KEB COMBIVERT F5 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the KEB COMBIVERT F5 modular inverter and servo drive series. Search or filter through the complete fault code directory below.

Modular Inverter & Servo System Power: 0.37 to 900 kW (0.5 to 1200 HP) ASCL / SCL & Integrated Safety
Power Range 0.37 – 900 kW (0.5 – 1200 HP)
Supply Voltage 1-ph 230V / 3-ph 230V, 400V, 690V
Control Modes V/Hz, SCL, ASCL & Closed-Loop FOC
Operator Interface LED Keypad / LCD Operator / COMBIVIS

Complete KEB COMBIVERT F5 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E.OC, E.OP, E.dOH, or Overcurrent).

Fault CodeCause and Solution / Troubleshoot
E.OL2 fault in KEB COMBIVERT F5 Drive
E.OL2 fault in KEB COMBIVERT F5 Drive indicates a Low Speed Overload. This means the motor has drawn excessive current at a low frequency or standstill for too long, exceeding its thermal capacity.
Cause:


Excessive current at low speed (typically below 3Hz). Possible factors include:

  • Incorrect motor data.

  • Incorrect encoder configuration.

  • High mechanical load/friction issues (e.g. starting or stopping against brake).





Remedy:



  • Verify motor data, specifically the motor rated speed and frequency relationship for PM Synchronous Motors.

  • Verify correct encoder settings including:

    • LF.27: Encoder Pulse Number

    • LF.28: Swap Encoder Channels (A/B setting)

    • LF.77: Encoder Pole position for PM Synchronous Motors. Relearn Encoder Pole Position as needed (see Section 5.11.1).



  • Check for high mechanical load/issues (friction) such as starting or stopping against brake.


E.dOH fault in KEB COMBIVERT F5 Drive
E.dOH fault in KEB COMBIVERT F5 Drive indicates a Motor Overheat. This means the external PTC temperature sensor has tripped, signaling that the motor is running dangerously hot.
Cause:


If a motor PTC temperature sensor, relay, or KTY (special hardware required) is connected to terminals T1, T2 and the motor overheat function US.33 EdOH Function = On, then the relay opens when PTC resistance exceeds 1650 Ohms.



Excessive motor heating causes may include:

  • Excessive current.

  • Incorrect encoder settings.

  • High mechanical load/friction.

  • Insufficient motor cooling.





Remedy:



  • Verify correct motor data.

  • Verify correct encoder settings including:

    • LF.27: Encoder Pulse Number

    • LF.28: Swap Encoder Channels (A/B setting)

    • LF.77: Encoder Pole position for PM Synchronous Motors.



  • Check for high mechanical load/issues (friction).

  • Inspect and ensure sufficient motor cooling.


E.OH2 fault in KEB COMBIVERT F5 Drive
E.OH2 fault in KEB COMBIVERT F5 Drive indicates a Motor Protection error. This means the electronic motor overload protection was activated because the RMS motor current exceeded safe parameters.
Cause:


Excessive RMS motor current according to the LF.08 Electric Motor Protection overload curve, or if the LF09 Peak Motor Current Factor is exceeded for more than 3 seconds for PM Synchronous Motors.

  • For induction motors, the baseline current for Electric Motor Protection corresponds to LM09 Electric Motor Overload Current.

  • For PM Synchronous Motors, the baseline current corresponds to LF.12 Motor Current.





Remedy:



  • Verify motor data, specifically the motor rated speed and frequency relationship for PM Synchronous Motors (see Section 5.6.2).

  • Verify correct encoder settings including:

    • LF.27: Encoder Pulse Number

    • LF.28: Swap Encoder Channels (A/B setting)

    • LF.77: Encoder Pole position for PM Synchronous Motors. Relearn Encoder Pole Position as needed (see Section 5.11).



  • Check for high mechanical load/issues (friction).


E.OC / EOC fault in KEB COMBIVERT F5 Drive
E.OC / EOC fault in KEB COMBIVERT F5 Drive indicates an Over Current. This means the inverter's output current spiked beyond the permissible peak limit or a ground fault occurred.
Cause:



  • If the error occurs instantly at the start of each run:

    • Ground fault on motor leads.

    • Damaged or slow to close motor contactor.

    • Shorted output transistor.

    • Motor failure.



  • If the error is intermittent:

    • Damaged or slow to close motor contactor.

    • Loose motor connections.

    • Electrical noise, faulty grounding.







Remedy:


The current and peak current may be viewed in LF.93 and LF.94. To reset the logged peak value, press enter.



