Danfoss VLT AQUA Drive FC 202 Fault Codes & Diagnostic Guide
Complete alarm, warning, and trip code directory for the Danfoss VLT® AQUA Drive FC 202 dedicated water and wastewater inverter series. Diagnose dry-run detection, flow alarms, overcurrent, and power trips with verified troubleshooting steps.
Complete Danfoss VLT AQUA Drive FC 202 Alarm & Warning Directory
Use the search box in the table below to quickly find your alarm or warning (e.g., type Alarm 13, Alarm 14, Dry Run, or Overvoltage).
| Fault/Alarm Code | Description & Troubleshooting |
|---|---|
| WARNING 1 10 Volts low | Cause: The control card voltage is less than 10 V from terminal 50. The 10 V supply is overloaded. A short circuit in a connected potentiometer or incorrect wiring can cause this condition. Remedy:
|
| WARNING/ALARM 2 Live zero error | Cause: The signal on one of the analog inputs is less than 50% of the minimum value programmed. Broken wiring or a faulty device can cause this. Remedy:
|
| WARNING/ALARM 3 No motor | Cause: No motor has been connected to the output of the drive. Appears only if programmed in parameter 1-80. Remedy:
|
| WARNING/ALARM 4 Mains phase loss | Cause: A phase is missing on the supply side, or the mains voltage imbalance is too high. Can also appear for a fault in the input rectifier. Remedy:
|
| WARNING 5 DC link voltage high | Cause: The DC-link voltage is higher than the high-voltage warning limit. The unit is still active. Remedy: No specific troubleshooting steps provided for this warning. |
| WARNING 6 DC link voltage low | Cause: The DC-link voltage is lower than the low-voltage warning limit. The unit is still active. Remedy: No specific troubleshooting steps provided for this warning. |
| WARNING/ALARM 7 DC overvoltage | Cause: If the DC-link voltage exceeds the limit, the drive trips after a certain time. Remedy:
|
| WARNING/ALARM 8 DC under voltage | Cause: If the DC-link voltage drops below the undervoltage limit, the drive trips after a fixed time delay. Remedy:
|
| WARNING/ALARM 9 Inverter overload | Cause: The drive has run with more than 100% overload for too long and is about to cut out. The drive cannot be reset until the counter is below 90%. Remedy:
|
| WARNING/ALARM 10 Motor overload temperature | Cause: According to the electronic thermal protection (ETR), the motor is too hot. Remedy:
|
| WARNING/ALARM 11 Motor thermistor overtemp | Cause: The thermistor may be disconnected or the motor is overheating. Remedy:
|
| WARNING/ALARM 12 Torque limit | Cause: The torque has exceeded the programmed value in either motor or generator mode. Remedy:
|
| WARNING/ALARM 13 Over current | Cause: Inverter peak current limit (approx. 200% of rated current) is exceeded. Shock loading or quick acceleration can cause this. Remedy:
|
| ALARM 14 Earth (ground) fault | Cause: There is current from the output phase to ground, either in the cable or in the motor itself. Remedy:
|
| ALARM 15 Hardware mismatch | Cause: A fitted option is not operational with the present control card hardware or software. Remedy:
|
| ALARM 16 Short circuit | Cause: There is short-circuiting in the motor or motor wiring. Remedy:
|
| WARNING/ALARM 17 Control word timeout | Cause: There is no communication to the drive. Remedy:
|
| WARNING/ALARM 20 Temp. input error | Cause: The temperature sensor is not connected. Remedy: No specific troubleshooting steps provided. |
| WARNING/ALARM 21 Parameter error | Cause: The parameter is out of range. The parameter number is shown in the display. Remedy:
|
| WARNING/ALARM 22 Hoist mechanical brake | Cause: An issue with the hoist mechanical brake. The value indicates the cause: 0 = Torque reference was not reached before timeout. 1 = Expected brake feedback was not received before timeout. Remedy: No specific troubleshooting steps provided. |
| WARNING 23 Internal fan fault | Cause: Protective function that checks if the internal fan is running/mounted. Remedy:
|
| WARNING 24 External fan fault | Cause: Protective function that checks if the external fan is running/mounted. Can also show a communication error. Remedy: Fan troubleshooting:
Power card troubleshooting:
|
| WARNING 25 Brake resistor short circuit | Cause: A short circuit in the brake resistor is detected. The brake function is disabled. Remedy:
|
| WARNING/ALARM 26 Brake resistor power limit | Cause: The power to the brake resistor is over 90% of its rating. A surge in power can cause overheating. Remedy:
|
