Danfoss VLT Refrigeration Drive FC 103

Home / Danfoss / Danfoss VLT Refrigeration Drive FC 103

Danfoss VLT Refrigeration Drive FC 103 Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Danfoss VLT Refrigeration Drive FC 103 series. Search or filter through the complete diagnostic database below.

Dedicated Refrigeration Drive Power: 1.1 to 800 kW (1.5 to 1000 HP) Compressor & Condenser Fan Control
Power Range 1.1 – 800 kW (1.5 – 1000 HP)
Supply Voltage 200–240V / 380–480V / 525–690V
Control Modes VVC+ & Flux Vector Control
Operator Interface Graphical LCP 102 / MCT 10 Setup

Complete Danfoss VLT Refrigeration Drive FC 103 Fault Code Directory

Use the search box in the table below to quickly find your alarm code (e.g., type Alarm 13, Alarm 14, Alarm 16, or Overcurrent).

Fault/Alarm CodeDescription & Troubleshooting
WARNING 1
10 Volts low

Cause: The 10 V voltage from terminal 50 on the control card is below 10 V. The supply is overloaded.

Remedy: Remove some of the load from terminal 50. The maximum load is 15 mA or a minimum of 590 Ω.

WARNING/ALARM 2
Live zero error

Cause: The signal on terminal 53 or 54 is less than 50% of the value set in parameter 6-10, 6-12, 6-20, or 6-22.

Remedy: Check the connections and settings for terminals 53 and 54.

WARNING/ALARM 3
No motor

Cause: No motor has been connected to the output of the frequency converter.

Remedy: Connect a motor to the output terminals.

WARNING/ALARM 4
Mains phase loss

Cause: A phase is missing on the supply side, or the mains voltage imbalance is too high. This can also indicate a fault in the input rectifier.

Remedy: Check the supply voltage and supply currents to the frequency converter.

WARNING 5
DC link voltage high

Cause: The intermediate circuit voltage (DC) is higher than the overvoltage limit of the control system.

Remedy: The frequency converter is still active, but the condition should be monitored.

WARNING 6
DC link voltage low

Cause: The intermediate circuit voltage (DC) is below the undervoltage limit of the control system.

Remedy: The frequency converter is still active, but the condition should be monitored.

WARNING/ALARM 7
DC over voltage

Cause: The intermediate circuit voltage exceeds the limit, causing the frequency converter to trip after a time.

Remedy:

  • Select [2] Enable in parameter 2-17 Over-voltage Control.

  • Extend the ramp time.

  • Activate functions in parameter 2-10 Brake Function.

  • Increase parameter 14-26 Trip Delay at Inverter Fault.



WARNING/ALARM 8
DC under voltage

Cause: The intermediate circuit voltage (DC) drops below the 'voltage warning low' limit. The frequency converter checks if 24 V back-up supply is connected and trips if it is not.

Remedy: Check whether the supply voltage matches the frequency converter specifications. See the VLT® Refrigeration Drive FC 103 Design Guide.

WARNING/ALARM 9
Inverter overloaded

Cause: The frequency converter is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection gives a warning at 98% and trips at 100%.

Remedy: The frequency converter cannot be reset until the counter is below 90%. Reduce the load on the motor.

WARNING/ALARM 10
Motor ETR over temperature

Cause: According to the electronic thermal protection (ETR), the motor is too hot. The motor is overloaded by more than nominal current for too long.

Remedy: Reduce the load on the motor. Check that parameter 1-24 Motor Current is set correctly.

WARNING/ALARM 11
Motor thermistor over temp

Cause: The thermistor or the thermistor connection is disconnected or has detected an over-temperature condition.

Remedy: Check that the thermistor is connected correctly between terminal 53 or 54 and terminal 50, or between terminal 18/19 and terminal 50. If a KTY sensor is used, check for correct connection between terminal 54 and 55.

WARNING/ALARM 12
Torque limit

Cause: The torque is higher than the value in parameter 4-16 (motor mode) or parameter 4-17 (generator mode).

Remedy: Check the load and torque limit parameters.

