Lenze i550 Cabinet Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze i550 Cabinet frequency inverter series. Search or filter through the complete fault code directory below.

Scalable Modular Inverter Power: 0.25 to 110 kW (0.33 to 150 HP) Integrated Safe Torque Off (STO SIL 3 / PL e)
Power Range 0.25 – 110 kW (0.33 – 150 HP)
Supply Voltage 1-Ph 120/230V | 3-Ph 230/400/480V
Control Modes Sensorless Vector, V/f, & SLPSM
Operator Interface Keypad / USB / WLAN Module

Complete Lenze i550 Cabinet Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type 0x2310, 0x3210, 0x4210, or Overcurrent).

Fault Code and MeaningCause and Remedy
8784 0x2250

CiA: Continuous over current (internal)

Cause:

  • Continuous overcurrent on the inverter/motor side.

  • Overcurrent at the brake chopper (brake transistor).

  • DC bus relay has not been closed due to a malfunction.





Remedy:

  • Check motor and wiring for short circuits.

  • Check brake resistor and wiring.

  • Check motor switching.

  • Check settings of the motor data.


8992 0x2320

Short circuit or earth leakage at the motor end

Cause:

  • Short circuit/earth fault of motor cable.

  • Capacitive charging current of the motor cable too high.





Remedy:

  • Check motor cable.

  • Check length of the motor cable.

  • Use shorter or lower-capacitance motor cable.


9024 0x2340

Short circuit at the motor end

Cause:

Short circuit of motor cable.



Remedy:

  • Check motor cable for short circuit.


9040 0x2350

CiA: i²xt overload (thermal state)

Cause:

Motor thermally overloaded, e. g. by an impermissible continuous current or by frequent or too long acceleration processes.



Remedy:

  • Check drive sizing.

  • Check machine/driven mechanics for excessive load.

  • Check settings of the motor data.

  • Reduce values for slip compensation and oscillation damping.


9090 0x2382

Fault - Device utilization (ixt) too high

Cause:

Device utilisation (ixt) too high by frequent and too long acceleration processes.



Remedy:

  • Check drive sizing.

  • Reduce the maximum current of the inverter.

  • In case of high mass inertias, reduce maximum current of the inverter to 150 %.


9091 0x2383

Warning - Device utilization (ixt) too high

Cause:

Device utilisation (ixt) too high by frequent and too long acceleration processes.



Remedy:

  • Check drive dimensioning.


9095 0x2387

Clamp responded too often

Cause:

Maximum current of the axis has been reached too often in succession.



Remedy:

  • Select a flatter speed ramp.

  • Reduce the load.

  • Set Imax controller more dynamically.


9096 0x2388

SL-PSM stall detection active

Cause:

Overload of the motor with sensorless control for synchronous motors (SL-PSM).



Remedy:

  • Reduce load at the axis.

  • Check settings of the SL-PSM parameters.


9098 0x238A

Maximum current reached

Cause:

The actual current is equal to or higher than the max. current.



Remedy:

  • Reduce the load on the motor or change the settings for the maximum current.


12576 0x3120

Mains phase fault

Cause:

Mains phase failure.



Remedy:

  • Check wiring of the mains connection.

  • Check fuses.


12672 0x3180

UPS operation active

Cause:

Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided.



Remedy:

  • Switch back to operation with regular mains voltage.


12816 0x3210

Fault - DC bus overvoltage

Cause:

DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage.



Remedy:

  • Reduce dynamic performance of the load profile.

  • Check mains voltage.

  • Check settings for brake energy management.

  • Connect brake resistor to the power unit and activate the integrated brake chopper.


12817 0x3211

DC bus overvoltage warning

Cause:

DC-bus voltage has exceeded the warning threshold for overvoltage.



Remedy:

  • Reduce dynamic performance of the load profile.

  • Check mains voltage.

  • Check settings for brake energy management.

  • Connect brake resistor to the power unit and activate the integrated brake chopper.


