imbalance is too high. Can also appear for a fault in the input rectifier.

Remedy:
  • Check the supply voltage and supply currents to the drive.

WARNING 5
DC link voltage high

Cause: The DC-link voltage is higher than the high-voltage warning limit. The unit is still active.

Remedy:

No specific troubleshooting steps provided for this warning.


WARNING 6
DC link voltage low

Cause: The DC-link voltage is lower than the low-voltage warning limit. The unit is still active.

Remedy:

No specific troubleshooting steps provided for this warning.


WARNING/ALARM 7
DC overvoltage

Cause: If the DC-link voltage exceeds the limit, the drive trips after a certain time.

Remedy:
  • Connect a brake resistor.
  • Extend the ramp time.
  • Change the ramp type.
  • Activate functions in parameter 2-10 Brake Function.
  • If the alarm occurs during a power sag, use kinetic back-up.

WARNING/ALARM 8
DC under voltage

Cause: If the DC-link voltage drops below the undervoltage limit, the drive trips after a fixed time delay.

Remedy:
  • Check that the supply voltage matches the drive voltage.
  • Perform an input voltage test.
  • Perform a soft-charge circuit test.

WARNING/ALARM 9
Inverter overload

Cause: The drive has run with more than 100% overload for too long and is about to cut out. The drive cannot be reset until the counter is below 90%.

Remedy:
  • Compare the output current on the LCP with the drive rated current and the measured motor current.
  • Monitor the thermal drive load on the LCP.

WARNING/ALARM 10
Motor overload temperature

Cause: According to the electronic thermal protection (ETR), the motor is too hot.

Remedy:
  • Check for motor overheating and mechanical overload.
  • Check motor current set in parameter 1-24.
  • Ensure motor data in parameters 1-20 to 1-25 is correct.
  • Running AMA (Automatic Motor Adaptation) tunes the drive to the motor more accurately.

WARNING/ALARM 11
Motor thermistor overtemp

Cause: The thermistor may be disconnected or the motor is overheating.

Remedy:
  • Check for motor overheating and mechanical overload.
  • Check that the thermistor is connected correctly to the appropriate terminal (53, 54, or digital inputs) and terminal 50.
  • Check that parameter 1-93 Thermistor Source selects the correct terminal.

WARNING/ALARM 12
Torque limit

Cause: The torque has exceeded the programmed value in either motor or generator mode.

Remedy:
  • If exceeded during ramp-up/ramp-down, extend the ramp time.
  • If it occurs while running, increase the torque limit.
  • Check the application for excessive current draw.

WARNING/ALARM 13
Over current

Cause: Inverter peak current limit (approx. 200% of rated current) is exceeded. Shock loading or quick acceleration can cause this.

Remedy:
  • Remove power and check if the motor shaft can be turned.
  • Check that the motor size matches the drive and data is correct in parameters 1-20 to 1-25.

ALARM 14
Earth (ground) fault

Cause: There is current from the output phase to ground, either in the cable or in the motor itself.

Remedy:
  • Remove power and repair the ground fault.
  • Check for ground faults in the motor using a megohmmeter.
  • Reset any potential offset in the current transducers.

ALARM 15
Hardware mismatch

Cause: A fitted option is not operational with the present control card hardware or software.

Remedy:
  • Record the value of parameter 15-40 FC Type and 15-41 Power Section and contact Danfoss.

ALARM 16
Short circuit

Cause: There is short-circuiting in the motor or motor wiring.

Remedy:
  • Remove the power to the drive and repair the short circuit.
  • Check for the correct current scaling card.

WARNING/ALARM 17
Control word timeout

Cause: There is no communication to the drive.

Remedy:
  • Check connections on the serial communication cable.
  • Increase parameter 8-03 Control Timeout Time.
  • Check communication equipment operation.

WARNING/ALARM 20
Temp. input error

Cause: The temperature sensor is not connected.

Remedy:

No specific troubleshooting steps provided.


WARNING/ALARM 21
Parameter error

Cause: The parameter is out of range. The parameter number is shown in the display.

Remedy:
  • Set the affected parameter to a valid value.

