Inovance MD500 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Inovance MD500 high-performance current vector drive series. Search or filter through the complete fault code directory below.

General-Purpose Vector Drive Power: 0.4 to 450 kW (0.5 to 600 HP) Dual Overload: G-Type / P-Type
Power Range 0.4 – 450 kW (0.5 – 600 HP)
Supply Voltage 380–480V / 200–240V AC
Control Modes SVC, FVC (Closed-Loop) & V/F
Operator Interface LED Keypad / Optional LCD Panel

Complete Inovance MD500 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type Err02, Err09, or Overcurrent).

Fault CodesCause & Solution
Err02
Overcurrent
during
acceleration
Cause & Solution:

1. Ground fault or short circuit exists in the output circuit.
- Check whether short-circuit occurs on the motor, the motor cable or contactor.
2. Acceleration time is too short.
- Increase acceleration time.
3. Customized torque boost or V/F curve is not appropriate.
- Adjust the customized torque boost or V/F curve.
4. The voltage is too low.
- Adjust the voltage to normal range.
5. The spinning motor is started.
- Enable the catching a spinning motor function or start the motor after it stops.
6. A load is applied suddenly during acceleration.
- Cancel the suddenly added load.
7. The rated AC drive power is low.
- Replace the drive by one with higher rated power.
8. The braking resistor resistance is small.
- The braking resistor is short circuited.
- Replace a new braking resistor.
Err03
Overcurrent
during
deceleration
Cause & Solution:

1. Ground fault or short circuit exists in the output circuit.
- Check whether short-circuit occurs on motor, motor cable or contactor.

2. Acceleration time is too short.
- Increase acceleration time.

3. The voltage is too low.
- Adjust the voltage to normal range.

4. A load is added suddenly during deceleration.
- Cancel the suddenly added load.

5. Braking unit and braking resistor are not installed.
- Install the braking unit and braking resistor.

6. The braking resistor resistance is small or the braking resistor is short circuited.
- Replace a new braking resistor.
Err04
Overcurrent
at constant
speed
Cause & Solution:

1. Ground fault or short circuit exists in the output circuit.
- Check whether short-circuit occurs on the motor, motor cable or contactor

2. The voltage is too low.
- Adjust the voltage to normal range.

3. A load is added suddenly during running.
- Cancel the suddenly added load.

4. The rated AC drive power is low.
- Replace the drive by one with higher rated power.

5. The braking resistor resistance is small or the braking resistor is short circuited.
- Replace a new braking resistor.
Err05
Overvoltage
during
acceleration
Cause & Solution:

1. Input voltage is too high.
- Adjust input voltage to normal range.

2. An external force drives motor during acceleration.
- Cancel the external force.

3. Braking unit and braking resistor are not installed.
- Install the braking unit and braking resistor.

4. Acceleration time is too short.
- Increase acceleration time.
Err06
Overvoltage
during
deceleration
Cause & Solution:

1. Input voltage is too high.
- Adjust input voltage to normal range.

2. An external force drives motor during deceleration.
- Cancel the external force or install the braking resistor.

3. Deceleration time is too short.
- Increase deceleration time.

4. Braking unit and braking resistor are not installed.
- Install the braking unit and braking resistor.
Err07
Overvoltage
at constant
speed
Cause & Solution:

1. Input voltage is too high.
- Adjust input voltage to normal range.

2. An external force drives motor during running.
- Cancel the external force or install a braking resistor.
Err08
Pre-charge
resistor
fault
Cause: Bus voltage fluctuates around undervoltage threshold continuously

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
Err09
Undervoltage
Cause & Solution:

1. An instantaneous power failure occurs.
- Reset the fault

2. The AC drive's input voltage is not within the permissible range.
- Adjust the voltage to normal range.

3. The bus voltage is abnormal.
- Replace the AC drive.

4. The rectifier bridge, the pre-charge resistor, the drive board or the control board are abnormal.
- Replace the AC drive.
Err10
Drive
overload
Cause & Solution:

1. The load is too heavy or locked-rotor occurs on the motor.
- Reduce the load or check motor and mechanical conditions.

