Lenze 9300 Servo Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip error causes, and step-by-step troubleshooting procedures for the Lenze 9300 Servo inverter series. Search or filter through the complete diagnostic directory below.

High-Performance Servo Inverter Power: 0.37 to 75 kW (0.5 to 100 HP) Integrated Motion & Positioning
Power Range 0.37 – 75 kW (0.5 – 100 HP)
Supply Voltage 3~ 320–528V AC (400/500V)
Control Modes Field-Oriented Servo & Vector
Operator Interface Keypad XT / Global Drive Control (GDC)

Complete Lenze 9300 Servo Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OU, LU, Sd2, or Overcurrent).

Fault Code and MeaningCause and Remedy
0011 (OC1)
Short circuit of motor cable

Cause: Short circuit or Excessive capacitive charging current in the motor cable.



Remedy:

  • Search for cause of short circuit.

  • Check motor cable.

  • Use motor cable which is shorter or of lower capacitance.


0012 (OC2)
Motor cable earth fault

Cause: One of the motor phases has earth contact.



Remedy:

  • Search for cause of short circuit.

  • Check motor cable.


0015 (OC5)
I x t overload

Cause: Frequent and too long acceleration with overcurrent or Continuous overload with Imotor > 1.05 x Irx.



Remedy:

  • Check drive dimensioning.


0016 (OC6)
I²xt overload

Cause: Frequent and too long acceleration processes with motor overcurrent or Permanent motor overload with Imotor > Irmotor.



Remedy:

  • Check drive dimensioning.


x018 (OC8)
I²xt overload advance warning

Cause: Frequent and too long acceleration processes with motor overcurrent or Permanent motor overload with Imotor > Irmotor.



Remedy:

  • Check drive dimensioning.


1020 (OU)
Overvoltage in DC bus

Cause: Braking energy is too high (DC-bus voltage is higher than set in C0173).



Remedy:

  • Use braking unit or regenerative module.

  • Check dimensioning of the brake resistance.


1030 (LU)
Undervoltage in the DC bus

Cause: DC bus voltage is lower than specified in C0173.



Remedy:

  • Check mains voltage.

  • Check supply cable.


x032 (LP1)
Motor phase failure

Cause: A current-carrying motor phase has failed or The current limit value is set too low.



Remedy:

  • Check motor.

  • Check motor cable.

  • Switch off monitoring (C0597 = 3).

  • Set higher current limit value via C0599.


0050 (OH)
Heatsink temperature > +90 °C

Cause: Ambient temperature Tu > +40 °C or > +50 °C; Heatsink is very dirty; or Wrong mounting position.



Remedy:

  • Allow module to cool and ensure better ventilation.

  • Check ambient temperature in the control cabinet.

  • Clean heatsink.

  • Change mounting position.


x053 (OH3)
Motor temperature > +150 °C threshold

Cause: Motor is thermally overloaded due to impermissible continuous current, frequent/long acceleration, or no PTC/temperature contact connected.



Remedy:

  • Check drive dimensioning.

  • Switch off monitoring (C0583 = 3).

  • Correct wiring.


x054 (OH4)
Heatsink temperature > C0122

Cause: Ambient temperature high, Heatsink dirty, Wrong mounting position, or The value specified under C0122 is set too low.



Remedy:

  • Allow module to cool and ensure better ventilation.

  • Check ambient temperature in the control cabinet.

  • Switch off monitoring (C0582 = 3).

  • Clean heatsink.

  • Change mounting position.

  • Enter a higher value under C0122.


x057 (OH7)
Motor temperature > C0121

Cause: Motor is thermally overloaded, No PTC connected, or value specified under C0121 is set too low.



Remedy:

  • Check drive dimensioning.

  • Switch off monitoring (C0584 = 3).

  • Correct wiring.

  • Enter a higher value in C0121.


x058 (OH8)
Motor temperature via inputs T1 and T2 is too high

Cause: Motor is thermally overloaded or Terminals T1 and T2 are not connected.



Remedy:

  • Check drive dimensioning.

  • Switch off monitoring (C0585 = 3).

  • Connect PTC/temperature contact.


x061 (CE0)
Automation interface (AIF) communication error

Cause: Faulty transfer of control commands via AIF.



Remedy:

  • Plug in the communication module/keypad XT firmly, screw down if necessary.

  • Switch off monitoring (C0126 = 3).


x062 (CE1)
Communication error on CAN1_IN

Cause: CAN1_IN object receives faulty data or communication is interrupted.