Systematic Isolation & Checks:

  • To determine if the over current is caused by the inverter, motor, or intermediate components (e.g. motor contactor), systematically isolate these items.

  • Bypass testing: Start by bypassing the motor contactor (do not simply jumper!).

  • Resistance checks: Perform checks with the motor disconnected from the inverter. Measure resistance from phase to phase (should read winding resistance specified by manufacturer). Measure phase to ground resistance (should read open circuit). If a fault is indicated, disconnect cables at the motor side and remake the test to isolate motor vs. cabling.

  • Insulation tests: Meg tests to check motor winding insulation can only be performed with the motor completely disconnected from the inverter to prevent high-voltage damage to the output section of the drive.

  • Inverter output testing (Open-loop mode):

    1. Power off, wait for appropriate discharge time, and disconnect motor leads from the inverter.

    2. If not an induction motor, change the motor configuration to induction motor in US10 (note existing settings before doing this, as changing this parameter will default all parameters), then Write Configuration to Drive in US04.

    3. Set LF.30 Control Mode = Open Loop V/Hz.

    4. Run the system with the motor leads disconnected in open-loop. If the overcurrent error still occurs, the inverter output is faulty. If it does not occur, the fault lies in the motor, cabling, or contactor.






Note: Under normal operation, the drive limits the output current to the maximum torque in 0.LF36 (Maximum Output Current = LF.12 Motor Current × 0.LF.36 Maximum Torque / LF.17 Motor Torque). The drive also limits output current to the hardware current limit listed as Peak Current (30sec.) rating in the Technical Data tables (Sec. 2.1 and 2.2).
E.OP fault in KEB COMBIVERT F5 Drive
E.OP fault in KEB COMBIVERT F5 Drive indicates an Over Voltage. This means the DC bus voltage rose above the permissible limit, typically due to regenerative motor energy or line voltage spikes.
Cause:


Elevated DC bus voltage. Common sources include:

  • Motor regenerative operation (deceleration or overhauling).

  • Transient voltage spikes from the mains supply.

  • High line input voltage.

  • Malfunctions in the DC bus voltage measurement circuit.

  • High-frequency electrical noise.





Remedy:


The DC bus voltage LF.95 and the peak DC bus voltage LF.96 can be monitored.

  • Braking Resistor Check: When using a braking resistor to dissipate regenerated energy, the braking resistor should come on at:

    • 460V drives = 760VDC

    • 230V drives = 380VDC


    Ensure proper connection of the braking resistor to the braking transistor terminals PB, ++. Disconnect the braking resistor and measure resistance to verify if correct. Check the braking transistor if problems persist.

  • Line Regen Unit Check: If a line regen unit is used, by default, the line regen unit will turn on at 103% of the idle DC bus voltage. Ensure proper connection between the drive and regen unit at the ++ and - - terminals at both units. Ensure the regen unit is regenerating properly, is in the regen status when required, and has no active faults preventing operation.

  • Transient Spikes: If the over voltage is due to transient voltage spikes from the line, install a 3-5% line reactor.

  • High Line Voltage: Step-down the line voltage using a transformer.

  • Measurement Circuit or Noise Issues: Measure the DC bus directly and verify against the DC bus voltage read from the Diagnostics screen. The DC bus should measure approximately 1.41 x AC Input phase-to-phase. If there is high-frequency noise, verify proper mains grounding.


E.PU fault in KEB COMBIVERT F5 Drive
E.PU fault in KEB COMBIVERT F5 Drive indicates a Power Unit error. This means a general hardware malfunction occurred within the internal power circuit stages.
Cause:


Internal power circuit malfunction.



Remedy:


The inverter must be inspected and repaired by KEB or replaced.
E.PUCH fault in KEB COMBIVERT F5 Drive
E.PUCH fault in KEB COMBIVERT F5 Drive indicates the Power Unit Changed. This means the control card detected a new power stage, usually following a hardware replacement or modification.
Cause:


Control card change or hardware modification.



Remedy:


This error should automatically clear itself.
E.PUCI fault in KEB COMBIVERT F5 Drive
E.PUCI fault in KEB COMBIVERT F5 Drive indicates a Power Unit Invalid error. This means the drive's control card could not correctly identify the power circuit during initialization, often due to electrical noise or poor connection.
Cause:


Initialization recognition failure. This error could occur from electrical noise.



Remedy:



  • Disconnect the terminal strip, encoder cable, and serial communication (if used), then power cycle the drive.

  • Check phase-to-phase and phase-to-ground line voltages to make sure they are balanced and not causing noise.

  • Re-seat the ribbon cable connecting the control card to the power stage.


