Danfoss VLT 3500 Drive Fault Codes & Diagnostic Guide
Complete troubleshooting directory, alarm trip list, warning codes, and recovery procedures for the legacy Danfoss VLT® Series 3500 inverter. Search or filter through the complete diagnostic database below.
Power Range
1.1 – 200 kW (1.5 – 300 HP)
Supply Voltage
200–230V / 380–500V (3-Phase)
Control Modes
VVC (Voltage Vector) & U/f
Operator Interface
Alphanumeric LCD Display Panel
Complete Danfoss VLT 3500 Drive Fault Code Directory
Use the search box in the table below to quickly find your alarm code (e.g., type Error 04, Overcurrent, or Trip Locked).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Error code 1 Inverter Fault (INVERT FAULT) | Cause: There is a fault on the power side of the drive. Remedy:
|
| Error code 2 Overvoltage (OVER VOLTAGE) | Cause: The DC bus voltage is above the overvoltage limit of the drive. Remedy:
|
| Error code 3 Undervoltage (UNDER VOLTAGE) | Cause: The DC bus voltage is below the undervoltage limit of the drive. Remedy:
|
| Error code 4 Overcurrent (OVER CURRENT) | Cause: The peak current limit of the inverter (approx. 250% of rated current) has been exceeded for more than 7 to 11 seconds. This causes a Trip Locked fault. Remedy:
|
| Error code 5 Ground Fault (GROUND FAULT) | Cause: There is a current path from the output phases to the ground, either in the wiring between the drive and the motor, or within the motor. Remedy:
|
| Error code 6 Overtemperature (OVER TEMP) | Cause: Too high a temperature has been measured within the drive. Remedy:
|
| Error code 7 Inverter Overloaded (OVERLOAD) | Cause: The electronic thermal inverter protection reports that the drive has tripped because of overload (too high a current for too long). The counter has reached 100%. Remedy:
|
| Error codes 8 and 15 Motor Overloaded (MOTOR TRIP) | Cause: The motor electronic thermal relay (ETR) protection reports that the motor is too hot. Remedy:
|
| Error code 9 Current Limit (CURRENT LIMIT) | Cause: The motor current has exceeded the value of parameter 209 for a longer time than that permitted in parameter 310. Remedy:
|
| KEY DISABLED Prohibited Parameter Change | Cause: An attempt is made to change a parameter when Factory Setup has been selected in parameter 001. Remedy:
|
| ONLY IN STOP Prohibited Function Change | Cause: An attempt is made to change data that cannot be changed while the drive is running. Remedy:
|
| LOCK OPEN Keypad Lockout | Cause: An attempt is made to change a parameter, but the mechanical keypad lockout is open. Remedy:
|
| LIMIT Range Limit | Cause: A parameter is being changed and one end of the permissible range has been reached. Remedy:
|
| VOLTAGE LOW Low Voltage Warning | Cause: The DC bus voltage is below the warning limit. The inverter is still operating. Remedy:
|
| VOLTAGE HIGH High Voltage Warning | Cause: The DC bus voltage is above the warning limit. The inverter is still operating. Remedy:
|
| REF FAULT Reference Fault | Cause: An analog input signal with a “live zero” (e.g., 4-20 mA, 1-5 V) is below half the minimum level. Remedy:
|
| NO MOTOR No Motor | Cause: The motor check function in parameter 313 detects that no motor has been connected to the drive’s output. Remedy:
|
| LO FREQ WARN Low Frequency Warning | Cause: The output frequency is lower than the value selected in parameter 210. Remedy:
|
| HI FREQ WARN High Frequency Warning | Cause: The output frequency is higher than the value selected in parameter 211. Remedy:
|
| LO CURR WARN Low Current Warning | Cause: The output current is lower than the value selected in parameter 212. Remedy:
|
| HI CURR WARN High Current Warning | Cause: The output current is higher than the value selected in parameter 213. Remedy:
|
| NO 24 VOLT 24 V Fault | Cause: The 24 V DC supply to the control card is not present. Remedy:
|
| EEPROM ERROR EEPROM Fault | Cause: EEPROM fault. Data changes are not saved when AC power is removed. Remedy:
|
| Start-up Test (CONTROL CARD FAULT) Control card problem | Cause: The drive carries out a self-test when AC power is applied. This message indicates a control card problem. Remedy:
|
| Inverter Fault Power section defective | Cause: An operational problem caused the Inverter to fault trip to protect itself or the motor. The power section of the drive is defective. Remedy:
|
| Overvoltage DC bus voltage too high | Cause: The voltage in the DC bus is too high. Possible causes include:
Remedy:
|
| Undervoltage DC bus voltage too low | Cause: The voltage of the DC bus is too low. Possible causes include:
Remedy:
|
| Overcurrent Rectifier peak current exceeded | Cause: Upper limit of the rectifier peak current has been exceeded, possibly because of a short circuit in the output of the drive. Remedy:
|
| Ground Fault Ground fault on drive output | Cause: Indicates a ground fault on the drive's output. Possible causes include:
Remedy:
|
| Critical Temperature Internal temperature too high | Cause: The temperature inside the drive is too high. Possible causes include:
|
| Overload Electronic thermal overload protection tripped | Cause: The motor has consumed more than 110% of the rated current of the drive for too long. Remedy:
|
| Motor Trip Motor electronic thermal relay (ETR) active | Cause: Current consumed by the motor at low speed has been too high for too long (loaded excessively at low speed). Remedy:
|
How to Clear & Reset Danfoss VLT 3500 Drive Faults
- Keypad Reset: Press the [Stop/Reset] key on the front alphanumeric operator panel. Note: if the drive indicates a “Trip Locked” state (such as after an earth fault or severe short-circuit), line power must be removed and reapplied before a reset can occur.
- Digital Input Reset (DI): If configured via digital input parameter settings (e.g., Terminal 16 programmed for Reset), pulse the 24V DC terminal high.
- Automatic Reset: If programmed in Parameter 309 (Reset Function), the drive can automatically attempt up to 10 resets after a trip with an interval delay set in Parameter 312.
- Serial Bus Reset: Transmit a control word reset command via the RS-485 serial communication port using Danfoss FC Protocol or Metasys N2 network.
- Power Cycle & Capacitor Discharge: Switch off AC mains power completely. Wait 4 to 14 minutes (depending on model frame size) until the LCD display fades and internal intermediate capacitors discharge safely before switching power back on.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across DC bus terminals or motor output terminals (U, V, W) before touching wiring or internal components. Wait at least 4 to 14 minutes after disconnecting mains supply.