WARNING/ALARM 22
Hoist mechanical brake

Cause: An issue with the hoist mechanical brake. The value indicates the cause: 0 = Torque reference was not reached before timeout. 1 = Expected brake feedback was not received before timeout.

Remedy:

No specific troubleshooting steps provided.


WARNING 23
Internal fan fault

Cause: Protective function that checks if the internal fan is running/mounted.

Remedy:
  • Check for proper fan operation.
  • Cycle power to the drive and check that the fan operates briefly at start-up.
  • Check sensors on the control card.

WARNING 24
External fan fault

Cause: Protective function that checks if the external fan is running/mounted. Can also show a communication error.

Remedy:

Fan troubleshooting:

  • Cycle power and check that the fan operates briefly at start-up.
  • Check for proper fan operation.

Power card troubleshooting:

  • Check the wiring between the power card and the control card.
  • Power card may need to be replaced.
  • Control card may need to be replaced.

WARNING 25
Brake resistor short circuit

Cause: A short circuit in the brake resistor is detected. The brake function is disabled.

Remedy:
  • Remove power to the drive and replace the brake resistor.

WARNING/ALARM 26
Brake resistor power limit

Cause: The power to the brake resistor is over 90% of its rating. A surge in power can cause overheating.

Remedy:
  • Remove power to the drive.
  • Remove the brake resistor.
  • Troubleshoot the short circuit.

WARNING/ALARM 28
Brake check failed

Cause: The brake resistor is not connected or not working.

Remedy:
  • Check parameter 2-15 Brake Check.

ALARM 29
Heat sink temp

Cause: The maximum temperature of the heat sink has been exceeded.

Remedy:

Check for the following conditions:

  • Ambient temperature too high
  • Motor cable too long
  • Incorrect airflow clearance
  • Blocked airflow around the drive
  • Damaged heat sink fan
  • Dirty heat sink

ALARM 30
Motor phase U missing

Cause: Motor phase U between the drive and the motor is missing.

Remedy:
  • Remove the power from the drive and check motor phase U.

ALARM 31
Motor phase V missing

Cause: Motor phase V between the drive and the motor is missing.

Remedy:
  • Remove the power from the drive and check motor phase V.

ALARM 32
Motor phase W missing

Cause: Motor phase W between the drive and the motor is missing.

Remedy:
  • Remove the power from the drive and check motor phase W.

ALARM 33
Inrush fault

Cause: Too many power-ups have occurred within a short time period.

Remedy:
  • Let the unit cool to operating temperature.
  • Check potential DC-link fault to ground.

WARNING/ALARM 34
Fieldbus communication fault

Cause: The fieldbus on the communication option card is not working.

Remedy:

No specific troubleshooting steps provided.


WARNING/ALARM 35
Option fault

Cause: An option-specific alarm is received, likely caused by a power-up or communication fault.

Remedy:

No specific troubleshooting steps provided.


WARNING/ALARM 36
Mains failure

Cause: The supply voltage to the drive system is lost.

Remedy:
  • Check fuses and mains supply.
  • Check that mains voltage conforms to specifications.
  • Check for other voltage-related alarms.

ALARM 37
Phase imbalance

Cause: There is a current imbalance between the power units.

Remedy:

No specific troubleshooting steps provided.


ALARM 38
Internal fault

Cause: An internal fault has occurred. A specific code number is shown on the display. Refer to the manual for code definitions.

Remedy:
  • Cycle power.
  • Check that the option is properly installed.
  • Check for loose or missing wiring.
  • Contact Danfoss service with the specific code number.

ALARM 39
Heat sink sensor

Cause: No feedback from the heat sink temperature sensor. Signal from IGBT thermal sensor is not available on the power card.

Remedy:
  • Check the ribbon cable between the power card and gatedrive card.
  • Check for a defective power card or gatedrive card.

WARNING 40
Overload of digital output terminal 27

Cause: Check the load connected to terminal 27 or remove the short-circuit connection.

Remedy:
  • Check parameter 5-00 Digital I/O Mode and parameter 5-01 Terminal 27 Mode.