| WARNING/ALARM 28 Brake check failed | Cause: The brake resistor is not connected or not working. Remedy:
|
| ALARM 29 Heat sink temp | Cause: The maximum temperature of the heat sink has been exceeded. Remedy: Check for the following conditions:
|
| ALARM 30 Motor phase U missing | Cause: Motor phase U between the drive and the motor is missing. Remedy:
|
| ALARM 31 Motor phase V missing | Cause: Motor phase V between the drive and the motor is missing. Remedy:
|
| ALARM 32 Motor phase W missing | Cause: Motor phase W between the drive and the motor is missing. Remedy:
|
| ALARM 33 Inrush fault | Cause: Too many power-ups have occurred within a short time period. Remedy:
|
| WARNING/ALARM 34 Fieldbus communication fault | Cause: The fieldbus on the communication option card is not working. Remedy: No specific troubleshooting steps provided. |
| WARNING/ALARM 35 Option fault | Cause: An option-specific alarm is received, likely caused by a power-up or communication fault. Remedy: No specific troubleshooting steps provided. |
| WARNING/ALARM 36 Mains failure | Cause: The supply voltage to the drive system is lost. Remedy:
|
| ALARM 37 Phase imbalance | Cause: There is a current imbalance between the power units. Remedy: No specific troubleshooting steps provided. |
| ALARM 38 Internal fault | Cause: An internal fault has occurred. A specific code number is shown on the display. Refer to the manual for code definitions. Remedy:
|
| ALARM 39 Heat sink sensor | Cause: No feedback from the heat sink temperature sensor. Signal from IGBT thermal sensor is not available on the power card. Remedy:
|
| WARNING 40 Overload of digital output terminal 27 | Cause: Check the load connected to terminal 27 or remove the short-circuit connection. Remedy:
|
| WARNING 41 Overload of digital output terminal 29 | Cause: Check the load connected to terminal 29 or remove the short-circuit connection. Remedy:
|
| WARNING 42 Overload of digital output on X30/6 or X30/7 | Cause: Check the load connected to the specified terminal or remove the short-circuit connection. Remedy:
|
| ALARM 43 Ext. supply | Cause: Extended Relay Option MCB 113 is mounted without an external 24 V DC supply. Remedy:
|
| ALARM 45 Earth fault 2 | Cause: Ground fault. Remedy:
|
| ALARM 46 Power card supply | Cause: The supply on the power card is out of range. 4 supplies are generated: 48 V, 24 V, 5 V, ±18 V. Remedy:
|
| WARNING 47 24 V supply low | Cause: The 24 V supply on the power card is out of range. Remedy:
|
| WARNING 48 1.8 V supply low | Cause: The 1.8 V DC supply on the control card is outside of the allowable limits. Remedy:
|
| WARNING 49 Speed limit | Cause: The motor speed is outside of the specified range in parameters 4-11 and 4-13. Remedy: No specific troubleshooting steps provided. |
| ALARM 50 AMA calibration failed | Cause: The Automatic Motor Adaptation (AMA) calibration has failed. Remedy:
|
| ALARM 51 AMA check Unom and Inom | Cause: The settings for motor voltage, current, and power are wrong. Remedy:
|
| ALARM 52 AMA low Inom | Cause: The motor current is too low for the AMA to operate. Remedy:
|
| ALARM 53 AMA motor too big | Cause: The motor is too large for the AMA to operate. Remedy: No specific troubleshooting steps provided. |
| ALARM 54 AMA motor too small | Cause: The motor is too small for the AMA to operate. Remedy: No specific troubleshooting steps provided. |
| ALARM 55 AMA parameter out of range | Cause: The AMA cannot run because motor parameter values are outside the acceptable range. Remedy: No specific troubleshooting steps provided. |
| ALARM 56 AMA interrupted by user | Cause: The AMA was manually interrupted. Remedy: No specific troubleshooting steps provided. |
| ALARM 57 AMA internal fault | Cause: An internal fault occurred during the AMA. Repeated restarts can overheat the motor. Remedy:
|
| ALARM 58 AMA Internal fault | Cause: An internal fault occurred during the AMA. Remedy:
|
| WARNING 59 Current limit | Cause: The current is higher than the value in parameter 4-18 Current Limit. Remedy:
|
| WARNING 60 External interlock | Cause: A digital input signal indicates an external fault condition has commanded the drive to trip. Remedy:
|
| WARNING/ALARM 61 Feedback error | Cause: An error is detected between calculated speed and the speed measurement from the feedback device. Remedy:
|
| WARNING 62 Output frequency at maximum limit | Cause: The output frequency has reached the maximum limit set in parameter 4-19. Remedy:
|
