Inovance MD200 drive

Home / Inovance / Inovance MD200 drive

Inovance MD200 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Inovance MD200 compact economic AC drive series. Search or filter through the complete fault code directory below.

Economic Compact AC Drive Power: 0.4 to 3.7 kW (0.5 to 5.0 HP) Built-in Modbus RTU / RS485
Power Range 0.4 – 3.7 kW (0.5 – 5.0 HP)
Supply Voltage 1PH 200–240V / 3PH 380–480V
Control Modes V/F Control & Sensorless Vector (SVC)
Operator Interface Integrated LED Keypad / InoDriveShop

Complete Inovance MD200 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type Err02, Err04, or Overcurrent).

Fault CodesCause & Solution
Err02
Overcurrent
during
acceleration
Cause & Solution:

1. Ground fault or short circuit exists in the output circuit.
- Check whether short-circuit occurs on the motor, the motor cable or contactor.
2. Acceleration time is too short.
- Increase acceleration time.
3. Customized torque boost or V/F curve is not appropriate.
- Adjust the customized torque boost or V/F curve.
4. The voltage is too low.
- Adjust the voltage to normal range.
5. The spinning motor is started.
- Enable the catching a spinning motor function or start the motor after it stops.
6. A load is applied suddenly during acceleration.
- Cancel the suddenly added load.
7. The rated AC drive power is low.
- Replace the drive by one with higher rated power.
8. The braking resistor resistance is small.
- The braking resistor is short circuited.
- Replace a new braking resistor.
Err03
Overcurrent
during
deceleration
Cause & Solution:

1. Ground fault or short circuit exists in the output circuit.
- Check whether short-circuit occurs on motor, motor cable or contactor.

2. Acceleration time is too short.
- Increase acceleration time.

3. The voltage is too low.
- Adjust the voltage to normal range.

4. A load is added suddenly during deceleration.
- Cancel the suddenly added load.

5. Braking unit and braking resistor are not installed.
- Install the braking unit and braking resistor.

6. The braking resistor resistance is small or the braking resistor is short circuited.
- Replace a new braking resistor.
Err04
Overcurrent
at constant
speed
Cause & Solution:

1. Ground fault or short circuit exists in the output circuit.
- Check whether short-circuit occurs on the motor, motor cable or contactor

2. The voltage is too low.
- Adjust the voltage to normal range.

3. A load is added suddenly during running.
- Cancel the suddenly added load.

4. The rated AC drive power is low.
- Replace the drive by one with higher rated power.

5. The braking resistor resistance is small or the braking resistor is short circuited.
- Replace a new braking resistor.
Err05
Overvoltage
during
acceleration
Cause & Solution:

1. Input voltage is too high.
- Adjust input voltage to normal range.

2. An external force drives motor during acceleration.
- Cancel the external force.

3. Braking unit and braking resistor are not installed.
- Install the braking unit and braking resistor.

4. Acceleration time is too short.
- Increase acceleration time.
Err06
Overvoltage
during
deceleration
Cause & Solution:

1. Input voltage is too high.
- Adjust input voltage to normal range.

2. An external force drives motor during deceleration.
- Cancel the external force or install the braking resistor.

3. Deceleration time is too short.
- Increase deceleration time.

4. Braking unit and braking resistor are not installed.
- Install the braking unit and braking resistor.
Err07
Overvoltage
at constant
speed
Cause & Solution:

1. Input voltage is too high.
- Adjust input voltage to normal range.

2. An external force drives motor during running.
- Cancel the external force or install a braking resistor.
Err08
Control
power fault
Cause: Input voltage is not within the permissible range.

Solution: Adjust the input voltage in the permissible range.
Err09
Undervoltage
Cause & Solution:

1. An instantaneous power failure occurs.
- Reset the fault

2. The AC drive's input voltage is not within the permissible range.
- Adjust the voltage to normal range.

3. The bus voltage is abnormal.
- Replace the AC drive.

4. The rectifier bridge, the pre-charge resistor, the drive board or the control board are abnormal.
- Replace the AC drive.
Err10
Drive
overload
Cause & Solution:

1. The load is too heavy or locked-rotor occurs on the motor.
- Reduce the load or check motor and mechanical conditions.

2. The rated AC drive power is low.
- Replace the drive by one with higher rated power.
Err11
Motor
overload
Cause & Solution:

1. F9-01 (Motor overload protection gain) is set improperly.
- Set F9-01 correctly.

2. The load is too heavy or locked-rotor occurs on the motor.
- Reduce the load or check motor and mechanical conditions.

3. The rated AC drive power is low.
- Replace the drive by one with higher rated power.
Err12
Input phase
loss
Cause & Solution:

1. Three phase input is abnormal.
- Eliminate faults in external circuitry

2. Drive board is abnormal.
- Eliminate faults in external circuitry

3. Lightning protection board is abnormal.
- There is an hardware or software issue in drive. Need to repair or replace drive.