WARNING 41
Overload of digital output terminal 29

Cause: Check the load connected to terminal 29 or remove the short-circuit connection.

Remedy:
  • Check parameter 5-00 Digital I/O Mode and parameter 5-02 Terminal 29 Mode.

WARNING 42
Overload of digital output on X30/6 or X30/7

Cause: Check the load connected to the specified terminal or remove the short-circuit connection.

Remedy:
  • Check relevant parameters (5-32 or 5-33) for the terminal in question.

ALARM 43
Ext. supply

Cause: Extended Relay Option MCB 113 is mounted without an external 24 V DC supply.

Remedy:
  • Connect a 24 V DC external supply or specify that no external supply is used via parameter 14-80.

ALARM 45
Earth fault 2

Cause: Ground fault.

Remedy:
  • Check for proper grounding and loose connections.
  • Check for proper wire size.
  • Check the motor cables for short circuits or leakage currents.

ALARM 46
Power card supply

Cause: The supply on the power card is out of range. 4 supplies are generated: 48 V, 24 V, 5 V, ±18 V.

Remedy:
  • Check for a defective power card, control card, or option card.
  • If a 24 V DC supply is used, verify proper supply power.
  • Check various fans for defects on D-sized and E-sized drives.

WARNING 47
24 V supply low

Cause: The 24 V supply on the power card is out of range.

Remedy:
  • Check for a defective power card.

WARNING 48
1.8 V supply low

Cause: The 1.8 V DC supply on the control card is outside of the allowable limits.

Remedy:
  • Check for a defective control card.
  • If an option card is present, check for overvoltage.

WARNING 49
Speed limit

Cause: The motor speed is outside of the specified range in parameters 4-11 and 4-13.

Remedy:

No specific troubleshooting steps provided.


ALARM 50
AMA calibration failed

Cause: The Automatic Motor Adaptation (AMA) calibration has failed.

Remedy:
  • Contact the Danfoss supplier or service department.

ALARM 51
AMA check Unom and Inom

Cause: The settings for motor voltage, current, and power are wrong.

Remedy:
  • Check the settings in parameters 1-20 to 1-25.

ALARM 52
AMA low Inom

Cause: The motor current is too low for the AMA to operate.

Remedy:
  • Check the settings in parameter 1-24 Motor Current.

ALARM 53
AMA motor too big

Cause: The motor is too large for the AMA to operate.

Remedy:

No specific troubleshooting steps provided.


ALARM 54
AMA motor too small

Cause: The motor is too small for the AMA to operate.

Remedy:

No specific troubleshooting steps provided.


ALARM 55
AMA parameter out of range

Cause: The AMA cannot run because motor parameter values are outside the acceptable range.

Remedy:

No specific troubleshooting steps provided.


ALARM 56
AMA interrupted by user

Cause: The AMA was manually interrupted.

Remedy:

No specific troubleshooting steps provided.


ALARM 57
AMA internal fault

Cause: An internal fault occurred during the AMA. Repeated restarts can overheat the motor.

Remedy:
  • Try to restart the AMA.

ALARM 58
AMA Internal fault

Cause: An internal fault occurred during the AMA.

Remedy:
  • Contact the Danfoss supplier.

WARNING 59
Current limit

Cause: The current is higher than the value in parameter 4-18 Current Limit.

Remedy:
  • Ensure motor data is set correctly.
  • Increase the current limit if necessary, ensuring safe operation.

WARNING 60
External interlock

Cause: A digital input signal indicates an external fault condition has commanded the drive to trip.

Remedy:
  • Clear the external fault condition.
  • To resume, apply 24 V DC to the terminal and reset the drive.

WARNING/ALARM 61
Feedback error

Cause: An error is detected between calculated speed and the speed measurement from the feedback device.

Remedy:
  • Check settings in parameter 4-30 Motor Feedback Loss Function.
  • Set tolerable error in parameter 4-31 and loss time in 4-32.

WARNING 62
Output frequency at maximum limit

Cause: The output frequency has reached the maximum limit set in parameter 4-19.

Remedy:
  • Check the application for possible causes.
  • Increase the output frequency limit, ensuring safe operation.

