Inovance MD290 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Inovance MD290 general-purpose open-loop AC drive series. Search or filter through the complete fault code directory below.
Power Range
0.4 – 450 kW (0.5 – 600 HP)
Supply Voltage
3-Ph 380–480V / 3-Ph 200–240V AC
Control Modes
V/f Control & Open-Loop Vector (SVC)
Operator Interface
Integrated LED Keypad / Optional LCD (MDKE9)
Complete Inovance MD290 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type Err02, Err08, or Overcurrent).
| Fault Codes | Cause & Solution |
|---|---|
| Err02 Overcurrent during acceleration | Cause & Solution: 1. Ground fault or short circuit exists in the output circuit. - Check whether short-circuit occurs on the motor, the motor cable or contactor. 2. Acceleration time is too short. - Increase acceleration time. 3. Customized torque boost or V/F curve is not appropriate. - Adjust the customized torque boost or V/F curve. 4. The voltage is too low. - Adjust the voltage to normal range. 5. The spinning motor is started. - Enable the catching a spinning motor function or start the motor after it stops. 6. A load is applied suddenly during acceleration. - Cancel the suddenly added load. 7. The rated AC drive power is low. - Replace the drive by one with higher rated power. 8. The braking resistor resistance is small. - The braking resistor is short circuited. - Replace a new braking resistor. |
| Err03 Overcurrent during deceleration | Cause & Solution: 1. Ground fault or short circuit exists in the output circuit. - Check whether short-circuit occurs on motor, motor cable or contactor. 2. Acceleration time is too short. - Increase acceleration time. 3. The voltage is too low. - Adjust the voltage to normal range. 4. A load is added suddenly during deceleration. - Cancel the suddenly added load. 5. Braking unit and braking resistor are not installed. - Install the braking unit and braking resistor. 6. The braking resistor resistance is small or the braking resistor is short circuited. - Replace a new braking resistor. |
| Err04 Overcurrent at constant speed | Cause & Solution: 1. Ground fault or short circuit exists in the output circuit. - Check whether short-circuit occurs on the motor, motor cable or contactor 2. The voltage is too low. - Adjust the voltage to normal range. 3. A load is added suddenly during running. - Cancel the suddenly added load. 4. The rated AC drive power is low. - Replace the drive by one with higher rated power. 5. The braking resistor resistance is small or the braking resistor is short circuited. - Replace a new braking resistor. |
| Err05 Overvoltage during acceleration | Cause & Solution: 1. Input voltage is too high. - Adjust input voltage to normal range. 2. An external force drives motor during acceleration. - Cancel the external force. 3. Braking unit and braking resistor are not installed. - Install the braking unit and braking resistor. 4. Acceleration time is too short. - Increase acceleration time. |
| Err06 Overvoltage during deceleration | Cause & Solution: 1. Input voltage is too high. - Adjust input voltage to normal range. 2. An external force drives motor during deceleration. - Cancel the external force or install the braking resistor. 3. Deceleration time is too short. - Increase deceleration time. 4. Braking unit and braking resistor are not installed. - Install the braking unit and braking resistor. |
| Err07 Overvoltage at constant speed | Cause & Solution: 1. Input voltage is too high. - Adjust input voltage to normal range. 2. An external force drives motor during running. - Cancel the external force or install a braking resistor. |
| Err08 Pre-charge resistor fault | Cause: Bus voltage fluctuates around undervoltage threshold continuously Solution: There is an hardware or software issue in drive. Need to repair or replace drive. |
| Err09 Undervoltage | Cause & Solution: 1. An instantaneous power failure occurs. - Reset the fault 2. The AC drive's input voltage is not within the permissible range. - Adjust the voltage to normal range. 3. The bus voltage is abnormal. - Replace the AC drive. 4. The rectifier bridge, the pre-charge resistor, the drive board or the control board are abnormal. - Replace the AC drive. |
| Err10 Drive overload | Cause & Solution: 1. The load is too heavy or locked-rotor occurs on the motor. - Reduce the load or check motor and mechanical conditions. 2. The rated AC drive power is low. - Replace the drive by one with higher rated power. |
| Err11 Motor overload | Cause & Solution: 1. F9-01 (Motor overload protection gain) is set improperly. - Set F9-01 correctly. 2. The load is too heavy or locked-rotor occurs on the motor. - Reduce the load or check motor and mechanical conditions. 3. The rated AC drive power is low. - Replace the drive by one with higher rated power. |
| Err12 Input phase loss | Cause & Solution: 1. Three phase input is abnormal. - Eliminate faults in external circuitry 2. Drive board is abnormal. - Eliminate faults in external circuitry 3. Lightning protection board is abnormal. - There is an hardware or software issue in drive. Need to repair or replace drive. 4. Control board is abnormal. - There is an hardware or software issue in drive. Need to repair or replace drive. |
| Err13 Output phase loss | Cause & Solution: 1. Motor winding is damaged. Check resistance between motor cables. - Replace motor is winding is damaged. 2. The cable connecting the AC drive and the motor is abnormal. - Check for wiring errors and ensure the output cable is connected properly 3. The AC drive's three-phase outputs are unbalanced when the motor is running. - Check whether the motor three-phase winding is normal. 4. The drive board or the IGBT is abnormal. - Replace the AC drive. |