WARNING/ALARM 13
Over Current

Cause: The inverter peak current limit (approx. 200% of rated current) is exceeded. The warning lasts for 8-12 seconds before the drive trips.

Remedy: Turn off the frequency converter and check if the motor shaft can be turned and if the motor size matches the frequency converter.

ALARM 14
Earth fault

Cause: There is a discharge from the output phases to ground, either in the cable or in the motor itself.

Remedy: Turn off the frequency converter and remove the ground fault.

ALARM 15
Incomplete hardware

Cause: A fitted option is not handled by the present control board (hardware or software).

Remedy: Contact Danfoss support; a hardware or software mismatch is present.

ALARM 16
Short-circuit

Cause: There is short-circuiting in the motor or on the motor terminals.

Remedy: Turn off the frequency converter and remove the short-circuit.

WARNING/ALARM 17
Control word timeout

Cause: There is no communication to the frequency converter. The warning is only active if parameter 8-04 is not set to [0] Off.

Remedy: Check the control wiring and communication source. Parameter 8-03 Control Timeout Time could possibly be increased.

ALARM 18
Start Failed

Cause: The speed has not been able to exceed the speed set in parameter 1-77 within the time allowed in parameter 1-79. This may be caused by a blocked rotor.

Remedy: Check the motor for a mechanical blockage. Ensure parameters 1-77 and 1-79 are set appropriately for the application.

WARNING 19
Discharge Temperature High

Cause: The discharge temperature exceeds the level programmed in parameter 28-24 Warning Level.

Remedy: The frequency converter lowers the speed of the compressor in an attempt to lower the discharge temperature. Check cooling and refrigerant levels.

ALARM 19
Discharge Temperature High

Cause: The discharge temperature exceeds the level programmed in parameter 28-26 Emergency Level.

Remedy: The drive will trip. Check the compressor cooling, refrigerant charge, and operating conditions immediately.

WARNING 23
Internal fans

Cause: External fans have failed due to defect hardware or fans not mounted.

Remedy: Check and replace the external fans. Ensure they are correctly mounted.

WARNING 24
External fan fault

Cause: The fan warning function is an extra protection function that checks if the fan is running/mounted.

Remedy: Check the external fan and its connection. The fan warning can be disabled in parameter 14-53 Fan Monitor, [0] Disabled.

WARNING/ALARM 29
Drive over temperature

Cause: The cutout temperature of the heat sink (95 °C) has been exceeded. The fault could be due to ambient temperature being too high or a too long motor cable.

Remedy: The temperature fault cannot be reset until the temperature of the heat sink is below 70 °C. Improve ventilation or shorten motor cable length.

ALARM 30
Motor phase U missing

Cause: Motor phase U between the frequency converter and the motor is missing.

Remedy: Turn off the frequency converter and check motor phase U wiring.

ALARM 31
Motor phase V missing

Cause: Motor phase V between the frequency converter and the motor is missing.

Remedy: Turn off the frequency converter and check motor phase V wiring.

ALARM 32
Motor phase W missing

Cause: Motor phase W between the frequency converter and the motor is missing.

Remedy: Turn off the frequency converter and check motor phase W wiring.

ALARM 33
Inrush fault

Cause: Too many power-ups have occurred within a short time period.

Remedy: Respect the allowed number of power-ups per minute as specified in the VLT® Refrigeration Drive FC 103 Design Guide.

WARNING/ALARM 34
Fieldbus communication fault

Cause: The fieldbus on the communication option card is not working.

Remedy: Check the fieldbus connection, wiring, and configuration.

WARNING/ALARM 36
Mains failure

Cause: This warning/alarm is only active if the supply voltage to the frequency converter is lost and parameter 14-10 is not set to [0] No function.

Remedy: Check the fuses to the frequency converter and the incoming power supply.

ALARM 38
Internal fault

Cause: An internal fault has been detected in the frequency converter.

Remedy: Contact the local Danfoss supplier.

WARNING 40
Overload of Digital Output Terminal 27

Cause: Overload of Digital Output Terminal 27.

Remedy: Check the load connected to terminal 27 or remove short-circuit. Check parameter 5-00 and 5-01.

