KEB Drives Fault Codes & Troubleshooting
Complete diagnostic database for 2 KEB drive series (COMBIVERT F5 & R6). Browse fault codes, error status, causes, and step-by-step fixes for industrial AC inverter, servo, and regenerative systems. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.
1 Inverter & Servo Series
1 Regenerative Unit Series
2 Total Series
KEB COMBIVERT Drive & Regeneration Systems
2 Models
COMBIVERT F5
→
Universal AC Frequency Inverter & Dynamic Servo Drive (Basic, Compact & Multi Variants)
COMBIVERT R6
→
Active Regenerative Braking & Mains Infeed Feedback Recuperation Unit
Most Common KEB Drive Fault Codes
Diagnostic Quick Reference| Display Code | Hex / Status | Fault Description | Common Root Cause |
|---|---|---|---|
| E.OC | 0x01 | Overcurrent Trip | Instantaneous peak current limit exceeded; phase-to-phase short on motor terminals U, V, W, jammed mechanical gearbox, or rapid acceleration ramp. |
| E.OP | 0x02 | Overpotential (Overvoltage) | Intermediate circuit DC bus exceeded maximum threshold; high regenerative energy returned during deceleration without dynamic braking resistor or active R6 unit. |
| E.UP | 0x03 | Underpotential (Undervoltage) | DC link voltage dropped below allowable operating limit; mains supply failure, severe line voltage sag, or blown upstream input protection fuse. |
| E.OH / E.dOH | 0x05 / 0x06 | Heatsink / Drive Overheat | Power module or internal enclosure temperature exceeded safety limit; clogged heatsink ventilation channels, internal cooling fan malfunction, or ambient >45°C. |
| E.OL | 0x07 | Drive Overload | Continuous operation exceeding 100% rated capacity according to thermal model; mechanical binding or undersized drive for continuous load profile. |
| E.OL2 | 0x08 | Motor Overload | Motor electronic thermal protection activated (I²t calculation); sustained low-speed high-torque operation without forced ventilation cooling fan. |
| E.EnC | 0x09 | Encoder / Feedback Error | Speed feedback signal missing, broken encoder cable, inverted channel connection (A/B), or resolver communication timeout. |
| E.buS | 0x0D | Fieldbus Watchdog Timeout | Cyclic communication interrupted across fieldbus interface (EtherCAT, CANopen, Profinet); damaged communication patch cable or master PLC cycle stop. |
How to Clear & Reset KEB Faults
- Keypad Reset: Press the ENTER / RESET key (or toggle the F/R key depending on operator module) on the front digital operator once the error root cause is resolved.
- Digital Input Terminal: Apply a 24VDC pulse to the digital input terminal configured for fault reset (e.g., configure parameter di.01–di.08 to option
Reseton terminal strip X2A). - COMBIVIS 5 / 6 Software: Connect via diagnostic serial/USB cable or Ethernet, open the diagnostic control panel inside KEB COMBIVIS, and click the “Error Reset” button.
- Main Power Disconnect Cycle: Turn off incoming 3-phase AC line power, wait until the internal DC bus voltage completely discharges below 50VDC (minimum 5 minutes), and re-energize the unit.
⚠️ High-Voltage Safety Warning:
Hazardous electrical voltages up to 900 VDC remain stored in the intermediate circuit DC bus capacitors after mains supply disconnection. Wait at least 5 minutes and verify with a calibrated digital multimeter across terminals (++) and (–) that the voltage is strictly below 50VDC before inspecting internal wiring or touching motor output terminals.