Danfoss VLT 3500 Drive Fault Codes & Diagnostic Guide

Complete troubleshooting directory, alarm trip list, warning codes, and recovery procedures for the legacy Danfoss VLT® Series 3500 inverter. Search or filter through the complete diagnostic database below.

Legacy HVAC & Industrial Inverter Power: 1.1 to 200 kW (1.5 to 300 HP) VVC Voltage Vector Control
Power Range 1.1 – 200 kW (1.5 – 300 HP)
Supply Voltage 200–230V / 380–500V (3-Phase)
Control Modes VVC (Voltage Vector) & U/f
Operator Interface Alphanumeric LCD Display Panel

Complete Danfoss VLT 3500 Drive Fault Code Directory

Use the search box in the table below to quickly find your alarm code (e.g., type Error 04, Overcurrent, or Trip Locked).

Fault Code and MeaningCause and Remedy
Error code 1
Inverter Fault (INVERT FAULT)

Cause: There is a fault on the power side of the drive.

Remedy:

  • Check the power section of the drive.

  • Contact service if the issue persists.


Error code 2
Overvoltage (OVER VOLTAGE)

Cause: The DC bus voltage is above the overvoltage limit of the drive.

Remedy:

  • Check for high mains voltage.

  • Check for deceleration times that are too short (regenerative energy).

  • Refer to the voltage limit table in the manual.


Error code 3
Undervoltage (UNDER VOLTAGE)

Cause: The DC bus voltage is below the undervoltage limit of the drive.

Remedy:

  • Check the input supply voltage.

  • Check for phase loss.

  • Refer to the voltage limit table in the manual.


Error code 4
Overcurrent (OVER CURRENT)

Cause: The peak current limit of the inverter (approx. 250% of rated current) has been exceeded for more than 7 to 11 seconds. This causes a Trip Locked fault.

Remedy:

  • Remove and reapply AC power to reset (Trip Locked).

  • Check for short circuits or motor issues.

  • Check if the load is too heavy.


Error code 5
Ground Fault (GROUND FAULT)

Cause: There is a current path from the output phases to the ground, either in the wiring between the drive and the motor, or within the motor.

Remedy:

  • This causes a Trip Locked fault (requires power cycle to reset).

  • Check the motor wiring for ground faults.

  • Check the motor insulation.


Error code 6
Overtemperature (OVER TEMP)

Cause: Too high a temperature has been measured within the drive.

Remedy:

  • Allow a cool-down period before resetting.

  • Check the ambient temperature and ventilation.

  • This causes a Trip Locked fault.


Error code 7
Inverter Overloaded (OVERLOAD)

Cause: The electronic thermal inverter protection reports that the drive has tripped because of overload (too high a current for too long). The counter has reached 100%.

Remedy:

  • Reduce the load on the motor/drive.

  • Check parameter settings related to limits.


Error codes 8 and 15
Motor Overloaded (MOTOR TRIP)

Cause: The motor electronic thermal relay (ETR) protection reports that the motor is too hot.

Remedy:

  • Ensure "Trip" is selected in parameter 315 for this alarm to activate.

  • Check motor cooling and load.


Error code 9
Current Limit (CURRENT LIMIT)

Cause: The motor current has exceeded the value of parameter 209 for a longer time than that permitted in parameter 310.

Remedy:

  • Check the load on the motor.

  • Adjust Current Limit (param 209) or time delay (param 310) if appropriate.


KEY DISABLED
Prohibited Parameter Change

Cause: An attempt is made to change a parameter when Factory Setup has been selected in parameter 001.

Remedy:

  • Change parameter 001 to setup 1, 2, 3, or 4 to allow changes.


ONLY IN STOP
Prohibited Function Change

Cause: An attempt is made to change data that cannot be changed while the drive is running.

Remedy:

  • Press Stop/Reset to stop the drive.

  • Change the parameter.


LOCK OPEN
Keypad Lockout

Cause: An attempt is made to change a parameter, but the mechanical keypad lockout is open.

Remedy:

  • Switch pin 01 must be closed before any parameter is changed.


LIMIT
Range Limit

Cause: A parameter is being changed and one end of the permissible range has been reached.

Remedy:

  • Do not exceed the minimum or maximum values defined for the parameter.


VOLTAGE LOW
Low Voltage Warning

Cause: The DC bus voltage is below the warning limit. The inverter is still operating.

Remedy:

  • Monitor mains supply voltage.


VOLTAGE HIGH
High Voltage Warning

Cause: The DC bus voltage is above the warning limit. The inverter is still operating.

Remedy:

  • Monitor mains supply voltage.

  • Check for regenerative energy from the load.


REF FAULT
Reference Fault

Cause: An analog input signal with a “live zero” (e.g., 4-20 mA, 1-5 V) is below half the minimum level.

Remedy:

  • Check the signal source and wiring to terminal 53 or 60.