12832 0x3220

Fault - DC bus undervoltage

Cause:

DC-bus voltage has fallen below the error threshold for undervoltage.



Remedy:

  • Check mains voltage.

  • Check DC-bus voltage.

  • Check mains settings.

  • Check fuses.


12833 0x3221

DC bus undervoltage warning

Cause:

DC-bus voltage has fallen below the warning threshold for undervoltage.



Remedy:

  • Check mains voltage.

  • Check DC-bus voltage.

  • Check mains settings.

  • Check fuses.


12834 0x3222

DC-bus voltage too low for power up

Cause:

The input voltage is too low to switch on the inverter.



Remedy:

  • Check mains voltage.

  • Check mains settings.

  • Check fuses.


16912 0x4210

Fault - Power unit overtemperature

Cause:

  • The heatsink temperature of the power unit has exceeded the fixed error threshold (100 °C).

  • Ambient temperature too high.

  • Fan or ventilation slots are polluted.

  • Fan is defective.





Remedy:

  • Check mains voltage.

  • Provide for a sufficient cooling of the device.

  • Clean fan and ventilation slots. If required, replace fan.

  • Reduce switching frequency.


17024 0x4280

Fault - Heat sink temperature sensor

Cause:

Sensor for the temperature monitoring of the power unit is defective.



Remedy:

  • Hardware error: it is necessary to contact the manufacturer, since the device must be replaced.


17025 0x4281

Heat sink fan warning

Cause:

Warning of the heatsink fan.



Remedy:

  • Clean fan and ventilation slots. If required, replace fan.


17029 0x4285

PU overtemperature warning

Cause:

  • The heatsink temperature has exceeded the warning threshold.

  • Ambient temperature too high.

  • Fan or ventilation slots are polluted.

  • Fan is defective.





Remedy:

  • Provide for a sufficient cooling of the device.

  • Clean fan and ventilation slots.

  • If required, replace fan.


17168 0x4310

Motor overtemperature

Cause:

  • The motor temperature sensor measures a too high motor temperature.

  • Motor too hot by impermissibly high currents.

  • Motor too hot by frequent and too long acceleration processes.





Remedy:

  • Check drive dimensioning.

  • Check motor temperature sensor and wiring.


20754 0x5112

External supply voltage critical

Cause:

External supply voltage failed or too low.



Remedy:

  • Check optional external 24V voltage supply (terminal X3/24E), if connected.

  • Check mains voltage.


20864 0x5180

Overload 24 V supply

Cause:

Output current at the 24V output or at the digital outputs too high.



Remedy:

  • Check 24V output and digital outputs for earth fault or overload.


21376 0x5380

OEM hardware incompatible

Cause:

The control unit (OEM hardware) is not compatible with the power unit (OEM hardware).



Remedy:

  • Use compatible hardware.

  • Contact the OEM.


24970 0x618A

Warning - Internal fan

Cause:

Warning of the internal fan.



Remedy:

  • Check/replace internal fan.


25216 0x6280

Trigger/functions connected incorrectly

Cause:

  • The assignment directives have not been observed.

  • Flexible I/O configuration active but Enable/Run not connected correctly.

  • Use of incompatible Start/Run functions (CW/CCW) simultaneously.





Remedy:

  • Check and correct the assignment of the triggers to the functions.


25217 0x6281

User-defined fault 1

Cause:

Flexible I/O configuration: the "Activate fault 1" function was activated via the trigger selected.



Remedy:

  • Eliminate error cause and then reset error.


25218 0x6282

User-defined fault 2

Cause:

Flexible I/O configuration: the "Activate fault 2" function was activated via the trigger selected.



Remedy:

  • Eliminate error cause and then reset error.


25232 0x6290

Warning invert rotation

Cause:

  • Negative setpoint selection with an active limitation of rotation.

  • The "Reverse rotational direction" function was requested with an active limitation of rotation.





Remedy:

  • Check setpoint selection and trigger.

  • Check setting in parameters.


