Danfoss VACON 10 Drive Fault Codes & Diagnostic Guide
Complete fault code list, alarm troubleshooting directory, and step-by-step diagnostic solutions for the compact Danfoss VACON® 10 micro drive series. Search or filter through the complete diagnostic database below.
Power Range
0.18 – 5.5 kW (0.25 – 7.5 HP)
Supply Voltage
115V / 208–240V / 380–480V (1/3-Ph)
Control Modes
U/f Frequency & Open-Loop Vector
Operator Interface
Integrated 7-Segment LED Keypad
Complete Danfoss VACON 10 Drive Fault Code Directory
Use the search box in the table below to quickly find your fault code (e.g., type F1, F2, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 1 Overcurrent | Cause: Frequency converter has detected too high a current (>4*IN) in the motor cable.
Remedy:
|
| 2 Overvoltage | Cause: The DC-link voltage has exceeded the internal safety limit.
Remedy:
|
| 3 Earth fault | Cause: Current measurement has detected extra leakage current at start.
Remedy:
|
| 8 System fault | Cause:
Remedy:
|
| 9 Undervoltage | Cause: The DC-link voltage has gone below the internal safety limit.
Remedy:
|
| 11 Output phase fault | Cause: Current measurement has detected that there is no current in one motor phase. Remedy:
|
| 13 Frequency converter undertemperature | Cause: Heat sink temperature is under -10 °C. Remedy:
|
| 14 Frequency converter overtemperature | Cause: Heat sink is overheated. Remedy:
|
| 15 Motor stalled | Cause: Motor stall protection has tripped. Remedy:
|
| 16 Motor overtemperature | Cause: Motor overheating has been detected by frequency converter motor temperature model. Motor is overloaded. Remedy:
|
| 17 Motor underload | Cause: Motor underload protection has tripped. Remedy:
|
| 22 EEPROM check sum fault | Cause: Parameter save fault.
Remedy:
|
| 25 Microcontroller watchdog fault | Cause:
Remedy:
|
| 27 Back EMF protection | Cause: Drive has detected that the magnetized motor is running in start situation.
Remedy:
|
| 29 Thermistor fault | Cause: The thermistor input of option board has detected increase. Remedy:
|
| 34 Internal bus communication | Cause: Ambient interference or defective hardware. Remedy:
|
| 35 Application fault | Cause: Application is not working properly. Remedy:
|
| 41 IGBT Overtemperature | Cause: Over temperature alarm is issued when the IGBT switch temperature exceeds 110 °C. Remedy:
|
| 50 Analog input select | Cause: Current at the analogue input is < 4mA; Voltage at the analogue input is < 2 V (selected signal range 4 to 20 mA or 2 to 10 V).
Remedy:
|
| 51 External fault | Cause: Digital input fault. Digital input has been programmed as external fault input and this input is active. Remedy:
|
| 53 Fieldbus fault | Cause: The data connection between the fieldbus Master and the fieldbus of the drive has broken. Remedy:
|
| 55 Wrong run fault (FWD/REV conflict) | Cause: Run forward and backward at the same time. Remedy:
|
| 57 Identification fault | Cause: Identification run has failed. Remedy:
|
| 111 Temperature fault | Cause: Over low or over high temperature. Remedy:
|
How to Clear & Reset Danfoss VACON 10 Faults
- Keypad Reset: Press the red [Stop/Reset] key on the integrated 7-segment LED keypad panel. If the drive is locked in a fault state, resolve the underlying problem before resetting.
- Digital Input Reset (DI): If assigned in parameter settings (parameter P2.2.1.2 – Fault Reset), pulse the assigned digital input terminal (DIN4 to DIN6) with a +24V DC signal.
- VACON Live PC Software: Connect via the serial communication interface adapter (MCA-01 / RS-485 to USB cable), open VACON Live, and click “Fault Reset” in the online monitoring dashboard.
- Fieldbus Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in the Fieldbus Control Word via optional embedded Modbus RTU (RS-485 serial interface).
- Power Cycle: Disconnect AC line power, wait until the 7-segment display goes completely blank, and wait at least 5 minutes for the internal DC bus capacitors to discharge safely before restoring power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] or motor output terminals U/T1, V/T2, and W/T3 before servicing wiring, opening covers, or handling the Danfoss VACON 10 drive unit.