KEB COMBIVERT F5 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the KEB COMBIVERT F5 modular inverter and servo drive series. Search or filter through the complete fault code directory below.
Power Range
0.37 – 900 kW (0.5 – 1200 HP)
Supply Voltage
1-ph 230V / 3-ph 230V, 400V, 690V
Control Modes
V/Hz, SCL, ASCL & Closed-Loop FOC
Operator Interface
LED Keypad / LCD Operator / COMBIVIS
Complete KEB COMBIVERT F5 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E.OC, E.OP, E.dOH, or Overcurrent).
| Fault Code | Cause and Solution / Troubleshoot |
|---|---|
| E.OL2 fault in KEB COMBIVERT F5 Drive | E.OL2 fault in KEB COMBIVERT F5 Drive indicates a Low Speed Overload. This means the motor has drawn excessive current at a low frequency or standstill for too long, exceeding its thermal capacity. Cause: Excessive current at low speed (typically below 3Hz). Possible factors include:
Remedy:
|
| E.dOH fault in KEB COMBIVERT F5 Drive | E.dOH fault in KEB COMBIVERT F5 Drive indicates a Motor Overheat. This means the external PTC temperature sensor has tripped, signaling that the motor is running dangerously hot. Cause: If a motor PTC temperature sensor, relay, or KTY (special hardware required) is connected to terminals T1, T2 and the motor overheat function US.33 EdOH Function = On, then the relay opens when PTC resistance exceeds 1650 Ohms. Excessive motor heating causes may include:
Remedy:
|
| E.OH2 fault in KEB COMBIVERT F5 Drive | E.OH2 fault in KEB COMBIVERT F5 Drive indicates a Motor Protection error. This means the electronic motor overload protection was activated because the RMS motor current exceeded safe parameters. Cause: Excessive RMS motor current according to the LF.08 Electric Motor Protection overload curve, or if the LF09 Peak Motor Current Factor is exceeded for more than 3 seconds for PM Synchronous Motors.
Remedy:
|
| E.OC / EOC fault in KEB COMBIVERT F5 Drive | E.OC / EOC fault in KEB COMBIVERT F5 Drive indicates an Over Current. This means the inverter's output current spiked beyond the permissible peak limit or a ground fault occurred. Cause:
Remedy: The current and peak current may be viewed in LF.93 and LF.94. To reset the logged peak value, press enter. Systematic Isolation & Checks:
Note: Under normal operation, the drive limits the output current to the maximum torque in 0.LF36 (Maximum Output Current = LF.12 Motor Current × 0.LF.36 Maximum Torque / LF.17 Motor Torque). The drive also limits output current to the hardware current limit listed as Peak Current (30sec.) rating in the Technical Data tables (Sec. 2.1 and 2.2). |
| E.OP fault in KEB COMBIVERT F5 Drive | E.OP fault in KEB COMBIVERT F5 Drive indicates an Over Voltage. This means the DC bus voltage rose above the permissible limit, typically due to regenerative motor energy or line voltage spikes. Cause: Elevated DC bus voltage. Common sources include:
Remedy: The DC bus voltage LF.95 and the peak DC bus voltage LF.96 can be monitored.
|
| E.PU fault in KEB COMBIVERT F5 Drive | E.PU fault in KEB COMBIVERT F5 Drive indicates a Power Unit error. This means a general hardware malfunction occurred within the internal power circuit stages. Cause: Internal power circuit malfunction. Remedy: The inverter must be inspected and repaired by KEB or replaced. |
| E.PUCH fault in KEB COMBIVERT F5 Drive | E.PUCH fault in KEB COMBIVERT F5 Drive indicates the Power Unit Changed. This means the control card detected a new power stage, usually following a hardware replacement or modification. Cause: Control card change or hardware modification. Remedy: This error should automatically clear itself. |
| E.PUCI fault in KEB COMBIVERT F5 Drive | E.PUCI fault in KEB COMBIVERT F5 Drive indicates a Power Unit Invalid error. This means the drive's control card could not correctly identify the power circuit during initialization, often due to electrical noise or poor connection. Cause: Initialization recognition failure. This error could occur from electrical noise. Remedy:
|
| E.UP fault in KEB COMBIVERT F5 Drive | E.UP fault in KEB COMBIVERT F5 Drive indicates an Under Voltage. This means the internal DC bus voltage dropped below the minimum operating threshold, often caused by a phase loss or low input mains. Cause: DC bus voltage drop. Common sources include:
Remedy:
Note: A 460V drive can operate on a 230V, single phase power supply if programmed for UPS mode operation. |
| nE.OL2 message in KEB COMBIVERT F5 Drive | nE.OL2 message in KEB COMBIVERT F5 Drive indicates no Error Low Speed Overload. This means the previous low-speed overload condition has cleared and the drive is ready to be reset. Cause: Low speed overload has cleared. Remedy: The error is cleared and the drive can be reset. |