NO MOTOR
No Motor

Cause: The motor check function in parameter 313 detects that no motor has been connected to the drive’s output.

Remedy:

  • Check motor connections.


LO FREQ WARN
Low Frequency Warning

Cause: The output frequency is lower than the value selected in parameter 210.

Remedy:

  • Check process requirements or adjust parameter 210.


HI FREQ WARN
High Frequency Warning

Cause: The output frequency is higher than the value selected in parameter 211.

Remedy:

  • Check process requirements or adjust parameter 211.


LO CURR WARN
Low Current Warning

Cause: The output current is lower than the value selected in parameter 212.

Remedy:

  • Check for load loss (e.g., broken belt).

  • Adjust parameter 212.


HI CURR WARN
High Current Warning

Cause: The output current is higher than the value selected in parameter 213.

Remedy:

  • Check for mechanical binding or high load.

  • Adjust parameter 213.


NO 24 VOLT
24 V Fault

Cause: The 24 V DC supply to the control card is not present.

Remedy:

  • Check the internal power supply or external 24V inputs.


EEPROM ERROR
EEPROM Fault

Cause: EEPROM fault. Data changes are not saved when AC power is removed.

Remedy:

  • Cycle power.

  • If the fault persists, the control card may require replacement.


Start-up Test (CONTROL CARD FAULT)
Control card problem

Cause: The drive carries out a self-test when AC power is applied. This message indicates a control card problem.



Remedy:

  • Contact a Danfoss service center.


Inverter Fault
Power section defective

Cause: An operational problem caused the Inverter to fault trip to protect itself or the motor. The power section of the drive is defective.



Remedy:

  • The cause of the fault must be found and eliminated.


Overvoltage
DC bus voltage too high

Cause: The voltage in the DC bus is too high. Possible causes include:

  • Input voltage too high.

  • Transients on the input.

  • Regenerative motor operation (energy returned to drive during deceleration).




Remedy:

  • If caused by deceleration, extend ramp time using parameters 216 and 218.


Undervoltage
DC bus voltage too low

Cause: The voltage of the DC bus is too low. Possible causes include:

  • Input voltage too low.

  • Failure of the charging circuit/rectifier of the drive.




Remedy:

  • Check the input line voltage before calling for service.


Overcurrent
Rectifier peak current exceeded

Cause: Upper limit of the rectifier peak current has been exceeded, possibly because of a short circuit in the output of the drive.



Remedy:

  • Check for an output short circuit before calling for service.


Ground Fault
Ground fault on drive output

Cause: Indicates a ground fault on the drive's output. Possible causes include:

  • Motor or motor wiring problems.

  • Motor wiring is too long (over 1,000 feet).




Remedy:

  • Check motor and motor wiring.

  • Ensure wiring is as short as possible.

  • Reduce output carrier frequency to 4.5 kHz or lower.


Critical Temperature
Internal temperature too high

Cause: The temperature inside the drive is too high. Possible causes include:

  • Ambient temperature is above 104°F (40°C).

  • The heat sink of the drive is dirty or obstructed.

  • The fan(s) is not operating.

  • The drive is not mounted vertically directly against a solid surface.


Overload
Electronic thermal overload protection tripped

Cause: The motor has consumed more than 110% of the rated current of the drive for too long.



Remedy:

  • Reduce the motor load.

  • If not possible, the application may require a larger drive.

  • Ensure the motor is not overloaded before installing a larger drive.


Motor Trip
Motor electronic thermal relay (ETR) active

Cause: Current consumed by the motor at low speed has been too high for too long (loaded excessively at low speed).



Remedy:

  • Try to reduce the load at low speed.

  • Make the motor run at a higher speed.

  • Replace motor with a larger one or provide extra cooling.

  • Note: Protection can be turned off in parameter 315 (risk of burning up motor).


How to Clear & Reset Danfoss VLT 3500 Drive Faults

  1. Keypad Reset: Press the [Stop/Reset] key on the front alphanumeric operator panel. Note: if the drive indicates a “Trip Locked” state (such as after an earth fault or severe short-circuit), line power must be removed and reapplied before a reset can occur.
  2. Digital Input Reset (DI): If configured via digital input parameter settings (e.g., Terminal 16 programmed for Reset), pulse the 24V DC terminal high.
  3. Automatic Reset: If programmed in Parameter 309 (Reset Function), the drive can automatically attempt up to 10 resets after a trip with an interval delay set in Parameter 312.
  4. Serial Bus Reset: Transmit a control word reset command via the RS-485 serial communication port using Danfoss FC Protocol or Metasys N2 network.
  5. Power Cycle & Capacitor Discharge: Switch off AC mains power completely. Wait 4 to 14 minutes (depending on model frame size) until the LCD display fades and internal intermediate capacitors discharge safely before switching power back on.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across DC bus terminals or motor output terminals (U, V, W) before touching wiring or internal components. Wait at least 4 to 14 minutes after disconnecting mains supply.