Lenze Drives Fault Codes & Troubleshooting
Complete diagnostic database for 24 Lenze drive series. Browse fault codes, trip errors, causes, and step-by-step fixes for industrial AC variable speed inverters and high-performance servo motion amplifiers. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.
Lenze AC Drives & Inverters
16 ModelsDecentralized IP65 Motor-Mounted Frequency Inverter for Distributed Automation
Modular Classic Vector Frequency Inverter with Plug-In Function Modules
Compact Entry-Level Inverter for Basic Controlled Motion & Conveyor Systems
Universal Frequency Inverter with Integrated Logic Control & Point-to-Point Positioning
Heavy-Duty Vector Control Inverter for Complex Production & Material Web Handling
Classic Compact Micro Inverter for Low-Power Conveyors & Packaging Machines
Robust General-Purpose Frequency Converter for Centrifugal Pumps & Blowers
Compact Sub-Micro Frequency Inverter with Quick Parameter Memory Technology
DIN-Rail Mounted Sub-Compact AC Drive for Fractional Horsepower Motor Regulation
Sub-Micro Drive Featuring EPM (Electronic Programmable Module) Chip Architecture
Dynamic Sensorless Flux Vector Inverter Available in NEMA 1 (IP31) & NEMA 4X (IP65)
Cost-Effective Micro Drive with Simple Dial Operation & Fast EPM Programming
Slim Booksize Space-Saving Inverter (0.25 to 15 kW) for Cabinet Machine Integration
Versatile Industrial Inverter Supporting Multi-Fieldbus, Integrated STO & Vector Control
Rugged Decentralized IP66 Motor-Mounted Inverter with IO-Link & Energy Regeneration
High IP-Protection (IP66) Wall-Mount Inverter for Extreme Wet & Dusty Factory Environments
Lenze Servo Drives & Motion Systems
8 ModelsClassic High-Dynamic Motion Servo Amplifier for Coordinated Multi-Axis Machinery
Position-Controlled Dynamic Servo Controller with Integrated Digital Positioning Profiles
High-Precision Servo Inverter with Integrated Motion Profiling & High-Resolution Resolver Support
Modular Servo System Architecture with Cam Profiler & Electronic Gearbox Functionality
Advanced Multi-Axis Servo System with Built-in Comprehensive Motion Control & Safety
Centralized Multi-Axis EtherCAT Servo System with Single & Double Axis Drive Modules
High-Performance Central Cabinet Servo Drive Supporting Real-Time Multi-Encoder Feedback
Flagship Smart Servo Controller Combining Motion Controller, Servo Drive & FAST Applications
Most Common Lenze Drive Fault Codes
Diagnostic Quick Reference| Fault Code | Hex / CANopen | Fault Description | Common Root Cause |
|---|---|---|---|
| OC1 / OC2 | 0x2310 | Short Circuit / Overcurrent | Peak instantaneous motor current exceeded; phase-to-phase short on U, V, W, mechanical jam, or damaged motor windings. |
| OU | 0x3210 | DC Bus Overvoltage | DC link voltage exceeded upper trip threshold; rapid deceleration without braking resistor or regenerative overhauling load. |
| LU | 0x3220 | DC Bus Undervoltage | DC link voltage dropped below allowable limit; mains power blackout, utility phase dip, or blown line protection fuse. |
| OH / OH1 | 0x4310 | Heatsink Over-Temperature | Internal power module temperature exceeded safety limits; clogged heatsink fins, cooling fan failure, or high ambient (>50°C). |
| OC6 | 0x2330 | Ground / Earth Fault | Current leakage detected from motor output phases to protective earth (PE); degraded cable jacket or damp motor terminals. |
| CE0 / CE1 | 0x8100 | Communication Error | Fieldbus watchdog timeout (CANopen, EtherCAT, PROFINET); severed communication cable, bus noise, or master PLC cycle stop. |
| OL | 0x7122 | Motor Thermal Overload (I²t) | Sustained operation above continuous rated Full Load Amps (FLA); mechanical binding or inadequate forced motor cooling. |
How to Clear & Reset Lenze Faults
- Keypad Reset: Press the STOP / RESET key directly on the plug-in keypad (Keypad XT or i500 keypad module) once the fault cause has been removed.
- Digital Input Terminal: Apply a 24VDC pulse to the digital input configured for error reset (e.g., parameter 0x2631:004 set to
Reset Erroron i500 series, or parameter C0410 on 8200/9300 series). - EASY Starter / Engineer Software: Connect via USB diagnostic adapter or Ethernet, navigate to the diagnostic tab inside Lenze EASY Starter or Global Drive Control (GDC), and click “Reset Fault”.
- Mains Power Cycle: Disconnect the incoming 3-phase AC line supply, wait until all diagnostic LEDs turn completely off (minimum 5 minutes), and reclose the circuit breaker.