Inovance IS810N Servo Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Inovance IS810N multi-axis EtherCAT servo drive platform. Search or filter through the complete fault code directory below.

Multi-Axis Servo Platform Drive Modules: 0.85 to 75 kW (Dual/Single Axis) Integrated STO SIL 3 / PL e
Power Range 0.85 – 75 kW (Rectifier Up to 355 kW)
Supply Voltage 3-Ph 380–480V AC (DC Bus 537–679V DC)
Control Modes CSP, CSV, CST, Profile & Homing (CiA 402)
Operator Interface Built-in 5-Digit LED / InoDriverShop PC Tool

Complete Inovance IS810N Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E1.101, E12.01, or Overcurrent).

Fault Code and MeaningCause and Remedy
E12.01
Input voltage abnormal

Cause: R phase loss occurs on input voltage.



Remedy:

  • Check the three-phase power.

  • Check whether the input power cable is broken.

  • Check that the input terminal is correctly connected.

  • Check the hardware voltage detection circuit.


E12.02
Input voltage abnormal

Cause: S phase loss occurs on input voltage.



Remedy:

  • Check the three-phase power.

  • Check whether the input power cable is broken.

  • Check that the input terminal is correctly connected.

  • Check the hardware voltage detection circuit.


E12.03
Input voltage abnormal

Cause: T phase loss occurs on input voltage.



Remedy:

  • Check the three-phase power.

  • Check whether the input power cable is broken.

  • Check that the input terminal is correctly connected.

  • Check the hardware voltage detection circuit.


E12.04
Input voltage abnormal

Cause: The input three-phase voltage is too high.



Remedy:

  • Adjust three-phase voltage to normal range.


E12.05
Input voltage abnormal

Cause: Three-phase input voltage unbalance occurs.



Remedy:

  • Check the three-phase power.

  • Check the hardware voltage detection circuit.


E14.00
SCR overheat

Cause:

- The ambient temperature is too high.

- The ventilation is clogged.

- The fan is damaged.

- The thermally sensitive resistor of SCR is damaged.

- The SCR is damaged.



Remedy:

  • Lower the ambient temperature.

  • Clean the ventilation.

  • Replace the cooling fan.

  • Contact the agent or Inovance.


E16.01
Communication fault

Cause: Modbus communication times out.



Remedy:

  • Check that the RS-485 communication cable is correctly connected.

  • Check that the setting of Fd-04 (Modbus communication timeout time) and PLC communication cycle are proper.


E16.11
Communication fault

Cause: CANopen communication times out.



Remedy:

  • Check that the CAN communication cable is correctly connected.

  • Check the setting of Fd-15 [Maximum value of node reception error count] to Fd-17 (Bus disconnection times) and confirm interference.


E16.12
Communication fault

Cause: The PDO mapping configured for CANopen is not consistent with the actual mapping.



Remedy:

  • Check the PDO mapping of parameters in group AF.


E16.13
Communication fault

Cause: Data exchange times out when the drive units receive data from the power supply unit.



Remedy:

  • Check that the power supply unit is running.

  • Check whether the network cables of the power supply unit and drive units are connected.

  • Check that the terminal build-out resistor is correctly connected.

  • Check Fd-12 (CAN baud rate) and confirm setting is consistent.


E16.14
Communication fault

Cause: Data exchange is abnormal when the drive units receive data from the power supply unit.



Remedy:

  • Rectify the fault of the power supply unit.


E16.21
Communication fault

Cause: The CANlink heartbeat times out.



Remedy:

  • Check that the CAN communication cable is correctly connected.

  • Check the setting of Fd-15 and Fd-17 and confirm interference.


E16.22
Communication fault

Cause: CANlink station numbers conflict.



Remedy:

  • Change the value of Fd-13 (CAN station number) to make CANlink station numbers different.


E16.31
Communication fault

Cause: Profibus-DP communication times out (specific to Profibus-DP-to-CANopen bridge mode).



Remedy:

  • Check that the Profibus-DP communication cable is correctly connected.


E16.34
Communication fault

Cause: A CAN slave is offline during Profibus-DP-to-CANopen bridge configuration.



Remedy:

  • Check whether the value of the "The number of devices" parameter of PLC is consistent with the actual number of stations.

  • Check that the slave station number is correctly set.


E16.35
Communication fault

Cause: Parameters of Profibus-DP-to-CANopen bridge configuration are incorrectly set.



Remedy:

  • Check that the value of the "NO. n" parameter of PLC is consistent with the setting of AF-66 (Valid RPDOs) and AF-67 (Valid TPDOs).


E16.41
Communication fault

Cause: Profibus-DP communication times out.



Remedy:

  • Check that the Profibus-DP communication cable is correctly connected.


E16.42
Communication fault

Cause: Parameters of Profibus-DP-to-CANopen bridge configuration are incorrectly set.