Remedy:

  • Check wiring at X4.

  • Check sender.

  • Increase monitoring time under C0357/1, if necessary.

  • Switch off monitoring (C0591 = 3).


x063 (CE2)
Communication error on CAN2_IN

Cause: CAN2_IN object receives faulty data or communication is interrupted.



Remedy:

  • Check wiring at X4.

  • Check sender.

  • Increase monitoring time under C0357/2, if necessary.

  • Switch off monitoring (C0592 = 3).


x064 (CE3)
Communication error on CAN3_IN

Cause: CAN3_IN object receives faulty data or communication is interrupted.



Remedy:

  • Check wiring at X4.

  • Check sender.

  • Increase monitoring time under C0357/3, if necessary.

  • Switch off monitoring (C0593 = 3).


x065 (CE4)
BUS-OFF state of system bus (CAN)

Cause: The controller has received too many faulty telegrams via the system bus (CAN) and has disconnected from the bus.



Remedy:

  • Check wiring at X4: Is the bus correctly terminated?

  • Check shield connection of the cables.

  • Check PE connection.

  • Check bus load, reduce the baud rate if necessary. (Observe cable length!)

  • Switch off the monitoring (C0595 = 3).


0071 (CCr)
System failure

Cause: Strong interference injection on the control cables or Ground/earth loops in the wiring.



Remedy:

  • Screen control cables.

  • Check wiring.

  • Check PE connection.

  • After troubleshooting: Deenergise the device completely (disconnect 24 V supply, discharge DC bus)!


0072 (PR1)
Checksum error in parameter set 1

Cause: Fault when loading a parameter set; Interruption while transmitting; or Stored parameters incompatible with loaded software.



Remedy:

  • Set the required parameters and store them under C0003 = 1.

  • As to PLC devices, check the use of pointers.

  • Store the parameter set under C0003 = 1 first to allow for a faults reset.


0074 (PEr)
Program error

Cause: Error in the program flow.



Remedy:

  • Send the parameter set (on floppy disk/CD-ROM) with a detailed description of the problem to Lenze.

  • After troubleshooting: Deenergise the device completely!


0075 (PR0)
Error in parameter set

Cause: The operating system software has been updated.



Remedy:

  • Storage of the Lenze setting C0003 = 1.

  • After troubleshooting: Deenergise the device completely!


0079 (PI)
Fault during parameter initialisation

Cause: Error detected during parameter set transfer between two devices or Parameter set does not match the controller (e.g. power rating mismatch).



Remedy:

  • Correct parameter set.

  • Send parameter set with description to Lenze.


x082 (Sd2)
Resolver error at X7

Cause: Resolver cable interrupted.



Remedy:

  • Check cable for open circuit.

  • Check resolver.

  • Switch off the monitoring (C0586 = 3).


x083 (Sd3)
Encoder error at X9

Cause: Cable interrupted or Pin X9/8 not connected.



Remedy:

  • Check cable for open circuit.

  • Apply 5 V to pin X9/8 or switch off monitoring (C0587 = 3).


x085 (Sd5)
Encoder error at X6/1 and X6/2

Cause: Current signal at X6/1 X6/2 < 2mA.



Remedy:

  • Check cable for open circuit.

  • Check current signal encoder.

  • Switch off monitoring (C0598 = 3).


x086 (Sd6)
Motor temperature sensor error (X7 or X8)

Cause: Encoder for detecting the motor temperature at X7 or X8 indicates undefined values.



Remedy:

  • Check cable for firm connection.

  • Switch off the monitoring (C0594 = 3).


x087 (Sd7)

Initialisation or Communication error of absolute value encoder at X8

Cause: The absolute value encoder must be initialised, has a defect, or is not sending data. A rotor position adjustment could not be completed.


Remedy:

  • Save parameter set, completely deenergise the device, and switch it on again.

  • Make sure the cable at X8 is tightened properly and check for open circuits.

  • Check absolute value encoder for correct function.

  • Set voltage supply via C0421 to 8.0 V.

  • If no Stegmann encoder is connected, check configuration.

  • Repeat rotor position adjustment (See 6.8-1).

  • Note: After an Sd7 fault, rotor position adjustment must be repeated to prevent uncontrolled movements.


x088 (Sd8)

SinCos encoder at X8 error

Cause: SinCos encoder sends inconsistent data (tracks damaged), interference level on cable is too high, or open circuit detected.


Remedy:

  • Replace SinCos encoder if tracks are damaged.

  • Check correct shield connection of encoder cable.