WARNING 41
Overload of Digital Output Terminal 29

Cause: Overload of Digital Output Terminal 29.

Remedy: Check the load connected to terminal 29 or remove short-circuit. Check parameter 5-00 and 5-02.

WARNING 42
Overload of Digital Output On X30/6 or X30/7

Cause: Overload of Digital Output On X30/6 or X30/7.

Remedy: Check the load connected to X30/6 or X30/7 or remove short-circuit. Check parameter 5-32 or 5-33.

WARNING 47
24 V supply low

Cause: The external 24 V DC back-up power supply may be overloaded.

Remedy: Check the external 24V DC supply and the connected load. Otherwise contact the Danfoss supplier.

ALARM 48
1.8 V supply low

Cause: Internal 1.8 V power supply is out of tolerance.

Remedy: Contact the Danfoss supplier.

WARNING 49
Speed limit

Cause: The motor speed is not within the specified range in parameters 4-11 and 4-13. The converter trips if the speed is below the limit in parameter 1-86.

Remedy: Check the application and motor speed. Adjust the speed limits in parameters 4-11, 4-13, and 1-86 if necessary.

ALARM 50
AMA calibration failed

Cause: The Automatic Motor Adaptation (AMA) process failed.

Remedy: Contact the Danfoss supplier.

ALARM 51
AMA check Unom and Inom

Cause: The setting of motor voltage, motor current, and motor power is presumably wrong during AMA.

Remedy: Check the motor data settings in the relevant parameters.

ALARM 52
AMA low Inom

Cause: The motor current is too low to perform the AMA.

Remedy: Check the motor data settings. Ensure the motor is correctly connected.

ALARM 53
AMA motor too big

Cause: The motor is too big for the AMA to be carried out.

Remedy: Ensure the motor size is compatible with the drive's AMA capability.

ALARM 54
AMA motor too small

Cause: The motor is too small for the AMA to be carried out.

Remedy: Ensure the motor size is compatible with the drive's AMA capability.

ALARM 55
AMA par. out of range

Cause: The parameter values found from the motor during AMA are outside acceptable range.

Remedy: Check motor data and connections. Run AMA again.

ALARM 56
AMA interrupted by user

Cause: The AMA has been interrupted by the user.

Remedy: If AMA needs to be completed, start the process again and let it finish.

ALARM 57
AMA timeout

Cause: The AMA process is taking too long to complete. Repeated runs may heat the motor.

Remedy: Try to start the AMA again. If it continues to time out, check motor connections and data.

WARNING/ALARM 58
AMA internal fault

Cause: An internal fault occurred during the AMA process.

Remedy: Contact the Danfoss supplier.

WARNING 59
Current limit

Cause: The motor current is higher than the value in parameter 4-18 Current Limit.

Remedy: Check the load and increase the current limit in parameter 4-18 if necessary.

WARNING 60
External Interlock

Cause: External interlock has been activated (a 24 V DC signal is missing from the programmed terminal).

Remedy: To resume normal operation, apply 24 V DC to the terminal programmed for external interlock and reset the frequency converter.

WARNING 62
Output Frequency at Maximum Limit

Cause: The output frequency is limited by the value set in Parameter 4-19 Max Output Frequency.

Remedy: Adjust parameter 4-19 if a higher output frequency is required.

WARNING 64
Voltage Limit

Cause: The load and speed combination demands a motor voltage higher than the actual DC-link voltage.

Remedy: Reduce the speed or load. Check if the input voltage is correct.

WARNING/ALARM/TRIP 65
Control Card Over Temperature

Cause: Control card overtemperature. The cutout temperature of the control card is 80 °C (176 °F).

Remedy: Improve ambient cooling or reduce the load on the drive.

WARNING 66
Heatsink Temperature Low

Cause: The heat sink temperature is measured as 0 °C (32 °F), which could indicate a defective sensor. This causes the fan to run at maximum speed.

Remedy: Check the temperature sensor. Contact Danfoss support if the issue persists.

ALARM 67
Option Configuration has Changed

Cause: One or more options has either been added or removed since the last power-down.

Remedy: Acknowledge the change. The drive will continue to operate with the new configuration.