ALARM 63
Mechanical brake low

Cause: The actual motor current has not exceeded the release brake current within the start delay time window.

Remedy:

No specific troubleshooting steps provided.


WARNING 64
Voltage Limit

Cause: The load and speed combination demands a motor voltage higher than the actual DC-link voltage.

Remedy:

No specific troubleshooting steps provided.


WARNING/ALARM 65
Control card over temperature

Cause: The cutout temperature of the control card (85 °C / 185 °F) has been reached.

Remedy:
  • Check that the ambient operating temperature is within limits.
  • Check for clogged filters.
  • Check fan operation.
  • Check the control card.

WARNING 66
Heat sink temperature low

Cause: The drive is too cold to operate, based on the IGBT module's temperature sensor.

Remedy:
  • Increase the ambient temperature of the unit.
  • A trickle amount of current can be supplied by setting parameter 2-00 DC Hold/Preheat Current.

ALARM 67
Option module configuration has changed

Cause: One or more options have been added or removed since the last power-down.

Remedy:
  • Check that the configuration change is intentional and reset the unit.

ALARM 68
Safe Stop activated

Cause: Safe Torque Off (STO) has been activated.

Remedy:
  • To resume normal operation, apply 24 V DC to terminal 37, then send a reset signal.

ALARM 69
Power card temperature

Cause: The temperature sensor on the power card is either too hot or too cold.

Remedy:
  • Check that the ambient operating temperature is within limits.
  • Check for clogged filters.
  • Check fan operation.

ALARM 70
Illegal FC configuration

Cause: The control card and power card are incompatible.

Remedy:
  • Contact the Danfoss supplier with the type code and part numbers to check compatibility.

WARNING/ALARM 71
PTC 1 Safe Stop

Cause: Safe Torque Off (STO) has been activated from the PTC Thermistor Card because the motor is too warm.

Remedy:
  • Once the motor cools and the input is deactivated, normal operation can resume after a reset signal is sent.

ALARM 72
Dangerous failure

Cause: STO with trip lock. An unexpected combination of STO commands has occurred.

Remedy:

No specific troubleshooting steps provided.


WARNING 73
Safe Stop auto restart

Cause: Safe Torque Off (STO) activated. With automatic restart enabled, the motor can start when the fault is cleared.

Remedy:

No specific troubleshooting steps provided.


ALARM 74
PTC Thermistor

Cause: Alarm related to VLT® PTC Thermistor Card MCB 112. The PTC is not working.

Remedy:

No specific troubleshooting steps provided.


ALARM 75
Illegal profile sel.

Cause: Do not write the parameter value while the motor is running.

Remedy:
  • Stop the motor before writing the MCO profile to parameter 8-10.

WARNING 76
Power unit setup

Cause: The required number of power units does not match the detected number of active power units.

Remedy:
  • Confirm that the spare part and its power card are the correct part number.
  • Ensure that the 44-pin cables are mounted properly.

WARNING 77
Reduced power mode

Cause: Applies to multi-drive systems. The system is operating in reduced power mode.

Remedy:

No specific troubleshooting steps provided.


ALARM 78
Tracking error

Cause: The difference between setpoint and actual value exceeds the value in parameter 4-35 Tracking Error.

Remedy:
  • Disable the function or select an alarm/warning in parameter 4-34.
  • Investigate mechanics around the load and motor.
  • Adjust the tracking error band.

ALARM 79
Illegal power section configuration

Cause: The scaling card has an incorrect part number or is not installed.

Remedy:

No specific troubleshooting steps provided.


ALARM 80
Drive initialised to default value

Cause: Parameter settings are initialized to default settings after a manual reset.

Remedy:
  • To clear the alarm, reset the unit.

ALARM 81
CSIV corrupt

Cause: CSIV file has syntax errors.

Remedy:

No specific troubleshooting steps provided.


ALARM 82
CSIV parameter error

Cause: CSIV failed to initialize a parameter.

Remedy:

No specific troubleshooting steps provided.


ALARM 83
Illegal option combination

Cause: The mounted options are incompatible.

