Inovance Drives Fault Codes & Troubleshooting

Complete diagnostic database for 20 Inovance drive series. Browse fault codes, alarms, causes, and step-by-step fixes for AC & servo drives. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.

12 AC Inverter Series 8 Servo Motion Drives 20 Total Series

Inovance AC Variable Frequency Drives

12 Models

Inovance AC Servo Drives & Motion Systems

8 Models

Most Common Inovance Drive Fault Codes

Diagnostic Quick Reference
Inovance Fault Code Servo Code Fault Name Common Root Cause
Err02 / Err03 Er.102 Overcurrent (Accel / Decel) Acceleration or deceleration ramp too fast, mechanical jam, or short circuit across motor phases U, V, and W.
Err05 / Err06 Er.120 Overvoltage (Accel / Decel) Excess regenerative energy during deceleration; check braking resistor connection or lengthen deceleration ramp.
Err09 Er.130 Undervoltage DC link voltage dropped below trip limit; supply grid sag, blown line fuse, or faulty main circuit contactor.
Err10 / Err11 Er.400 Drive / Motor Overload Continuous operation exceeding rated current; mechanical binding or improper motor parameter configuration in Group F1.
Err14 Er.420 Module Overheat (IGBT) Air duct clogged, cooling fan malfunction, high ambient temperature (>50°C), or loose heatsink mounting screws.
Err23 Er.104 Output Ground Fault Leakage current detected from motor phases to earth; inspect cable insulation breakdown or damp motor terminal box.
Err12 Er.131 Input Phase Loss Missing phase on incoming power lines R, S, T; loose supply terminals or blown upstream circuit breaker.

How to Clear & Reset Inovance Faults

  1. Keypad Reset: Press the red STOP/RESET key on the physical operating keypad once the fault cause has been removed.
  2. Digital Input (DI) Terminal: Send an external pulse to the digital input configured for fault reset (set multi-function terminal parameter F4-00 to F4-04 to function 9: Fault reset (RESET)).
  3. Software / Fieldbus Reset: Reset via Inovance commissioning software (InoDriverShop or InoShop) by clicking “Fault Reset”, or write the reset bit via Modbus/EtherCAT communication control word.
  4. Mains Power Cycle: Turn off main input AC power, wait 5 minutes until the charge indicator LED turns completely off, and restore power.
⚠️ High-Voltage Safety Warning: Intermediate DC bus capacitors remain charged at lethal voltage levels after input AC power is disconnected. Always verify with a calibrated digital multimeter that the DC voltage across terminals (+) and (-) is below 36VDC before servicing or touching wiring.