| ALARM 63 Mechanical brake low | Cause: The actual motor current has not exceeded the release brake current within the start delay time window. Remedy: No specific troubleshooting steps provided. |
| WARNING 64 Voltage Limit | Cause: The load and speed combination demands a motor voltage higher than the actual DC-link voltage. Remedy: No specific troubleshooting steps provided. |
| WARNING/ALARM 65 Control card over temperature | Cause: The cutout temperature of the control card (85 °C / 185 °F) has been reached. Remedy:
|
| WARNING 66 Heat sink temperature low | Cause: The drive is too cold to operate, based on the IGBT module's temperature sensor. Remedy:
|
| ALARM 67 Option module configuration has changed | Cause: One or more options have been added or removed since the last power-down. Remedy:
|
| ALARM 68 Safe Stop activated | Cause: Safe Torque Off (STO) has been activated. Remedy:
|
| ALARM 69 Power card temperature | Cause: The temperature sensor on the power card is either too hot or too cold. Remedy:
|
| ALARM 70 Illegal FC configuration | Cause: The control card and power card are incompatible. Remedy:
|
| WARNING/ALARM 71 PTC 1 Safe Stop | Cause: Safe Torque Off (STO) has been activated from the PTC Thermistor Card because the motor is too warm. Remedy:
|
| ALARM 72 Dangerous failure | Cause: STO with trip lock. An unexpected combination of STO commands has occurred. Remedy: No specific troubleshooting steps provided. |
| WARNING 73 Safe Stop auto restart | Cause: Safe Torque Off (STO) activated. With automatic restart enabled, the motor can start when the fault is cleared. Remedy: No specific troubleshooting steps provided. |
| ALARM 74 PTC Thermistor | Cause: Alarm related to VLT® PTC Thermistor Card MCB 112. The PTC is not working. Remedy: No specific troubleshooting steps provided. |
| ALARM 75 Illegal profile sel. | Cause: Do not write the parameter value while the motor is running. Remedy:
|
| WARNING 76 Power unit setup | Cause: The required number of power units does not match the detected number of active power units. Remedy:
|
| WARNING 77 Reduced power mode | Cause: Applies to multi-drive systems. The system is operating in reduced power mode. Remedy: No specific troubleshooting steps provided. |
| ALARM 78 Tracking error | Cause: The difference between setpoint and actual value exceeds the value in parameter 4-35 Tracking Error. Remedy:
|
| ALARM 79 Illegal power section configuration | Cause: The scaling card has an incorrect part number or is not installed. Remedy: No specific troubleshooting steps provided. |
| ALARM 80 Drive initialised to default value | Cause: Parameter settings are initialized to default settings after a manual reset. Remedy:
|
| ALARM 81 CSIV corrupt | Cause: CSIV file has syntax errors. Remedy: No specific troubleshooting steps provided. |
| ALARM 82 CSIV parameter error | Cause: CSIV failed to initialize a parameter. Remedy: No specific troubleshooting steps provided. |
| ALARM 83 Illegal option combination | Cause: The mounted options are incompatible. Remedy: No specific troubleshooting steps provided. |
| ALARM 84 No safety option | Cause: The safety option was removed without applying a general reset. Remedy:
|
| ALARM 88 Option detection | Cause: A change in the option layout is detected while parameter 14-89 is set to Frozen configuration. Remedy:
|
| WARNING 89 Mechanical brake sliding | Cause: The hoist brake monitor detects a motor speed exceeding 10 RPM. Remedy: No specific troubleshooting steps provided. |
| ALARM 90 Feedback monitor | Cause: An issue with the encoder/resolver option. Remedy:
|
| ALARM 91 Analog input 54 wrong settings | Cause: Wrong setting for analog input 54. Remedy:
|
| ALARM 96 Start delayed | Cause: The motor start has been delayed due to short-cycle protection. Remedy:
|
| WARNING 97 Stop delayed | Cause: Stopping the motor has been delayed because it has run for less than the minimum time specified in parameter 22-77. Remedy: No specific troubleshooting steps provided. |
| WARNING 98 Clock fault | Cause: Time is not set, or the RTC clock has failed. Remedy:
|
| ALARM 99 Locked rotor | Cause: The rotor is blocked. Remedy: No specific troubleshooting steps provided. |
| WARNING/ALARM 104 Mixing fan fault | Cause: The fan is not operating. Remedy:
|
| WARNING/ALARM 122 Mot. rotat. unexp. | Cause: The drive performs a function that requires the motor to be at a standstill when it is not. Remedy: No specific troubleshooting steps provided. |