E.UP fault in KEB COMBIVERT F5 Drive
E.UP fault in KEB COMBIVERT F5 Drive indicates an Under Voltage. This means the internal DC bus voltage dropped below the minimum operating threshold, often caused by a phase loss or low input mains.
Cause:


DC bus voltage drop. Common sources include:

  • Input voltage too low or unstable.

  • One phase of the line input is missing.

  • Line input phases are imbalanced (the phase-to-phase voltage imbalance should not exceed 2%).

  • Undersized or incorrectly wired isolation transformer.

  • Faulty DC bus voltage measurement circuit.





Remedy:



  • Verify the input voltage and wiring. The DC bus should measure approximately 1.41 x AC Input phase-to-phase, and should match the DC bus measurement read by the drive in the Diagnostics Menu.

  • Measure the DC bus directly and verify against the DC bus voltage read from the Diagnostics screen.




Note: A 460V drive can operate on a 230V, single phase power supply if programmed for UPS mode operation.
nE.OL2 message in KEB COMBIVERT F5 Drive
nE.OL2 message in KEB COMBIVERT F5 Drive indicates no Error Low Speed Overload. This means the previous low-speed overload condition has cleared and the drive is ready to be reset.
Cause:


Low speed overload has cleared.



Remedy:


The error is cleared and the drive can be reset.
nE.dOH message in KEB COMBIVERT F5 Drive
nE.dOH message in KEB COMBIVERT F5 Drive indicates no Error Motor Overheat. This means the motor temperature has dropped back to an acceptable level and the overheat fault can be reset.
Cause:


Motor temperature has dropped back to acceptable levels.



Remedy:


The motor overheat sensor is reset, and the Error Motor Overheat fault can be reset.
nE.OL message in KEB COMBIVERT F5 Drive
nE.OL message in KEB COMBIVERT F5 Drive indicates no Error Overload. This means the internal overload counter has returned to 0% and the drive can be safely reset.
Cause:


The overload counter has reached 0%.



Remedy:


Allowing the motor to cool down to 0% overload allows the error overload to be reset.
no_PU fault in KEB COMBIVERT F5 Drive
no_PU fault in KEB COMBIVERT F5 Drive indicates the Power Unit is Not Ready. This means the control card is powered up but cannot communicate with the power stage, often because main power is missing or a cable is loose.
Cause:


The Power Unit Not Ready message may occur due to:

  • Control card powered up by an external power supply, but the drive is not powered up by the line. Since the drive is not being powered by the line, the power stage cannot be identified.

  • Connection issues between the control card and the power stage.

  • Failure of the switching power supply.





Remedy:



  • For inverter housing sizes G, H, R, U: Remove then reconnect the ribbon cable connecting the control card to the power stage at the control card connection.

  • For inverter housing sizes D, E: Remove the control card then re-seat, ensuring correct pin connections.

  • If reseating the ribbon cable does not resolve the issue, there may be a failure of the switching power supply. The drive will need to be replaced or inspected and repaired by KEB.


I_data fault in KEB COMBIVERT F5 Drive
I_data fault in KEB COMBIVERT F5 Drive indicates Invalid Data. This means a parameter value was entered that falls outside the permissible limits for that setting.
Cause:


Parameter is outside of the permissible limits.



Remedy:


Ensure the parameter entered is within the permitted range.
I_oPE fault in KEB COMBIVERT F5 Drive
I_oPE fault in KEB COMBIVERT F5 Drive indicates an Invalid Operation. This means an operation was attempted while the drive was in an incorrect state or had active inputs preventing the action.
Cause:


An operation was attempted in an incorrect state or while inputs are active.



Remedy:


Change the drive mode from Run to Stop. Check LF.82 input status to ensure no inputs are currently active.
EOH fault in KEB COMBIVERT F5 Drive
EOH fault in KEB COMBIVERT F5 Drive indicates an Overheat Power Module. This means the inverter's heatsink temperature rose above the safe operating limit due to poor ventilation or fan failure.
Cause:


The heatsink temperature can be viewed in ru.38. The overheat limit is 90 degrees Celsius for most drives (see Technical Data for units 175HP and larger). Under normal operation, the heatsink temperature should usually be below 65 degrees Celsius.



Causes of inverter heatsink overheat include:

  • Insufficient cooling or ambient temperature too high.

  • Faulty temperature sensor.





Remedy:



  • Verify operation of fans: The fans are thermostatically controlled to come on at about 45 degrees Celsius. To turn all fans on high, US.37 Function Test can be set to "Fans On".

  • Make sure fans are not clogged.

  • Increase airflow around the inverter or add cabinet fans.