2. The rated AC drive power is low.
- Replace the drive by one with higher rated power.
Err11
Motor
overload
Cause & Solution:

1. F9-01 (Motor overload protection gain) is set improperly.
- Set F9-01 correctly.

2. The load is too heavy or locked-rotor occurs on the motor.
- Reduce the load or check motor and mechanical conditions.

3. The rated AC drive power is low.
- Replace the drive by one with higher rated power.
Err12
Input phase
loss
Cause & Solution:

1. Three phase input is abnormal.
- Eliminate faults in external circuitry

2. Drive board is abnormal.
- Eliminate faults in external circuitry

3. Lightning protection board is abnormal.
- There is an hardware or software issue in drive. Need to repair or replace drive.


4. Control board is abnormal.
- There is an hardware or software issue in drive. Need to repair or replace drive.
Err13
Output phase
loss
Cause & Solution:

1. Motor winding is damaged. Check resistance between motor cables.
- Replace motor is winding is damaged.

2. The cable connecting the AC drive and the motor is abnormal.
- Check for wiring errors and ensure the output cable is connected properly

3. The AC drive's three-phase outputs are unbalanced when the motor is running.
- Check whether the motor three-phase winding is normal.

4. The drive board or the IGBT is abnormal.
- Replace the AC drive.
Err14
IGBT
overheat
Cause & Solution:

1. The ambient temperature is too high.
- Lower the ambient temperature.

2. The ventilation is clogged.
- Clean the ventilation.

3. The fan is damaged.
- Replace the cooling fan.

4. The thermally sensitive resistor of IGBT is damaged.
- Replace the AC drive.

5. The AC drive IGBT is damaged.
- Replace the AC drive.
Err15
External
equipment
fault
Cause & Solution:

1. External fault signal is input via DI.
- Confirm that the mechanical condition allows restart (F8-18) and reset the operation.

2. External fault signal is input via virtual I/O.
- Confirm that the virtual I/O parameters in group A1 are set correctly and reset the operation.
Err16
Communication
fault
Cause & Solution:

1. The host controller is in abnormal state.
- Check the cable of the host controller.

2. Communication cable is abnormal.
- Check the communication cables.

3. Communication parameters in group Fd are set improperly.
- Set communication parameters in group Fd properly.

4. After all the preceding checkings are done but the fault still exists, restore the default settings.
Err17
Contactor
fault
Cause & Solution:

1. Drive board and power supply are abnormal.
- Replace drive board or power supply board.

2. Contactor is abnormal.
- Replace contactor.

3. The lightning protection board is abnormal.
- Replace the lightning protection board.
Err18
Current
detection
fault
Cause: The drive board is abnormal.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
Err19
Motor
auto-tuning
fault
Cause & Solution:

1. Motor parameters are not set according to nameplate.
- Set motor parameters correctly according to nameplate.

2. Motor auto-tuning times out.
- Check the cable connecting AC drive and motor.

3. The encoder is abnormal.
- Check whether F1-27 (encoder pulses per revolution) is set correctly.
- Check whether signal lines of encoder are connected correctly and securely.
Err20
Encoder
fault
Cause & Solution:

1. Encoder is not matched.
- Set the type of encoder correctly.

2. Encoder wiring is incorrect.
Check the PG card power supply and phase sequence.

3. Encoder is damaged.
- Replace encoder.

4. PG card is abnormal.
- Replace PG card.
Err21
EEPROM read-
write fault
Cause: EEPROM chip is damaged.

Solution: Replace the AC drive.
Err23
Short
circuit to
ground
Cause & Solution:

1. The motor is short circuited to the ground.
- Replace cable or motor.

2. The upper IGBT is damaged.
- There is an hardware or software issue in drive. Need to repair or replace drive.
Err26
Accumulative
running time
reached
Cause: Accumulative running time reaches the setting value.

Solution: Clear the record through parameter initialization.
Err27
User-defined
fault 1
Cause: User-defined fault 1 is input via DI.