| ALARM 144 Inrush Supply | Cause: A supply voltage on the inrush card is out of range. Remedy: See the bit field result report value for more details:
|
| ALARM 145 External SCR disable | Cause: The alarm indicates a series DC-link capacitor voltage imbalance. Remedy: No specific troubleshooting steps provided. |
| WARNING/ALARM 146 Mains voltage | Cause: Mains voltage is outside a valid operating range. Remedy: The following report values provide more details:
|
| WARNING/ALARM 147 Mains frequency | Cause: Mains frequency is outside a valid operating range. Remedy: Report value provides more details:
|
| WARNING/ALARM 148 System temp | Cause: One or more of the system temperature measurements is too high. Remedy: No specific troubleshooting steps provided. |
| WARNING 163 ATEX ETR cur.lim.warning | Cause: The drive has run above the characteristic curve for more than 50s. Remedy: No specific troubleshooting steps provided. |
| ALARM 164 ATEX ETR cur.lim.alarm | Cause: Operating above the characteristic curve for more than 60s within a 600s period activates the alarm and trips the drive. Remedy: No specific troubleshooting steps provided. |
| WARNING 165 ATEX ETR freq.lim.warning | Cause: The drive is running for more than 50s below the allowed minimum frequency. Remedy: No specific troubleshooting steps provided. |
| ALARM 166 ATEX ETR freq.lim.alarm | Cause: The drive has operated for more than 60s below the allowed minimum frequency. Remedy: No specific troubleshooting steps provided. |
| WARNING 200 Fire mode | Cause: The drive is operating in fire mode. Remedy:
|
| WARNING 201 Fire mode was active | Cause: The drive has entered fire mode. Remedy:
|
| WARNING 202 Fire mode limits exceeded | Cause: While in fire mode, one or more alarm conditions that would normally trip the unit have been ignored. This voids unit warranty. Remedy:
|
| WARNING 203 Missing motor | Cause: With a drive operating multi-motors, an underload condition was detected. This can indicate a missing motor. Remedy:
|
| WARNING 204 Locked rotor | Cause: With a drive operating multi-motors, an overload condition was detected. This can indicate a locked rotor. Remedy:
|
| WARNING 219 Compressor interlock | Cause: At least 1 compressor is inversely interlocked via a digital input. Remedy:
|
| ALARM 243 Brake IGBT | Cause: Only for multi-drive systems. Equivalent to alarm 27, Brake chopper fault. Can be caused by a blown DC fuse, incorrect brake jumper position, or Klixon switch opening. Remedy: No specific troubleshooting steps provided. |
| ALARM 245 Heat sink sensor | Cause: Only for multi-drive systems. No feedback from the heat sink temperature sensor. Equivalent to alarm 39. Remedy: Check the following:
|
| ALARM 246 Power card supply | Cause: Only for multi-drive systems. It is equivalent to alarm 46, Power card supply. Remedy: No specific troubleshooting steps provided. |
| ALARM 247 Power card temperature | Cause: Only for multi-drive systems. It is equivalent to alarm 69, Power card temperature. Remedy: No specific troubleshooting steps provided. |
| ALARM 248 Illegal power section configuration | Cause: Only for multi-drive systems. It is equivalent to alarm 79, Illegal power section configuration. Remedy:
|
| WARNING 250 New spare part | Cause: The power or switch mode supply has been exchanged. Remedy:
|
| WARNING 251 New type code | Cause: The power card or other components have been replaced and the type code has been changed. Remedy:
|
How to Clear & Reset Danfoss VLT AQUA Drive FC 202 Faults
- LCP Keypad Reset: Press the yellow [Reset] key directly on the control panel. If operating in automatic pumping control (Auto On) and locked out on trip, press [Off/Reset] before switching back to [Auto On].
- Digital Input Reset (DI): If programmed in parameter 5-12 (Terminal 27 Digital Input) or any input terminal (18, 19, 27, 29, 32, 33) set to [1] Reset, pulse the terminal with 24V DC from terminal 12 or 13.
- Danfoss MCT 10 Software: Connect via the USB Type-B port or RS-485 serial terminals (68/69), open the Danfoss MCT 10 Set-up Software, and trigger an active alarm reset command from the diagnostic window.
- Fieldbus Control Word: Set Bit 7 (Trip Reset) from
0to1in the Danfoss FC Profile or PROFIdrive Control Word over BACnet, Modbus RTU, PROFINET, or EtherNet/IP. - Power Cycle (Cold Reset): Disconnect incoming AC mains line power. Wait 4 to 20 minutes (up to 40 minutes on high-power frames) until the LCP display completely powers down and capacitors discharge before restoring power.