Remedy:

No specific troubleshooting steps provided.


ALARM 84
No safety option

Cause: The safety option was removed without applying a general reset.

Remedy:
  • Reconnect the safety option.

ALARM 88
Option detection

Cause: A change in the option layout is detected while parameter 14-89 is set to Frozen configuration.

Remedy:
  • To apply the change, enable option layout changes in parameter 14-89.
  • Alternatively, restore the correct option configuration.

WARNING 89
Mechanical brake sliding

Cause: The hoist brake monitor detects a motor speed exceeding 10 RPM.

Remedy:

No specific troubleshooting steps provided.


ALARM 90
Feedback monitor

Cause: An issue with the encoder/resolver option.

Remedy:
  • Check the connection to the encoder/resolver option and replace if necessary.

ALARM 91
Analog input 54 wrong settings

Cause: Wrong setting for analog input 54.

Remedy:
  • Set switch S202 in position OFF (voltage input) when a KTY sensor is connected.

ALARM 96
Start delayed

Cause: The motor start has been delayed due to short-cycle protection.

Remedy:
  • Troubleshoot the system and reset the drive after clearing the fault.

WARNING 97
Stop delayed

Cause: Stopping the motor has been delayed because it has run for less than the minimum time specified in parameter 22-77.

Remedy:

No specific troubleshooting steps provided.


WARNING 98
Clock fault

Cause: Time is not set, or the RTC clock has failed.

Remedy:
  • Reset the clock in parameter 0-70 Date and Time.

ALARM 99
Locked rotor

Cause: The rotor is blocked.

Remedy:

No specific troubleshooting steps provided.


WARNING/ALARM 104
Mixing fan fault

Cause: The fan is not operating.

Remedy:
  • Cycle power to the drive to determine if the warning/alarm returns.

WARNING/ALARM 122
Mot. rotat. unexp.

Cause: The drive performs a function that requires the motor to be at a standstill when it is not.

Remedy:

No specific troubleshooting steps provided.


ALARM 144
Inrush Supply

Cause: A supply voltage on the inrush card is out of range.

Remedy:

See the bit field result report value for more details:

  • Bit 2: Vcc high.
  • Bit 3: Vcc low.
  • Bit 4: Vdd high.
  • Bit 5: Vdd low.

ALARM 145
External SCR disable

Cause: The alarm indicates a series DC-link capacitor voltage imbalance.

Remedy:

No specific troubleshooting steps provided.


WARNING/ALARM 146
Mains voltage

Cause: Mains voltage is outside a valid operating range.

Remedy:

The following report values provide more details:

  • Voltage too low: 0=R-S, 1=S-T, 2=T-R
  • Voltage too high: 3=R-S, 4=S-T, 5=T-R

WARNING/ALARM 147
Mains frequency

Cause: Mains frequency is outside a valid operating range.

Remedy:

Report value provides more details:

  • 0: frequency too low.
  • 1: frequency too high.

WARNING/ALARM 148
System temp

Cause: One or more of the system temperature measurements is too high.

Remedy:

No specific troubleshooting steps provided.


WARNING 163
ATEX ETR cur.lim.warning

Cause: The drive has run above the characteristic curve for more than 50s.

Remedy:

No specific troubleshooting steps provided.


ALARM 164
ATEX ETR cur.lim.alarm

Cause: Operating above the characteristic curve for more than 60s within a 600s period activates the alarm and trips the drive.

Remedy:

No specific troubleshooting steps provided.


WARNING 165
ATEX ETR freq.lim.warning

Cause: The drive is running for more than 50s below the allowed minimum frequency.

Remedy:

No specific troubleshooting steps provided.


ALARM 166
ATEX ETR freq.lim.alarm

Cause: The drive has operated for more than 60s below the allowed minimum frequency.

Remedy:

No specific troubleshooting steps provided.


WARNING 200
Fire mode

Cause: The drive is operating in fire mode.

Remedy:
  • Warning clears when fire mode is removed. Refer to the fire mode data in the alarm log.

WARNING 201
Fire mode was active

Cause: The drive has entered fire mode.