25233 0x6291

Maximum allowed troubles exceeded

Cause:

The number of permitted restart attempts after a fault was exceeded. The fault occurred too frequently and could not be reset.



Remedy:

  • Check and eliminate the fault.


25248 0x62A0

User-defined fault (LECOM)

Cause:

The "Activate fault" function was triggered via bit 10 of the LECOM control word.



Remedy:

  • Eliminate error cause and then reset error.


25249 0x62A1

Network: user fault 1

Cause:

The "Activate fault 1" function was triggered via the NetWordIN1 data word.



Remedy:

  • Eliminate error cause and then reset error.


25250 0x62A2

Network: user fault 2

Cause:

The "Activate fault 2" function was triggered via the NetWordIN1 data word.



Remedy:

  • Eliminate error cause and then reset error.


25265 0x62B1

NetWordIN1 configuration incorrect

Cause:

Two bits of the NetWordIN1 data word were assigned to the same function.



Remedy:

  • Check and correct configuration of the NetWordIN1 data word.


25266 0x62B2

Changed device ID not yet active

Cause:

The device ID of the device was changed manually.



Remedy:

  • Execute device command "Save user data".

  • Switch inverter off and on again.


25267 0x62B3

Default settings not yet active

Cause:

The "Back-to-Box" system command has been executed. The standard parameter set has been written and saved.



Remedy:

  • Switch inverter off and on again.


25505 0x63A1

CU: load error ID tag

Cause:

Calibration data of the control unit not compatible or faulty.



Remedy:

  • Update firmware of the inverter to the most recent version.

  • If the error persists, the control unit or the device has to be replaced.


25506 0x63A2

PU: load error ID tag

Cause:

Calibration data of the power unit not compatible or faulty.



Remedy:

  • Update firmware of the inverter to the most recent version.

  • If the error persists, the power unit or the device has to be replaced.


25507 0x63A3

Power unit unknown

Cause:

The power unit installed is not supported by the software.



Remedy:

  • Update firmware of the inverter to the most recent version.


28800 0x7080

Assertion level monitoring (Low/High)

Cause:

The last setting of the connection level differs from the saved setting.



Remedy:

  • Execute device command "Save user data".

  • Switch inverter off and on again.


28801 0x7081

Fault - Analog input 1

Cause:

The monitoring function of the input signal configured for analog input 1 has been triggered.



Remedy:

  • Check input signal at analog input 1.

  • Check configuration of the monitoring function.


28802 0x7082

Analog input 2 fault

Cause:

The monitoring function of the input signal configured for analog input 2 has been triggered.



Remedy:

  • Check input signal at analog input 2.

  • Check configuration of the monitoring function.


28803 0x7083

HTL input fault

Cause:

(No specific cause listed in OCR, implies signal failure)



Remedy:

  • No response (configurable).


28833 0x70A1

Analog output 1 fault

Cause:

Open circuit or short circuit at analog output 1.



Remedy:

  • Check wiring of analog output 1.

  • Check definition of the output range.


28834 0x70A2

Analog output 2 fault

Cause:

Open circuit or short circuit at analog output 2.



Remedy:

  • Check wiring of analog output 2.

  • Check definition of the output range.


28961 0x7121

Fault - Pole position identification

Cause:

  • Too many deviations during the pole position identification.

  • Compared to the inverter, the rated motor current is too high or too low.





Remedy:

  • Check setting of the motor data.

  • Ensure that the motor is at a standstill during the pole position identification process.

  • Ensure that the motor and inverter match each other in terms of power.


29056 0x7180

Motor overcurrent

Cause:

The motor current has exceeded the warning/error threshold for the motor current monitoring.



Remedy:

  • Check motor load.

  • Check drive dimensioning.

  • Check warning threshold or error threshold.


29445 0x7305

Encoder open circuit

Cause:

The encoder signal loss monitoring function has detected a failure of the encoder signal.



Remedy:

  • Check the encoder connection.

  • Check encoder cable for wire breakage.

  • Check encoder current supply.


