KEB COMBIVERT R6 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the KEB COMBIVERT R6 power supply and regenerative energy series. Search or filter through the complete fault code directory below.
Power / Capacity Range
11 kW – 1,000 kVA (Modular/Cascading)
Supply Voltage
180–528V AC (3-Phase, 50/60 Hz)
Operating Modes
Central Supply & Line Regeneration
Operator Interface
Digital Operator Keypad / COMBIVIS Tool
Complete KEB COMBIVERT R6 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E.OC, E.OP, or Overcurrent).
| Status / Fault Code and Meaning | Cause and Solution / Remedy |
|---|---|
| regen active Status Message | Cause: Normal regeneration operation active. Remedy: Regen active (regeneration operation). No action required; status is informational. |
| base block Status Message | Cause: Base-block time active. Unit is temporarily blocked from operation. This status precedes all error states. Remedy: Informational status. Wait for the block period to complete automatically. |
| no operation Status Message | Cause: The enable input is not activated. Output modulation is switched off. Remedy: Activate the enable input to resume operations. |
| net off Status Message | Cause: Line power failure. Remedy: Regen operation mode is possible; check line supply conditions if unexpected. |
| standby Status Message | Cause: The unit is enabled but in stand-by operation (motoric operation). Remedy: Informational status; system is ready for operation. |
| SYn Status Message | Cause: Phase synchronization mode. Remedy: The unit is checking the connection and phase angle of the line voltage. |
| fault reset level reached Status Message | Cause: Fault reset level reached. Remedy: A fault reset operation is now permitted. |
| 9: ERROR drive overheat Error Message | Cause: Over temperature commutation choke; temperature sensing on the commutation choke indicates the choke is too hot and the overheat delay timer has run out. Remedy: Allow the commutation choke to cool down. Check ventilation and structural choke layout. |
| 31: ERROR External Fault Error Message | Cause: External Fault. The R6 has been programmed to trigger this error for assistance in identifying high regenerative/supply current and line voltage sag (refer to CP.19 settings and section 6.2 for troubleshooting). Remedy: The error can be triggered by an external device through one of the digital inputs, or manually by setting a temporary jumper across X2A.15-X2A.17. Refer to CP.21 - CP.28 for use with the fault log. |
| 40: ERROR line frequency Error Message | Cause: Main Line Frequency out of tolerance. Remedy: Verify the stability and frequency parameters of the input supply. |
| 15: ERROR load shunt fault Error Message | Cause: Load-shunt relay has not picked up; occurs for a short time during the switch-on phase. Remedy: The relay will automatically reset immediately. If the error remains, inspect the load-shunt relay. |
| 3: ERROR net Error Message | Cause: Line power failure: one or more phases are missing. Remedy: Verify the line phases, fuses, and connections. |
| 36: no ERROR overheat Error Message | Cause: Over-temperature condition is no longer present. Remedy: The E.OH overheat error can now be reset. |
| 17: no ERROR overload Error Message | Cause: The cooling period after E.OL is over. Remedy: The overload error can now be reset. |
| 4: ERROR overcurrent Error Message | Cause: Over current; output current too high or ground fault. Remedy: Check the motor, cables, and power connections for ground faults or short circuits. |
| 8: ERROR overheat pow. mod. Error Message | Cause: Over temperature; overheating of the heat sink. Remedy: Check cooling conditions, heatsink fans, and air filters (see "technical data"). |
| 6: ERROR overheat internal Error Message | Cause: R6 Unit interior temperature is too high (interior temperature > 95°C). Remedy: Improve ventilation of the enclosure or cabinet housing the R6 unit. |
| 16: ERROR overload Error Message | Cause: Over Load; the actual load was greater than 105% and the overload timer timed out. Remedy: Reduce the load on the motor and drive. |
| 1: ERROR: over voltage Error Message | Cause: Over Voltage; DC bus voltage is too high (> 900VDC). Remedy: Ensure braking resistor or regen unit is properly operating and connected. |
| 49: ERROR pow. unit code inv. Error Message | Cause: Power unit identification is invalid. Remedy: Verify power unit parameters and code compatibility. |
| 50: ERROR pow. unit changed Error Message | Cause: Power unit change detected. Remedy: Refer to parameter CP.31 to acknowledge and verify power unit configuration. |
| 59: synchronization error Error Message | Cause: Synchronization error; connection of line phasing is not correct. Remedy: Check line phasing and connection logic. |
| 2: ERROR under voltage Error Message | Cause: Under voltage; DC bus voltage is too low. Remedy: Verify incoming mains supply voltage levels. |
| 12: ERROR power unit Error Message | Cause: General power circuit error. Remedy: Inspect power unit power stage and connections. |
| E.Syn Synchronization error | Cause: Line frequency calculated incorrectly. Remedy: If the value in CP.02 is negative, swap L1.1 and L2.1 at the commutation choke so that CP.02 is positive. |
| E.nEt Error net | Cause: Mains connection or line loss issue. Common factors:
Remedy: Refer to Sections 4.4.2 to determine the corresponding wiring of the regen unit (Wiring Scheme A). Verify three-phase supply. Refer to Noise/EMI in Section 6.2.2. |
| E.OC Error overcurrent | Cause: Elevated output current levels. Common sources:
Remedy: Check for any loose or missing power connections. Check for similar errors on the (F5) Elevator Drive indicating a ground fault, short, or excessive current. This may indicate the cause of the fault is occurring from the end of the drive, motor contactor, or motor. Refer to Noise/EMI in Section 6.2.2. Check to see if the utilization in CP.6 is high. Refer to High Regenerative/Supply Current in Section 6.2.2. Verify sizing with controller manufacturer. |
| E.FnEt Error line frequency | Cause: Main line frequency variations.