Remedy:
  • Cycle power to the unit to remove the warning. Refer to the fire mode data in the alarm log.

WARNING 202
Fire mode limits exceeded

Cause: While in fire mode, one or more alarm conditions that would normally trip the unit have been ignored. This voids unit warranty.

Remedy:
  • Cycle power to the unit to remove the warning. Refer to the fire mode data in the alarm log.

WARNING 203
Missing motor

Cause: With a drive operating multi-motors, an underload condition was detected. This can indicate a missing motor.

Remedy:
  • Inspect the system for proper operation.

WARNING 204
Locked rotor

Cause: With a drive operating multi-motors, an overload condition was detected. This can indicate a locked rotor.

Remedy:
  • Inspect the motor for proper operation.

WARNING 219
Compressor interlock

Cause: At least 1 compressor is inversely interlocked via a digital input.

Remedy:
  • The interlocked compressors can be viewed in parameter 25-87 Inverse Interlock.

ALARM 243
Brake IGBT

Cause: Only for multi-drive systems. Equivalent to alarm 27, Brake chopper fault. Can be caused by a blown DC fuse, incorrect brake jumper position, or Klixon switch opening.

Remedy:

No specific troubleshooting steps provided.


ALARM 245
Heat sink sensor

Cause: Only for multi-drive systems. No feedback from the heat sink temperature sensor. Equivalent to alarm 39.

Remedy:

Check the following:

  • Power card
  • Gatedrive card
  • Ribbon cable between them

ALARM 246
Power card supply

Cause: Only for multi-drive systems. It is equivalent to alarm 46, Power card supply.

Remedy:

No specific troubleshooting steps provided.


ALARM 247
Power card temperature

Cause: Only for multi-drive systems. It is equivalent to alarm 69, Power card temperature.

Remedy:

No specific troubleshooting steps provided.


ALARM 248
Illegal power section configuration

Cause: Only for multi-drive systems. It is equivalent to alarm 79, Illegal power section configuration.

Remedy:
  • Check the current scaling cards on the MDCIC.

WARNING 250
New spare part

Cause: The power or switch mode supply has been exchanged.

Remedy:
  • Restore the drive type code in the EEPROM. Select the correct type code in parameter 14-23 and save to EEPROM.

WARNING 251
New type code

Cause: The power card or other components have been replaced and the type code has been changed.

Remedy:
  • Reset to remove the warning and to resume normal operation.

How to Clear & Reset Danfoss VLT AQUA Drive FC 202 Faults

  1. LCP Keypad Reset: Press the yellow [Reset] key directly on the control panel. If operating in automatic pumping control (Auto On) and locked out on trip, press [Off/Reset] before switching back to [Auto On].
  2. Digital Input Reset (DI): If programmed in parameter 5-12 (Terminal 27 Digital Input) or any input terminal (18, 19, 27, 29, 32, 33) set to [1] Reset, pulse the terminal with 24V DC from terminal 12 or 13.
  3. Danfoss MCT 10 Software: Connect via the USB Type-B port or RS-485 serial terminals (68/69), open the Danfoss MCT 10 Set-up Software, and trigger an active alarm reset command from the diagnostic window.
  4. Fieldbus Control Word: Set Bit 7 (Trip Reset) from 0 to 1 in the Danfoss FC Profile or PROFIdrive Control Word over BACnet, Modbus RTU, PROFINET, or EtherNet/IP.
  5. Power Cycle (Cold Reset): Disconnect incoming AC mains line power. Wait 4 to 20 minutes (up to 40 minutes on high-power frames) until the LCP display completely powers down and capacitors discharge before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Danfoss VLT AQUA Drive FC 202 inverters contain high-voltage intermediate DC bus capacitors. Disconnect all AC power, auxiliary supplies, and load sharing connections. Wait a minimum of 4 to 20 minutes (up to 40 minutes on high-power modular frames) and verify with a calibrated multimeter that DC voltage across terminals -88 (-DC) and +89 (+DC) or motor output terminals 96 (U), 97 (V), 98 (W) measures strictly below 50V DC before servicing pump wiring or internal components.