29573 0x7385

Feedback system: speed limit

Cause:

The feedback system exceeds the maximum permissible frequency range of the digital inputs.



Remedy:

  • Check feedback system.


30336 0x7680

Memory module is full

Cause:

The memory module contains too many parameter settings.



Remedy:

  • Execute "Save user data" device command again. This reinitialises the user memory with the current parameter settings.


30337 0x7681

Memory module not present

Cause:

The inverter memory module was removed.



Remedy:

  • Switch off inverter.

  • Plug the memory module into the inverter.

  • Switch the inverter on again.


30338 0x7682

Invalid user data

Cause:

The user parameter settings in the memory module are invalid.



Remedy:

  • Execute user parameter settings again.

  • Execute device command "Save user data".


30340 0x7684

Data not compl. saved before powerdown

Cause:

Saving of the parameter settings was interrupted by an unexpected disconnection.



Remedy:

  • Check user parameter settings.

  • If required, repeat the changes made last.

  • Execute device command "Save user data".


30345 0x7689

Memory module: invalid OEM data

Cause:

The OEM memory contains invalid parameter settings or is empty.



Remedy:

  • Execute device command "Save OEM data".


30346 0x768A

Memory module: wrong type

Cause:

The memory module connected is not supported by the inverter.



Remedy:

  • Switch off inverter.

  • Replace plugged-in memory module by a memory module that matches the inverter.

  • Switch the inverter on again.


30352 0x7690

EPM firmware version incompatible

Cause:

The parameter settings saved in the memory module are incompatible with the firmware version.



Remedy:

  • Execute device command "Load default settings".

  • Execute "Save user data" or "Save OEM data" device command.


30353 0x7691

EPM data: firmware type incompatible

Cause:

The parameter settings saved in the memory module are incompatible with the firmware type.



Remedy:

  • Execute device command "Load default settings".

  • Execute "Save user data" or "Save OEM data" device command.


30354 0x7692

EPM data: new firmware type detected

Cause:

The parameter settings saved in the memory module do not match the inverter hardware.



Remedy:

  • Check parameter settings.

  • Reset error.

  • Execute "Save user data" or "Save OEM data" device command.


30355 0x7693

EPM data: PU size incompatible

Cause:

The parameter settings saved in the memory module are incompatible with the inverter.



Remedy:

  • Execute device command "Load default settings".

  • Execute "Save user data" or "Save OEM data" device command.


30356 0x7694

EPM data: new PU size detected

Cause:

The parameter settings saved in the memory module comply with a different hardware.



Remedy:

  • Check parameter settings.

  • Reset error.

  • Execute "Save user data" or "Save OEM data" device command.


30357 0x7695

Invalid parameter changeover configuration

Cause:

One or more parameters can no longer be used for the "Parameter change-over" function.



Remedy:

  • Check error message for parameter change-over.

  • Correct the list entry shown in parameters.


30358 0x7696

EPM data: unknown parameter found

Cause:

The memory module contains parameter settings for one or several parameters that are not known to the inverter.



Remedy:

  • Execute the "Save user data" device command. This reinitialises the user memory with the current parameter settings.


30359 0x7697

Parameter changes lost

Cause:

A voltage failure has occurred and changed parameter settings that had not been saved yet were available.



Remedy:

  • Execute parameter settings again.

  • Execute device command "Save user data".


33042 0x8112

Network - Time-out explicit message

Cause:

  • Within the time-out period for explicit messages, no "explicit message" was received.

  • The connection to the scanner has been interrupted.

  • Failure of an explicit connection.





Remedy:

  • Check cables and terminals.

  • Plug network cables into the Ethernet port.

  • Check the requested package interval (RPI) of the explicit connection.

  • Increase time limit for explicit messages in the scanner.


33044 0x8114

Network - Overall communication time-out

Cause:

  • EtherNet/IP: the maximum permissible time-out period for the CIP communication has been exceeded.

  • Modbus TCP/IP: the maximum permissible time-out period for the TCP communication has been exceeded.