Remedy: Monitor Main Line Frequency at CP.2. Output frequency from generator may be too high/low and may change as various other loads come on/offline. Refer to Noise/EMI in Section 6.2.2. |
| E.PuCH Error power unit changed | Cause: The voltage class of the line supply has changed since last power on and must be confirmed (cycling power will not clear). Remedy: Re-enter the value in CP.31 to clear the fault. The value displayed cannot be changed and is an arbitrary ID number and NOT a voltage setting. |
| E.OL Error overload | Cause: Supply or regenerative current too high. Remedy: Check to see if the utilization in CP.6 is high. Refer to High Regenerative/Supply Current in Section 6.2.2. Verify sizing with the controller manufacturer. |
| E.LSF Error DC Bus charge fault | Cause: If the error does not reset itself after power up and the fault remains, the following causes may be applicable:
Remedy: The unit must be serviced. Verify the line supply or transformer output supply and ensure there is no excessive sags or brown-out conditions. |
| E.PU Error power unit | Cause: Error on the power stage. Remedy: General error on the power stage. Check grounding of the transformer. If the error is always active, the unit must be sent in for evaluation. If intermittent, it may indicate excessive line sag conditions. |
| E.UP Error undervoltage | Cause: DC bus level is too low. Remedy: Likely indicates poor power quality. Verify line input voltage. Sagging voltage or loss of phase could cause E.UP error. Check all grounding including X0 of transformer. |
| E.OP Error Overpotential (faults on F5 Elevator Drive) | Cause: Regen unit is unable to regen back to the line; CP.1 status is not in 'regen' status during generating operation.
Remedy: Verify enable input at X2A.12. When active under normal operation, the CP.1 status should be either 'Stby' or 'rEgEn'. Verify di.00 setting according to input type (PNP: inputs must be +24VDC to be active; NPN: inputs must be at 0VDC to be active). CP.1 status displays fault message or if the fault message has been cleared from the screen by pressing ENTER on the operator keypad, a flashing red indicator LED on the keypad and R6 indicates an active fault remains. Reset (2AX.13) or resolve the cause of the fault. If the fault has been automatically reset, the last fault can be viewed in the fault log, CP.21. If it is unclear whether a fault actually occurred, refer to the note under CP.21...28 to force a specific fault in order to determine if a new fault is occurring. The DC bus fuse(s), internal to the R6, can be checked visibly whether they are open and replaced as needed. Before checking, ensure all safety measures necessary including powering down the unit from the mains disconnect and locking it out and allowing the DC bus to fully dissipate and verifying 0VDC across the DC bus terminals ++, - -. |
| E.EF External Fault | Cause:
Remedy: Refer to section 6.2.2 regarding high regenerative / supply current and excessive line voltage sag. |
| CP.0 Password input | Cause: Restricts parameter editing to authorized personnel. Remedy: Enter password to unlock level access. |
| CP.1 Status display | Cause: Diagnostics feedback stage. Remedy: Read current operating status or active fault states. |
| CP.2 Main Line Frequency | Cause: Measures main line frequency of incoming AC power. Remedy: Diagnostic only; check for source frequency instability. |
| CP.3 AC-Phase current L1 | Cause: Measures current draw on phase L1. Remedy: Diagnostic only; monitor for phase current imbalances. |
| CP.4 AC-Phase current L2 | Cause: Measures current draw on phase L2. Remedy: Diagnostic only; monitor for phase current imbalances. |
| CP.5 AC-Phase current L3 | Cause: Measures current draw on phase L3. Remedy: Diagnostic only; monitor for phase current imbalances. |
| CP.6 Actual Load | Cause: Real-time calculated load on the drive system. Remedy: Diagnostic parameter; check if load regularly exceeds 100%. |
| CP.7 Actual Load / peak value | Cause: Peak load captured during the current run cycle. Remedy: If peak utilization equals or exceeds 160%, evaluate sizing parameters. |
| CP.8 DC output current | Cause: Direct current output reading. Remedy: Diagnostic only. |
| CP.9 Actual DC voltage | Cause: Real-time DC bus voltage level. Remedy: Check if this falls below undervoltage limits or spikes above overvoltage thresholds. |
| CP.10 DC voltage / peak value | Cause: Highest recorded DC bus voltage level during run. Remedy: Useful for diagnosing overvoltage spike events. |