4. Control board is abnormal.
- There is an hardware or software issue in drive. Need to repair or replace drive.
Err13
Output phase
loss
Cause & Solution:

1. Motor winding is damaged. Check resistance between motor cables.
- Replace motor is winding is damaged.

2. The cable connecting the AC drive and the motor is abnormal.
- Check for wiring errors and ensure the output cable is connected properly

3. The AC drive's three-phase outputs are unbalanced when the motor is running.
- Check whether the motor three-phase winding is normal.

4. The drive board or the IGBT is abnormal.
- Replace the AC drive.
Err14
IGBT
overheat
Cause & Solution:

1. The ambient temperature is too high.
- Lower the ambient temperature.

2. The ventilation is clogged.
- Clean the ventilation.

3. The fan is damaged.
- Replace the cooling fan.

4. The thermally sensitive resistor of IGBT is damaged.
- Replace the AC drive.

5. The AC drive IGBT is damaged.
- Replace the AC drive.
Err15
External
equipment
fault
Cause & Solution:

1. External fault signal is input via DI.
- Confirm that the mechanical condition allows restart (F8-18) and reset the operation.

2. External fault signal is input via virtual I/O.
- Confirm that the virtual I/O parameters in group A1 are set correctly and reset the operation.
Err16
Communication
fault
Cause & Solution:

1. The host controller is in abnormal state.
- Check the cable of the host controller.

2. Communication cable is abnormal.
- Check the communication cables.

3. Communication parameters in group Fd are set improperly.
- Set communication parameters in group Fd properly.

4. After all the preceding checkings are done but the fault still exists, restore the default settings.
Err18
Current
detection
fault
Cause: The drive board is abnormal.

Solution: Replace the AC drive.
Err21
EEPROM read-
write fault
Cause: EEPROM chip is damaged.

Solution: Replace the AC drive.
Err23
Short
circuit to
ground
Cause & Solution:

1. The motor is short circuited to the ground.
- Replace cable or motor.

2. The upper IGBT is damaged.
- There is an hardware or software issue in drive. Need to repair or replace drive.
Err26
Accumulative
running time
reached
Cause: Accumulative running time reaches the setting value.

Solution: Clear the record through parameter initialization.
Err27
User-defined
fault 1
Cause: User-defined fault 1 is input via DI.

Solution: Reset the operation.
Err28
User-defined
fault 2
Cause: User-defined fault 2 is input via DI.

Solution: Reset the operation.
Err29
Accumulative
power-on
time reached
Cause: Accumulative power-on time reaches the setting value.

Solution: Clear the record through parameter initialization.
Err30
Off load
fault
Cause: The output current of AC drive is smaller than F9-64 (load loss detection level).

Solution: Check whether the load is disconnected or the setting of F9-64 and F9-65 (load lost detection time) satisfies actual running conditions.
Err31
PID
feedback
lost
during
running
Cause: PID feedback is smaller than the setting value of FA-26 (detection level of PID feedback loss).

Solution: Check PID feedback or set FA-26 properly.
Err40
Quick
current
limit
Cause & Solution:

1. The load is too heavy or locked-rotor occurs on the motor.
- Reduce the load or check motor and mechanical conditions.

2. The rated AC drive power is low.
- Replace the drive by one with higher rated power.
Err55
Slave faulty
in speed
synchronous
Cause: When speed synchronous is enabled, the master receives CAN communication data but does not detect the salve. Then Err55 is reported.

Solution:

1. Check the slave CAN communication cable connection.
2. Check whether CAN communication of the slave is normal.
HC FaultCause & Solution:

1. The cable between the drive board and control board is in poor contact.
- Re-connect the 4-pin cable and 28-pin cable.

2. The control board is damaged.
- Replace the AC drive.

3. The motor or motor cable is short circuited to ground.
- Check whether short-circuit occurs on motor, motor cable or contactor.

4. The mains voltage is too low.
- Check the power supply.

How to Clear & Reset Inovance MD200 Drive Faults

  1. Keypad Reset: Press the red STOP/RES button on the drive’s integrated LED operating panel while in a tripped fault state (indicated by an active Err display).
  2. Digital Input Reset (DI): If any digital input (DI1 to DI5) has been assigned to function 9 (Fault reset) via parameters F4-00 to F4-04, activate that physical switch or relay to clear the trip.
  3. InoDriveShop PC Software: Connect a PC to the drive via an RS485 communication adapter, open InoDriveShop, navigate to online status monitoring, and send a fault reset command.
  4. Serial Modbus Reset: Write the reset command word to address 2000H over the built-in RS485 / Modbus RTU network to reset the fault remotely from a PLC or HMI.
  5. Power Cycle: Disconnect the incoming AC power supply, wait at least 5 to 10 minutes until the DC bus indicator light turns completely off and capacitors discharge, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus voltage across terminals (+) and (-) has discharged completely below 36VDC before removing terminal covers, handling control boards, or servicing output terminals U, V, and W on the Inovance MD200 drive.