Remedy:

  • Check cables and terminals.

  • Connect network cable.


33045 0x8115

Time-out (PAM)

Cause:

The parameter access monitoring (PAM) function has been activated, but no value was entered into the "Keep-alive-Register" in time.



Remedy:

  • Check communication.

  • Check settings of the parameter access monitoring (PAM) function.


33046 0x8116

Modbus TCP master time-out

Cause:

No valid messages have been received by the Modbus master for a time longer than the time-out period set.



Remedy:

  • Check communication with the master.


33047 0x8117

Modbus TCP Keep Alive time-out

Cause:

For a time longer than the time-out period set, no value was entered into the Keep alive register.



Remedy:

  • Check communication with the master.


33154 0x8182

CAN: bus off

Cause:

  • Too many faulty frames have been received.

  • Defective cable (e. g. loose contact).

  • Two nodes with the same node address.





Remedy:

  • Check wiring of the network.

  • Check bus terminating resistor.

  • Set the identical baud rate for each node of the network.

  • Assign a unique node address to each node of the network.

  • Eliminate EMC interferences.


33155 0x8183

CAN: warning

Cause:

  • Too many faulty frames have been received.

  • Defective cable (e. g. loose contact).

  • Two nodes with the same node address.





Remedy:

  • Check wiring of the network.

  • Check bus terminating resistor.

  • Set the identical baud rate for each node of the network.

  • Assign a unique node address to each node of the network.

  • Eliminate EMC interferences.


33156 0x8184

CAN: heartbeat time-out consumer 1

Cause:

Within the heartbeat time, no heartbeat telegram was received by node 1 to be monitored.



Remedy:

  • Check communication with the heartbeat producer.

  • Reactivate heartbeat producer.


33157 0x8185

CAN: heartbeat time-out consumer 2

Cause:

Within the heartbeat time, no heartbeat telegram was received by node 2 to be monitored.



Remedy:

  • Check communication with the heartbeat producer.

  • Reactivate heartbeat producer.


33158 0x8186

CAN: heartbeat time-out consumer 3

Cause:

Within the heartbeat time, no heartbeat telegram was received by node 3 to be monitored.



Remedy:

  • Check communication with the heartbeat producer.

  • Reactivate heartbeat producer.


33159 0x8187

CAN: heartbeat time-out consumer 4

Cause:

Within the heartbeat time, no heartbeat telegram was received by node 4 to be monitored.



Remedy:

  • Check communication with the heartbeat producer.

  • Reactivate heartbeat producer.


33168 0x8190

Network - Watchdog time-out

Cause:

Time-out during cyclic data reception, e.g. due to an interrupted communication link to the master or missing cyclic data.



Remedy:

  • Check wiring of the network.

  • Eliminate EMC interferences.


33169 0x8191

Network - Disruption of cyclic data exchange

Cause:

The communication partner has interrupted the cyclic data exchange.



Remedy:

  • Check wiring of the network.

  • The slave must receive new parameterisation and configuration files by the master.


33170 0x8192

Network - Initialization error

Cause:

The initialisation of the communication stack has been interrupted due to an incorrect address setting or communication configuration.



Remedy:

  • Check master/slave configuration and restart the devices.


33171 0x8193

Network - Invalid cyclic process data

Cause:

The cyclic process data received are invalid.



Remedy:

  • Check cyclic process data sent by the master.


33185 0x81A1

Modbus: network time-out

Cause:

No valid messages have been received via the Modbus for a longer time than the time-out time set.



Remedy:

  • Check communication with the master.

  • Check wiring.

  • Check bus termination.


33186 0x81A2

Modbus: incorrect request by master

Cause:

The request by the master is invalid, e. g. invalid CRC checksum, non-supported function code, or impermissible data access.



Remedy:

  • Check request by the master.

  • Check value in the valid range.

  • Check function code valid.

  • Check if write access is impermissible.