  • Check sensor integrity: Power down the inverter or let it stand idle to allow for the heatsink temperature to cool. If the heatsink temperature read by the drive for diagnostics seems unreasonably high for a heatsink cool to the touch, the heatsink temperature sensor may be faulty and would need to be repaired by KEB.


EOL fault in KEB COMBIVERT F5 Drive
EOL fault in KEB COMBIVERT F5 Drive indicates an Overload. This means the drive experienced a time-dependent excessive current draw and will require a cooldown period before resetting.
Cause:


Excessive motor overload. Factors include:

  • Excessive current.

  • Incorrect motor data.

  • Incorrect encoder configuration.

  • High mechanical load/friction issues.





Remedy:



  • Verify correct motor data.

  • Verify correct encoder settings including:

    • LF.27: Encoder Pulse Number

    • LE.28: Swap Encoder Channels (A/B setting)

    • LF.77: Encoder Pole position for PM Synchronous Motors.



  • Check for high mechanical load/issues (friction).


E.OS fault in KEB COMBIVERT F5 Drive
E.OS fault in KEB COMBIVERT F5 Drive indicates an Overspeed. This means the motor's speed exceeded the internal safety limit, potentially due to bad machine data parameters or a loss of load control.
Cause:


The inverter internal overspeed is dictated as 125% of the LF.20 Contract Speed. This level is fixed and cannot be adjusted.



Possible causes of an overspeed error include:

  • Incorrect setting of the Machine Data parameters LF.20-25: The Machine Data parameters are used as a scalar to convert a linear speed (e.g. ft/min) to a rotary speed (rpm) used by the inverter. If the machine data is not set correctly, the overspeed limit may be calculated too low when control modes which dictate the drive speed exceed this limit.

  • Lack of control: Maximum Torque limit or peak inverter current reached. 0.LF.36 Maximum Torque may be set too low (default = 150%; typical for high speed/full load operation = 200-250%).

  • Excessive current: Incorrect motor data, specifically the motor rated speed and frequency relationship for PM Synchronous Motors, or incorrect Encoder Pole Position (LF.77).

  • Speed gains set too high or low: For an unloaded PM Synchronous Motor, the default speed gains LF.31-33 may be too high, causing the machine to jerk quickly. If left too low for normal operation, the drive may not track the speed.

  • Modulation gain exceeds maximum: If the modulation grade in ru42. exceeds 100%, there may be a loss of speed control.

  • Sudden, excessive movement: Incorrect motor data or incorrect Encoder Pole Position for PM Synchronous Motors.





Remedy:



  • Check and verify Machine Data parameters LF.20-25.

  • Monitor the motor current to see if it reaches a current corresponding to the 0.LF.36 Maximum Torque or the drive Peak Current rating. Adjust 0.LF.36 if set too low.

  • Verify motor data, specifically the motor rated speed and frequency relationship for PM Synchronous Motors (see Section 5.6).

  • Verify and correct Encoder Pole Position (LF.77) for PM Synchronous Motors. Relearn Encoder Pole Position as needed (see Section 5.11).

  • Verify speed gains are appropriately configured. Adjust LF.31-33 if needed.

  • Ensure that the modulation grade in ru42. does not exceed 100%.


How to Clear & Reset KEB COMBIVERT F5 Drive Faults

  1. Keypad / Operator Reset: On the standard 5-digit LED digital operator, press the ENTER key to acknowledge and clear the error display. On the plain-text LCD operator, press the designated F4 (RESET) softkey once the underlying root cause has been rectified.
  2. Digital Input Reset (Terminal Strip X2A): Assign a digital input to the error reset function via parameter configuration (parameter group di). Apply a momentary +24 VDC pulse to the assigned terminal to clear the latch.
  3. COMBIVIS PC Diagnostic Software: Connect your PC to the drive’s diagnostic interface via an HSP5 or RS232/RS485 adapter cable, launch COMBIVIS 5 / 6, and trigger the “Error Reset” function in the drive management menu.
  4. Fieldbus Control Word: If connected to industrial automation networks (EtherCAT, CANopen, PROFIBUS, or PROFINET), execute a low-to-high transition (`0` to `1`) on Bit 7 (Fault Reset) within the drive control word (Sy.50).
  5. Mains Power Cycle: Switch off the main line supply. Wait until the display extinguishes completely and intermediate DC capacitors safely discharge (approx. 5 to 10 minutes) before powering the drive back up.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [++] and [–] (or [+PA] and [-PA]) before inspecting motor connections, braking resistor wiring, or touching motor power output terminals U, V, and W on the KEB COMBIVERT F5 inverter.