| Err14 IGBT overheat | Cause & Solution: 1. The ambient temperature is too high. - Lower the ambient temperature. 2. The ventilation is clogged. - Clean the ventilation. 3. The fan is damaged. - Replace the cooling fan. 4. The thermally sensitive resistor of IGBT is damaged. - Replace the AC drive. 5. The AC drive IGBT is damaged. - Replace the AC drive. |
| Err15 External fault | Cause & Solution: 1. External fault signal is input via DI. - Confirm that the mechanical condition allows restart (F8-18)and reset the operation. 2. External fault signal is input via virtual I/O. - Confirm that the virtual I/O parameters in group A1 are setcorrectly and reset the operation. |
| Err16 Communication fault | Cause & Solution: 1. The host controller is in abnormal state. - Check the cable of the host controller. 2. Communication cable is abnormal. - Check the communication cables. 3. Communication parameters in group Fd are set improperly. - Set communication parameters in group Fd properly. 4. After all the preceding checkings are done but the fault still exists, restore the default settings. |
| Err17 Contactor fault | Cause & Solution: 1. Drive board and power supply are abnormal. - Replace drive board or power supply board. 2. Contactor is abnormal. - Replace contactor. 3. The lightning protection board is abnormal. - Replace the lightning protection board. |
| Err18 Current detection fault | Cause: The drive board is abnormal. Solution: There is an hardware or software issue in drive. Need to repair or replace drive. |
| Err19 Motor auto-tuning fault | Cause & Solution: 1. Motor parameters are not set according to nameplate. - Set motor parameters correctly according to nameplate. 2. Motor auto-tuning times out. - Check the cable connecting AC drive and motor. |
| Err21 EEPROM read- write fault | Cause: EEPROM chip is damaged. Solution: Replace the AC drive. |
| Err23 Short circuit to ground | Cause & Solution: 1. The motor is short circuited to the ground. - Replace cable or motor. 2. The upper IGBT is damaged. - There is an hardware or software issue in drive. Need to repair or replace drive. |
| Err26 Accumulative running time reached | Cause: Accumulative running time reaches the setting value. Solution: Clear the record through parameter initialization. |
| Err27 User-defined fault 1 | Cause: User-defined fault 1 is input via DI. Solution: Reset the operation. |
| Err28 User-defined fault 2 | Cause: User-defined fault 2 is input via DI. Solution: Reset the operation. |
| Err29 Accumulative power-on time reached | Cause: Accumulative power-on time reaches the setting value. Solution: Clear the record through parameter initialization. |
| Err30 Off load fault | Cause: The output current of AC drive is smaller than F9-64 (load loss detection level). Solution: Check whether the load is disconnected or the setting of F9-64 and F9-65 (load lost detection time) satisfies actual running conditions. |
| Err31 PID feedback lost during running | Cause: PID feedback is smaller than the setting value of FA-26 (detection level of PID feedback loss). Solution: Check PID feedback or set FA-26 properly. |
| Err40 Pulse-by- pulse current limit fault | Cause & Solution: 1. The load is too heavy or locked-rotor occurs on the motor. - Reduce the load or check motor and mechanical conditions. 2. The rated AC drive power is low. - Replace the drive by one with higher rated power. |
| Err41 Motor switchover fault during running | Cause: Motor switchover via terminal during drive running of the AC drive. Solution: Perform motor switchover after the AC drive stops. |
| Err45 Motor overtemperature | Cause & Solution: 1. Cable connection of temperature sensor becomes loose - Check cable connection of temperature sensor. 2. The motor temperature is too high. - Decrease carrier frequency or take other measures to cool the motor. |
| Err61 Braking unit overload | Cause: Resistance of braking resistor is too small. Solution: Replace a braking resistor of larger resistance. |
| Err62 Short-circuit of braking circuit | Cause: Braking IGBT is abnormal. Solution: There is an hardware or software issue in drive. Need to repair or replace drive. |
| HC Fault | Cause & Solution: 1. The cable between the drive board and control board is in poor contact. 2. The control board is damaged. - Replace the AC drive. 3. The motor or motor cable is short circuited to ground. - Check whether short-circuit occurs on motor, motor cable or contactor. 4. The mains voltage is too low. - Check the power supply. |
How to Clear & Reset Inovance MD290 Drive Faults
- Keypad Reset: Press the red STOP/RES key on the front operating panel. Ensure the active run command (from terminals, communication, or keypad) is removed before clearing the fault condition.
- Digital Input Reset (DI): If an input terminal is assigned to function 9 (Fault reset / RESET) in parameter group F4-00 to F4-04 (DI1–DI5), apply a pulse signal to that digital input terminal.
- InoDriveShop PC Software: Connect your PC to the drive using an RS-485 communication converter or optional PC comms kit, launch InoDriveShop, check active faults in parameter group U0, and select “Fault Reset” in the monitoring toolbar.
- Fieldbus Control Word: Write a rising edge on Bit 7 (Fault Reset) in the drive control word via the installed communication card (Modbus-RTU, PROFIBUS-DP, PROFINET, CANopen, or CANlink).
- Power Cycle: Disconnect the main AC line power, wait until the DC bus capacitors discharge completely (at least 10 minutes until the LED display is completely dark), and then restore mains power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual electrical charge remains in the intermediate DC link capacitors after AC mains power has been switched off. Always verify with a calibrated digital multimeter that the DC bus voltage across terminals [(+)] and [(-)] has dropped strictly below 36 VDC before opening terminal covers, handling dynamic braking units, or inspecting motor output terminals (U, V, W).