Remedy:

  • Check that the value of the "NO. 1" parameter of PLC is consistent with the setting of AF-66 and AF-67 of the bridge unit.


E16.71
Communication fault

Cause: PROFINET communication times out.



Remedy:

  • Check the Ethernet wiring.

  • Increase the PROFINET timeout interval.


E16.72
Communication fault

Cause: The CANopen slave communication times out.



Remedy:

  • Check the wiring.

  • Check whether the termination resistor is configured correctly.


E16.74
Communication fault

Cause: The configured CANopen slave is missing.



Remedy:

  • Modify the AC drive site number or modify the PLC configuration to ensure consistent configuration.


E16.75
Communication fault

Cause: CANopen mapping data does not match.



Remedy:

  • Check the process data mapping of parameter configuration.

  • Ensure that the data length of the PLC configuration is consistent with the process data length of the corresponding slave.


E16.76
Communication fault

Cause: The process data of the power supply unit does not match the configuration.



Remedy:

  • Check the process data mapping. Ensure data length of PLC configuration is consistent with process data length of the power supply unit.


E16.77
Communication fault

Cause: An internal serial communication fault occurs.



Remedy:

  • Check that Fd-10 (Communication protocol selection) is set to 5.

  • Re-power on the power supply unit.

  • Contact the agent or Inovance.


E16.78
Communication fault

Cause: An internal SPI communication fault occurs.



Remedy:

  • Check that Fd-10 (Communication protocol selection) is set to 5.

  • Re-power on the power supply unit.

  • Contact the agent or Inovance.


E61.01
Braking unit fault

Cause: The braking unit is directly connected.



Remedy:

  • Check whether the braking resistor is short circuited.

  • Check whether the brake transistor is directly connected.


E61.02
Braking unit fault

Cause: Overcurrent occurs on the braking unit.



Remedy:

  • Check whether the resistance and power of the braking resistor are too low.

  • Check for interference.

  • Check whether an error occurs during hardware circuit detection.


E61.03
Braking unit fault

Cause: Overload occurs on the braking unit.



Remedy:

  • Check whether the resistance and power of the braking resistor are too small.


E61.04
Braking unit fault

Cause: An overheat warning is detected on the braking unit.



Remedy:

  • Lower the ambient temperature.

  • Check whether the cooling fan runs properly.

  • Clean the ventilation.

  • Check whether the temperature sensor is damaged.


E61.05
Braking unit fault

Cause: The braking unit overheats.



Remedy:

  • Lower the ambient temperature.

  • Check whether the cooling fan runs properly.

  • Clean the ventilation.

  • Check whether the temperature sensor is damaged.


-H-C-
HC Displayed

Cause:

- Related components on control board are damaged.

- Motor or motor cable short circuited to ground.

- The hall is damaged.

- Mains voltage is too low.



Remedy:

  • Contact the agent or Inovance.


E23.00
Motor short circuit

Cause:

- The motor or motor cable is short circuited to the ground.

- The power supply unit is damaged.



Remedy:

  • Use a megger to measure the insulation resistance of the motor and motor cable.

  • Contact the agent or Inovance.


How to Clear & Reset Inovance IS810N Drive Faults

  1. Keypad Parameter Reset: Turn off the servo enable (S-ON) signal for the tripped axis. Navigate to auxiliary parameter H0d.01 or object 200D-02h (Fault reset) and set its value to 1 using the module keypad.
  2. Digital Input Reset (DI): With the S-ON signal removed, apply an active pulse signal (held high for at least 3 ms) to the digital input terminal configured with function FunIN.2 (ALM-RST: Fault and Warning Reset).
  3. InoDriverShop Commissioning Tool: Connect your PC via the dedicated RJ45 Ethernet port (Modbus TCP) or serial comms interface, launch InoDriverShop, inspect active alarms and logs in parameter group H0B, and execute the “Fault Reset” command.
  4. EtherCAT CiA 402 Controlword: In your master PLC or motion controller, write a rising edge transition from 0 to 1 on Bit 7 (Fault Reset) within Controlword 0x6040 for the affected axis over EtherCAT.
  5. Power Cycle: Disconnect both the 3-phase AC mains supply to the central rectifier unit (MD810) and the 24V DC auxiliary control power. Wait at least 15 minutes until the shared DC busbar discharges completely and the CHARGE LED turns off before restoring power.
⚠️ High-Voltage Electrical Safety Warning: The Inovance IS810N platform operates across a high-energy common DC bus linking the rectifier and multiple drive axes (537 to 679 VDC or higher). Always isolate upstream 3-phase AC power to the central power supply module and verify with a calibrated digital multimeter that the shared DC busbar voltage across [+] and [-] has dropped strictly below 36 VDC before disconnecting modules, servicing motor power terminals (U, V, W), or removing protective shrouds.