Lenze 8200 Vector Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze 8200 Vector modular frequency inverter series. Search or filter through the complete fault code directory below.
Power Range
0.25 – 90 kW (0.33 – 120 HP)
Supply Voltage
1/3-Ph 230V | 3-Ph 400/500V
Control Modes
Sensorless Vector & V/f Control
Operator Interface
Keypad XT / Fieldbus Modules
Complete Lenze 8200 Vector Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC1, OU, OH, or LU).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| ccr System fault (PC: 71) | Cause: Strong interference injections on the control cables; Earth loops in the wiring. Remedy:
|
| ce0 Communication error on AIF (PC: 61) | Cause: Faulty transmission of control commands via AIF. Remedy:
|
| ce1 / ce2 / ce3 Communication error on CAN-IN (PC: 62, 63, 64) | Cause: CAN-IN object receives faulty data, or communication is interrupted. Remedy:
|
| ce4 BUS-OFF (PC: 65) | Cause: Controller has received too many faulty telegrams via the system bus and has been disconnected. Remedy:
|
| ce5 CAN time-out (PC: 66) | Cause: Remote parameterization slave does not respond; Parameter set change-over incorrectly parameterised; Internal error. Remedy:
|
| FAn1 Fan failure (PC: 95) | Cause: Fan is defective or not connected. Remedy:
|
| LP1 Motor phase error (PC: 32 / 182) | Cause: Failure of motor phases; Motor current is too low. Remedy:
|
| LU DC-bus undervoltage | Cause: Mains voltage too low; 400V controller connected to 240V mains. Remedy:
|
| OC1 Short circuit (PC: 11) | Cause: Short circuit; Capacitive charging current of motor cable too high. Remedy:
|
| OC5 Controller overload (PC: 15) | Cause: Frequent and too long overload periods during steady-state operation. Remedy:
|
| OH Heatsink temperature > 85 °C (PC: 50) | Cause: Ambient temperature too high; Heatsink very dirty. Remedy:
|
| OH4 Controller overtemperature (PC: 54) | Cause: Controller is too hot inside. Remedy:
|
| OU DC-bus overvoltage | Cause: Mains voltage too high; Braking operation (deceleration too fast). Remedy:
|
| Pr Faulty parameter transfer (PC: 75) | Cause: All parameter sets are defective. Remedy:
|
| sd5 / sd7 Wire breakage, analog input (PC: 85 / 87) | Cause: Current on analog input < 4 mA for setpoint range 4...20 mA. Remedy:
|
| rSt Error during Auto-TRIP reset (PC: 76) | Cause: More than 8 error messages within 10 minutes. Remedy:
|
How to Clear & Reset Lenze 8200 Vector Drive Faults
- Keypad XT Reset: When using the pluggable XT keypad (EMZ8201BB) or operating module, note the TRIP message shown on the display. Inhibit the inverter controller, then press the red STOP key (or acknowledge the trip under parameter code C0043).
- Digital Terminal Reset (TRIP-RESET): Apply a LOW-to-HIGH signal edge (positive voltage pulse) to the digital input terminal assigned to the TRIP-RESET function (configured in parameter code C0410 / C0412, such as terminals E1, E2, E3, or E4 on the function module).
- Global Drive Control (GDC) PC Tool: Connect your PC to the drive via the front diagnostic/communication interface (LECOM-A/B RS232/RS485 or optical module), launch Lenze Global Drive Control, and execute the TRIP-Reset command.
- Fieldbus Control Word: Write Bit 7 (TRIP Reset) from `0` to `1` in the automation control word across CANopen, PROFIBUS-DP, or INTERBUS communication modules.
- Power Cycle: Disconnect main incoming AC line power, wait 3 to 10 minutes until internal DC bus discharge is complete and all LEDs are off, then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual voltage remains inside intermediate DC bus capacitors after mains supply disconnection. Always wait a minimum of 3 to 10 minutes (depending on inverter power frame) after powering down, and verify with a calibrated digital multimeter that the voltage across DC terminals [+UG] and [-UG] measures strictly below 50VDC before inspecting motor terminals U, V, and W or handling external braking resistor wiring.