  • Decelerate actuation of fault message via filter time constant (C0559 for ECSx, C0575 for 9300).

  • Check cable for wire breakage.

  • Connect correct SinCos encoder (Stegmann).

  • Set supply voltage correctly in C0421.


x089 (PL)

Error during rotor position adjustment

Cause: The rotor position adjustment was cancelled, or an error (Sd7 or Sd8) occurred during adjustment.


Remedy:

  • Repeat rotor position adjustment (See 6.8-1).

  • Note: Do not commission without successfully executed rotor position adjustment.


x091 (EEr)

External monitoring triggered via DCTRL

Cause: A digital signal assigned to the TRIP-SET function has been activated.


Remedy:

  • Check external encoder.

  • Switch off the monitoring (Set C0581 = 3).


0105 (H05)

Internal fault (memory)

Cause: Internal memory fault.


Remedy:

  • Contact Lenze.


0107 (H07)

Internal fault (power stage)

Cause: During initialisation, an incorrect power stage was detected.


Remedy:

  • Contact Lenze.


x110 (H10)

Heatsink temperature sensor error

Cause: Sensor for detecting heatsink temperature indicates undefined values.


Remedy:

  • Contact Lenze.

  • Switch off the monitoring (Set C0588 = 3).


x111 (H11)

Temperature sensor error (Internal)

Cause: Sensor for detecting internal temperature indicates undefined values.


Remedy:

  • Contact Lenze.

  • Switch off the monitoring (Set C0588 = 3).


x153 (P03)

Following error

Cause: Angle difference between set and actual position is larger than the limit (C0255), or drive cannot follow digital frequency.


Remedy:

  • Increase following error limit under C0255.

  • Switch off the monitoring (Set C0589 = 3).

  • Check drive dimensioning.


x163 (P13)

Angle overrun

Cause: Phase controller limit reached or drive cannot follow the digital frequency (Imax limit).


Remedy:

  • Enable drive.

  • Check drive dimensioning.


x166 (P16)

Faulty transfer of system bus (CAN) sync telegram

Cause: Sync telegram from master (PLC) is out of sync, not received, or controller enabled too fast.


Remedy:

  • Set "sync cycle" to transmission cycle of master under C1121.

  • Check communication channel, baud rate, and controller address.

  • Delay the controller enable (depends on time interval between sync telegrams).

  • Check C0362 (displays time interval). If C0362 = 0, communication is interrupted.


x169 (P19)

Input values at X9 are limited

Cause: The function block DFIN limits the input values causing loss of increments.


Remedy:

  • Reduce the frequency on the digital frequency connection.

  • Check settings for slave (C0425) and master (C0030). These must be identical.


x190 (nErr)

Speed control error

Cause: Speed out of tolerance margin (C0576). Active load too high (e.g. hoists) or mechanical blockades.


Remedy:

  • Check drive dimensioning.

  • Check for mechanical blockades on load side.


x200 (NMAX)

Maximum system speed exceeded

Cause: Maximum system speed (C0596) exceeded. Active load too high or torque excessively limited.


Remedy:

  • Check drive dimensioning.

  • Increase torque limit if necessary.

  • Switch off monitoring (Set C0607 = 3).


How to Clear & Reset Lenze 9300 Servo Drive Faults

  1. Keypad XT Reset: Press the red STOP / RESET key on the front-mounted Keypad XT (EMZ9371BC). Ensure terminal 28 (controller enable / RFR) is open to prevent immediate unexpected re-acceleration.
  2. Controller Enable / Digital Input Reset: Deactivate and reactivate terminal 28 (CINH / RFR) with a LOW-to-HIGH transition, or pulse the digital input linked to the function block TRIP-RESET (e.g. terminal E1–E4).
  3. Global Drive Control (GDC) PC Tool: Connect your PC via the LECOM interface (RS232/485) or system bus (CAN), navigate to the Diagnostics window, and select “Fault Reset” (TRIP-RESET) or write C0043 = 0.
  4. Fieldbus / CANopen Control Word: Write Bit 7 (TRIP-RESET) from 0 to 1 in the control word via the plug-in communication module (CAN, PROFIBUS DP, INTERBUS, or DeviceNet).
  5. Power Cycle: Disconnect the incoming 3-phase AC mains supply, wait at least 3 to 5 minutes until all front-panel LEDs turn off and DC bus capacitors fully discharge, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+UG] and [-UG] before inspecting motor power connections, resolver/encoder feedback cables, or touching terminals U, V, and W on the Lenze 9300 Servo drive.