| nE.dOH message in KEB COMBIVERT F5 Drive | nE.dOH message in KEB COMBIVERT F5 Drive indicates no Error Motor Overheat. This means the motor temperature has dropped back to an acceptable level and the overheat fault can be reset. Cause: Motor temperature has dropped back to acceptable levels. Remedy: The motor overheat sensor is reset, and the Error Motor Overheat fault can be reset. |
| nE.OL message in KEB COMBIVERT F5 Drive | nE.OL message in KEB COMBIVERT F5 Drive indicates no Error Overload. This means the internal overload counter has returned to 0% and the drive can be safely reset. Cause: The overload counter has reached 0%. Remedy: Allowing the motor to cool down to 0% overload allows the error overload to be reset. |
| no_PU fault in KEB COMBIVERT F5 Drive | no_PU fault in KEB COMBIVERT F5 Drive indicates the Power Unit is Not Ready. This means the control card is powered up but cannot communicate with the power stage, often because main power is missing or a cable is loose. Cause: The Power Unit Not Ready message may occur due to:
Remedy:
|
| I_data fault in KEB COMBIVERT F5 Drive | I_data fault in KEB COMBIVERT F5 Drive indicates Invalid Data. This means a parameter value was entered that falls outside the permissible limits for that setting. Cause: Parameter is outside of the permissible limits. Remedy: Ensure the parameter entered is within the permitted range. |
| I_oPE fault in KEB COMBIVERT F5 Drive | I_oPE fault in KEB COMBIVERT F5 Drive indicates an Invalid Operation. This means an operation was attempted while the drive was in an incorrect state or had active inputs preventing the action. Cause: An operation was attempted in an incorrect state or while inputs are active. Remedy: Change the drive mode from Run to Stop. Check LF.82 input status to ensure no inputs are currently active. |
| EOH fault in KEB COMBIVERT F5 Drive | EOH fault in KEB COMBIVERT F5 Drive indicates an Overheat Power Module. This means the inverter's heatsink temperature rose above the safe operating limit due to poor ventilation or fan failure. Cause: The heatsink temperature can be viewed in ru.38. The overheat limit is 90 degrees Celsius for most drives (see Technical Data for units 175HP and larger). Under normal operation, the heatsink temperature should usually be below 65 degrees Celsius. Causes of inverter heatsink overheat include:
Remedy:
|
| EOL fault in KEB COMBIVERT F5 Drive | EOL fault in KEB COMBIVERT F5 Drive indicates an Overload. This means the drive experienced a time-dependent excessive current draw and will require a cooldown period before resetting. Cause: Excessive motor overload. Factors include:
Remedy:
|
| E.OS fault in KEB COMBIVERT F5 Drive | E.OS fault in KEB COMBIVERT F5 Drive indicates an Overspeed. This means the motor's speed exceeded the internal safety limit, potentially due to bad machine data parameters or a loss of load control. Cause: The inverter internal overspeed is dictated as 125% of the LF.20 Contract Speed. This level is fixed and cannot be adjusted. Possible causes of an overspeed error include:
Remedy:
|
How to Clear & Reset KEB COMBIVERT F5 Drive Faults
- Keypad / Operator Reset: On the standard 5-digit LED digital operator, press the ENTER key to acknowledge and clear the error display. On the plain-text LCD operator, press the designated F4 (RESET) softkey once the underlying root cause has been rectified.
- Digital Input Reset (Terminal Strip X2A): Assign a digital input to the error reset function via parameter configuration (parameter group
di). Apply a momentary +24 VDC pulse to the assigned terminal to clear the latch. - COMBIVIS PC Diagnostic Software: Connect your PC to the drive’s diagnostic interface via an HSP5 or RS232/RS485 adapter cable, launch COMBIVIS 5 / 6, and trigger the “Error Reset” function in the drive management menu.
- Fieldbus Control Word: If connected to industrial automation networks (EtherCAT, CANopen, PROFIBUS, or PROFINET), execute a low-to-high transition (`0` to `1`) on Bit 7 (Fault Reset) within the drive control word (
Sy.50). - Mains Power Cycle: Switch off the main line supply. Wait until the display extinguishes completely and intermediate DC capacitors safely discharge (approx. 5 to 10 minutes) before powering the drive back up.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [++] and [–] (or [+PA] and [-PA]) before inspecting motor connections, braking resistor wiring, or touching motor power output terminals U, V, and W on the KEB COMBIVERT F5 inverter.