Solution: Reset the operation.
Err28
User-defined
fault 2
Cause: User-defined fault 2 is input via DI.

Solution: Reset the operation.
Err29
Accumulative
power-on
time reached
Cause: Accumulative power-on time reaches the setting value.

Solution: Clear the record through parameter initialization.
Err30
Off load
fault
Cause: The output current of AC drive is smaller than F9-64 (load loss detection level).

Solution: Check whether the load is disconnected or the setting of F9-64 and F9-65 (load lost detection time) satisfies actual running conditions.
Err31
PID
feedback
lost
during
running
Cause: PID feedback is smaller than the setting value of FA-26 (detection level of PID feedback loss).

Solution: Check PID feedback or set FA-26 properly.
Err40
Pulse-by-
pulse
current limit
fault
Cause & Solution:

1. The load is too heavy or locked-rotor occurs on the motor.
- Reduce the load or check motor and mechanical conditions.

2. The rated AC drive power is low.
- Replace the drive by one with higher rated power.
Err41
Motor
switchover
fault during
running
Cause: Motor switchover via terminal during drive running of the AC drive.

Solution: Perform motor switchover after the AC drive stops.
Err42
Speed error
Cause & Solution:

1. Encoder parameters are set improperly.
- Set encoder parameters properly.

2. Motor auto-tuning is not performed.
- Perform motor auto-tuning.

3. F9-69 (detection level of speed error) and F9-70 (detection time of speed error) are set oncorrectly.
- Set F9-69 and F9-70 correctly based on actual condition.
Err43
Motor
overspeed
Cause & Solution:

1. Encoder parameters are set improperly.
- Set encoder parameters properly.

2. Motor auto-tuning is not performed.
- Perform motor auto-tuning.

3. F9-67 (Overspeed detection level) and F9-68 (Overspeed detection time) are set incorrectly.
- Set F9-67 and F9-68 correctly based on the actual situation.
Err45
Motor
overtemperature
Cause & Solution:

1. Cable connection of temperature sensor becomes loose
- Check cable connection of temperature sensor.

2. The motor temperature is too high.
- Decrease carrier frequency or take other measures to cool the motor.
Err61
Braking
unit
overload
Cause: Resistance of braking resistor is too small.

Solution: Replace a braking resistor of larger resistance.
Err62
Short-circuit
of braking
circuit
Cause: Braking IGBT is abnormal.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
HC FaultCause & Solution:

1. The cable between the drive board and control board is in poor contact.
- Re-connect the 4-pin cable and 28-pin cable.

2. The control board is damaged.
- Replace the AC drive.

3. The motor or motor cable is short circuited to ground.
- Check whether short-circuit occurs on motor, motor cable or contactor.

4. The mains voltage is too low.
- Check the power supply.

How to Clear & Reset Inovance MD500 Drive Faults

  1. Keypad Reset: Press the red STOP/RES key on the operating keypad while the drive is in fault trip status (applicable when parameter F7-02 enables the STOP/RES key function).
  2. Digital Input Reset (DI): Configure any multi-function digital input terminal (DI1 to DI5) to function 9 (Fault reset) via parameters F4-00 to F4-04, then momentarily pulse that digital input to terminal COM.
  3. Communication Bus Reset: Transmit command code 0007H (Fault Reset) to control register address 2000H via embedded Modbus-RTU (RS485) or optional Profibus-DP, PROFINET, CANopen, or EtherCAT cards.
  4. Fault Log Diagnostic Review: Before clearing active faults, review parameters F9-14 through F9-44 to inspect operating frequency, output current, and intermediate bus voltage captured during the last three recorded trip events.
  5. AC Mains Power Cycle: Switch off primary AC line supply breaker, wait until the charge indicator LED completely extinguishes (minimum 5 minutes for internal capacitor bank discharge), and restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 36VDC across terminals [(+)] and [(-)] before inspecting motor cables, removing housing covers, or handling terminals U, V, and W on the Inovance MD500 drive.