ALARM 68
Safe Stop

Cause: Safe Torque Off has been activated.

Remedy: To resume normal operation, apply 24 V DC to terminal 37 then send a reset signal (via bus, digital I/O, or by pressing [Reset]).

ALARM 70
Illegal Frequency Converter Configuration

Cause: Actual combination of control board and power board is illegal.

Remedy: Ensure the control board and power board are a compatible pair. Contact Danfoss support.

ALARM 80
Drive Initialized to Default Value

Cause: Parameter settings are initialized to default setting after a manual (3-finger) reset or via parameter 14-22 Operation Mode.

Remedy: This is an informational alarm. Re-program the drive as needed.

WARNING/ALARM 92
NoFlow

Cause: A no-flow situation has been detected for the system.

Remedy: Check the pump and piping for blockages. See parameter group 22-2* No-Flow Detection.

WARNING/ALARM 93
Dry Pump

Cause: A no-flow situation and high speed indicates that the pump has run dry.

Remedy: Stop the pump immediately. Check the fluid source. See parameter group 22-2* No-Flow Detection.

WARNING/ALARM 94
End of Curve

Cause: Feedback stays lower than the setpoint, which may indicate a leakage in the pipe system.

Remedy: Inspect the pipe system for leaks. See parameter group 22-5* End of Curve.

WARNING/ALARM 95
Broken Belt

Cause: Torque is below the torque level set for no load indicating a broken belt.

Remedy: Check the belt and mechanical transmission. See parameter group 22-6* Broken Belt Detection.

WARNING 96
Start Delayed

Cause: Start of the motor has been delayed due to short cycle protection being active.

Remedy: This is a protective feature. See parameter group 22-7* Short Cycle Protection to adjust timings if necessary.

WARNING 97
Stop Delayed

Cause: Stop of the motor has been delayed due to short cycle protection being active.

Remedy: This is a protective feature. See parameter group 22-7* Short Cycle Protection to adjust timings if necessary.

WARNING 98
Clock Fault

Cause: Date and time has not been set or any back-up mounted has failed.

Remedy: Set the date and time. See parameter group 0-7* Clock Settings.

ALARM 250
New Spare Part

Cause: The power or switch mode power supply has been exchanged. The frequency converter type code must be restored in the EEPROM.

Remedy: Select the correct type code in parameter 14-23 Typecode Setting according to the label on the unit. Remember to select Save to EEPROM to complete.

ALARM 251
New Type Code

Cause: The frequency converter has a new type code.

Remedy: This is informational after a type code change. Acknowledge to continue.

How to Clear & Reset Danfoss VLT Refrigeration Drive FC 103 Faults

  1. Keypad Reset: Press the red [Reset] key on the Graphical Local Control Panel (LCP 102). If the drive is in a Trip Lock condition, the underlying cause must be cleared before the reset key will acknowledge.
  2. Digital Input Reset: Signal a digital input configured for Reset (parameter group 5-1* Digital Inputs, such as Terminal 27 configured in parameter 5-12 [1]).
  3. Automatic Reset: Configure parameter 14-20 (Reset Mode) to execute automatic resets (values [1]–[13] for 1 to 20 automatic restarts or infinite auto-reset) using the interval defined in parameter 14-21 (Automatic Restart Time).
  4. Fieldbus / BMS Interface: Set Bit 7 (Fault Reset) from `0` to `1` in the Control Word (CTW) through integrated RS-485 Modbus RTU, BACnet MSTP, or optional cards (PROFINET, PROFIBUS, LonWorks).
  5. Power Cycle: Disconnect the incoming AC mains power. Wait the mandatory discharge duration (4 to 20 minutes depending on enclosure frame size) until the LCP display completely shuts down, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Intermediate DC-bus capacitors remain charged at dangerous potentials even after disconnecting mains power. Always wait at least 4 minutes for frame sizes A2–A3, 15 minutes for frames B1–B4 and C1–C2, and 20 to 40 minutes for large frames D, E, and F. Always verify with a calibrated voltmeter that the voltage across DC-link terminals (+DC / -DC) is strictly below 50 V DC before opening enclosures or touching motor output terminals U, V, and W.