33200 0x81B0

Network communication faulty

Cause:

In case of the Ethernet communication interface, an internal software error has occurred.



Remedy:

  • Switch inverter off and on again.

  • In the event of a power failure during a firmware download, reload the firmware via the USB module.


33381 0x8265

POWERLINK: Loss of SoC

Cause:

SoC of master was not received.



Remedy:

  • Check configuration and system setup.


33382 0x8266

POWERLINK: CRC error

Cause:

CRC frame defective.



Remedy:

  • Check system setup.


33414 0x8286

Network - PDO mapping error

Cause:

  • Invalid PDO assignment by the master.

  • Internal PDO assignment was changed and does not comply with the configuration available in the master.





Remedy:

  • Check data mapping in the master and slave.


33425 0x8291

CAN: RPDO1 time-out

Cause:

RPDO1 was not received within the time-out period set or with the sync configured.



Remedy:

  • (Check setting parameters)


33426 0x8292

CAN: RPDO2 time-out

Cause:

RPDO2 was not received within the time-out period set or with the sync configured.



Remedy:

  • (Check setting parameters)


33427 0x8293

CAN: RPDO3 time-out

Cause:

RPDO3 was not received within the time-out period set or with the sync configured.



Remedy:

  • (Check setting parameters)


33553 0x8311

Torque limit reached

Cause:

Motor has reached the torque limit (positive or negative).



Remedy:

  • Observe load requirements.

  • Reduce motor load.

  • Check set torque limits and sources for the torque limits.


33664 0x8380

Function not allowed in selected operating mode

Cause:

The selected function is not permissible in the chosen operating mode.



Remedy:

  • Check settings of operation modes.

  • Note selection of torque modes with incompatible motor control.


36992 0x9080

Keypad removed

Cause:

The keypad was removed while the keypad control was activated.



Remedy:

  • Plug keypad back in or activate another control source.


65282 0xFF02

Fault - Brake resistor overload

Cause:

The calculated thermal load of the brake resistor has reached the error threshold. The regenerative energy is too high.



Remedy:

  • Check drive dimensioning.

  • Check settings for the brake energy management.


65285 0xFF05

Safety option - Internal error

Cause:

The safety module or safety circuit of the device was detected as being defective. The integrated safety technology is defective.



Remedy:

  • Hardware error: it is necessary to contact the manufacturer since the device must be replaced.

  • The safety module must not be removed.


65286 0xFF06

Motor overspeed

Cause:

The motor speed has reached the error threshold for overspeed.



Remedy:

  • Adapt the maximum motor speed and the warning/error thresholds.


65289 0xFF09

Motor phase missing

Cause:

A failure of several motor phases has been detected.



Remedy:

  • Check wiring between inverter and motor.

  • In case of a false tripping, adapt the settings for the motor phase failure detection.


65290 0xFF0A

Motor phase failure phase U

Cause:

A failure of the motor phase U has been detected.



Remedy:

  • Check wiring between inverter and motor.

  • In case of a false tripping, adapt the settings for the motor phase failure detection.


65291 0xFF0B

Motor phase failure phase V

Cause:

A failure of the motor phase V has been detected.



Remedy:

  • Check wiring between inverter and motor.

  • In case of a false tripping, adapt the settings for the motor phase failure detection.


65292 0xFF0C

Motor phase failure phase W

Cause:

(Implied failure of phase W based on previous faults).



Remedy:

  • No response (configurable).


65305 0xFF19

Motor parameter identification fault

Cause:

During the automatic identification of the motor, an error has occurred.



Remedy:

  • Set motor data so that they comply with the data on the motor nameplate.

  • Check wiring of the motor.


65311 0xFF1F

FMF Error

Cause:

Configuration or runtime error.



Remedy:

  • Check configuration.

  • Check FMF error code 0x4050:002 to determine the error cause.


65317 0xFF25

Cascading overload

Cause:

Cascade function for pumps and fans: The maximum frequency has been reached and no free additional pump is available.



Remedy:

  • Check configuration of the cascade function.