| CP.11 Heat sink temperature | Cause: Real-time heatsink temperature monitoring. Remedy: Temperatures should typically remain below 65°C under normal load. |
| CP.12 Over load counter | Cause: Tracks time-integrated thermal overload status. Remedy: Let the drive stand idle or cool until this returns to 0% to reset E.OL. |
| CP.13 Active power | Cause: Active power measurement output. Remedy: Diagnostic only. |
| CP.17 Apparent power / Line input | Cause: Apparent power draw measured from mains input. Remedy: Diagnostic only. |
| CP.18 Analog output 1 / amplification factor | Cause: Configures analog output scaling. Remedy: Adjust scaling factor to match external monitoring devices. |
| CP.19 DC bus switching level | Cause: Configurable threshold level for DC bus switching. Remedy: Refer to manual application notes before modifying. |
| CP.20 Auto error reset counter | Cause: Limits number of consecutive automatic fault resets. Remedy: Adjust value to control automatic retry attempts. |
| CP.21 Last Error | Cause: Registers the most recently occurred fault code. Remedy: Check value during diagnostics. |
| CP.22 Last Error 1 | Cause: Registers historical fault code (1 fault ago). Remedy: Check value during diagnostics. |
| CP.23 Last Error 2 | Cause: Registers historical fault code (2 faults ago). Remedy: Check value during diagnostics. |
| CP.24 Last Error 3 | Cause: Registers historical fault code (3 faults ago). Remedy: Check value during diagnostics. |
| CP.25 Last Error 4 | Cause: Registers historical fault code (4 faults ago). Remedy: Check value during diagnostics. |
| CP.26 Last Error 5 | Cause: Registers historical fault code (5 faults ago). Remedy: Check value during diagnostics. |
| CP.27 Last Error 6 | Cause: Registers historical fault code (6 faults ago). Remedy: Check value during diagnostics. |
| CP.28 Last Error 7 | Cause: Registers historical fault code (7 faults ago). Remedy: Check value during diagnostics. |
| CP.29 Software version | Cause: Control unit firmware version identification. Remedy: Useful for firmware compatibility audits. |
| CP.30 Software date code | Cause: Compilation date of the loaded firmware. Remedy: Informational only. |
| CP.31 Power part ID code | Cause: Configures or matches power stage hardware voltage class. Remedy: Re-enter correct ID parameter to clear E.PuCH faults after card replacement. |
| CP.32 Pulse off level | Cause: Modulation shutdown voltage threshold configuration. Remedy: Set according to local grid and application requirements. |
| CP.33 Operating mode | Cause: Determines control scheme operating mode. Remedy: Select appropriate open/closed loop control profile. |
| CP.34 Input Type | Cause: Input hardware selection (e.g. PNP vs. NPN). Remedy: Configure to match external sensor wiring logic. |
| CP.35 Kp Harmonic Filter | Cause: Proportional gain coefficient for the active harmonic filter. Remedy: Tuning parameter; adjust to mitigate line resonance. |
| CP.36 Ki Harmonic Filter | Cause: Integral gain coefficient for the active harmonic filter. Remedy: Tuning parameter; adjust to stabilize grid synchronization. |
How to Clear & Reset KEB COMBIVERT R6 Drive Faults
- Keypad Operator Reset: Press the ENTER key on the front digital operator keypad when an error code is displayed. This clears the trip message if the underlying fault condition is resolved.
- Terminal Strip Reset: Pulse a +24V DC signal to the programmed reset input terminal on control strip X2A (terminal X2A.13). Note: ensure correct logic polarity (PNP vs NPN) via parameter di.00.
- KEB COMBIVIS Software: Connect a PC via serial interface/USB diagnostic cable to the diagnostic port, launch KEB COMBIVIS 5 or COMBIVIS 6, navigate to drive status, and trigger the software Fault Reset command.
- Auto Error Reset Counter (CP.20): Review parameter CP.20 (General Fault Reset). If set between 1 and 10, the unit will attempt automatic reset cycles for transient line glitches up to the specified limit per hour.
- Complete Mains Power Cycle: Switch off the primary 3-phase AC line disconnect. Wait at least 5 minutes for the intermediate DC link discharge circuit to completely de-energize before reconnecting power.
⚠️ High-Voltage Electrical Safety Warning:
The KEB COMBIVERT R6 regenerative unit connects directly to active high-capacity DC bus rails. Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [++] and [–] before touching power terminals, inspecting internal DC fuses, or servicing commutation chokes.