  • Check drive sizing.


65334 0xFF36

Warning - Brake resistor overload

Cause:

The calculated thermal load of the brake resistor has reached the warning threshold. The regenerative energy is too high.



Remedy:

  • Check drive dimensioning.

  • Check settings for the brake energy management.


65335 0xFF37

Automatic start disabled

Cause:

At mains connection, a start command was already available and the automatic start at power-up is set to "Off".



Remedy:

  • Deactivate starting command and reset error.


65336 0xFF38

Load loss detected

Cause:

In a running motor, the motor load (current) falls below the threshold value specified in Load loss detection.



Remedy:

  • Check utilisation.


65337 0xFF39

Motor overload

Cause:

If the apparent motor current exceeds a defined threshold value for a certain amount of time.



Remedy:

  • Check the motor load.


65366 0xFF56

Maximum motor frequency reached

Cause:

  • The limitation of the maximum motor speed is active.

  • The maximum output frequency of the inverter has been reached.





Remedy:

  • Check application.


65370 0xFF5A

Manual mode disabled

Cause:

Indicates the deactivation of the manual speed control.



Remedy:

  • (Warning only)


65371 0xFF5B

Manual mode activated

Cause:

Indicates the activation of the manual speed control.



Remedy:

  • (Warning only)


65372 0xFF5C

Manual mode time-out

Cause:

If "manual operation" is active, an error is generated in case the communication links get lost.



Remedy:

  • The error can be only be reset if the connection is restored or the control mode is changed to a different value than "manual operation".


65393 0xFF71

Wrong password

Cause:

A wrong password has been entered several times.



Remedy:

  • Wait until the blocking time has elapsed and then enter the correct password.


65394 0xFF72

Warning

Cause:

  • Inverter is not compatible with the Controller/PLC (brand protection).

  • The Controller has not written a deactivation password in the parameter yet.





Remedy:

  • Use corresponding (compatible) OEM components.


65395 0xFF73

Fatal Error

Cause:

Error when reading the data from the control unit.



Remedy:

  • Switch inverter off and on again.

  • If the error occurs again, the manufacturer must be contacted.


65396 0xFF74

Power unit fatal error

Cause:

Error when reading the data from the power unit.



Remedy:

  • Switch inverter off and on again.

  • If the error occurs again, the manufacturer must be contacted.


65413 0xFF85

Keypad full control active

Cause:

If the "Keypad Full Control" control mode is active.



Remedy:

  • To exit the control mode, press the keypad key CTRL.


How to Clear & Reset Lenze i550 Cabinet Drive Faults

  1. Keypad Reset: Press the red STOP/RETURN key on the pluggable keypad module to clear an active fault once the root cause has been rectified.
  2. Digital Terminal Reset: Apply a LOW-to-HIGH signal edge (positive 24V pulse) to the digital input terminal assigned to “Reset fault” (configured in parameter 0x2631:004, typically assigned to DI1–DI5 on the control terminal strip).
  3. Lenze EASY Starter & SMART App: Connect via the pluggable USB diagnostic module or WLAN module, open the Lenze EASY Starter engineering tool (or mobile app), and click “Fault Reset” in the diagnostics toolbar.
  4. Fieldbus Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in the CiA 402 or drive control word (0x6040) across PROFINET, EtherCAT, Ethernet/IP, Modbus TCP/RTU, CANopen, or IO-Link networks.
  5. Mains Line Power Cycle: Switch off the AC mains incoming power. Wait at least 3 to 10 minutes until the DC bus capacitors fully discharge and all diagnostic LEDs extinguish completely, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous residual electrical charge remains in the intermediate DC bus capacitors after disconnecting the AC supply line. Always wait a minimum of 3 to 10 minutes (depending on inverter frame size) after switching off power, and verify with a calibrated digital multimeter that the DC bus voltage across terminals [+UG] and [-UG] measures safely below 50VDC before inspecting motor terminals (U, V, W) or brake chopper connections (+UG, RB).