Lenze 8200 Vector drive

Home / Lenze / Lenze 8200 Vector drive

Lenze 8200 Vector Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze 8200 Vector modular frequency inverter series. Search or filter through the complete fault code directory below.

Modular Frequency Inverter Power: 0.25 to 90 kW (0.33 to 120 HP) Sensorless Vector & V/f Control
Power Range 0.25 – 90 kW (0.33 – 120 HP)
Supply Voltage 1/3-Ph 230V | 3-Ph 400/500V
Control Modes Sensorless Vector & V/f Control
Operator Interface Keypad XT / Fieldbus Modules

Complete Lenze 8200 Vector Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OU, OH, or LU).

Fault Code and MeaningCause and Remedy
ccr
System fault
(PC: 71)

Cause: Strong interference injections on the control cables; Earth loops in the wiring.


Remedy:

  • Shield control cables.


ce0
Communication error on AIF
(PC: 61)

Cause: Faulty transmission of control commands via AIF.


Remedy:

  • Insert the communication module firmly into the diagnosis terminal.


ce1 / ce2 / ce3
Communication error on CAN-IN
(PC: 62, 63, 64)

Cause: CAN-IN object receives faulty data, or communication is interrupted.


Remedy:

  • Check plug connection bus module / FIF.

  • Check transmitter.

  • Increase monitoring time in C0357, if necessary.


ce4
BUS-OFF
(PC: 65)

Cause: Controller has received too many faulty telegrams via the system bus and has been disconnected.


Remedy:

  • Check bus termination.

  • Check shield connection of the cables.

  • Check PE connection.

  • Check bus load, reduce the baud rate if necessary.


ce5
CAN time-out
(PC: 66)

Cause: Remote parameterization slave does not respond; Parameter set change-over incorrectly parameterised; Internal error.


Remedy:

  • Check wiring of the system bus.

  • Check system bus configuration.

  • Ensure "parameter set change-over" signal (C0410/13/14) is connected to the same source in all sets.

  • Contact Lenze (if internal error).


FAn1
Fan failure
(PC: 95)

Cause: Fan is defective or not connected.


Remedy:

  • Replace fan.

  • Connect fan.

  • Check wiring.


LP1
Motor phase error
(PC: 32 / 182)

Cause: Failure of motor phases; Motor current is too low.


Remedy:

  • Check motor supply cables.

  • Check Vmin boost.

  • Connect motor with corresponding power or adapt with C0599.


LU
DC-bus undervoltage

Cause: Mains voltage too low; 400V controller connected to 240V mains.


Remedy:

  • Check mains voltage.

  • Check power supply module.

  • Connect controller to correct mains voltage.


OC1
Short circuit
(PC: 11)

Cause: Short circuit; Capacitive charging current of motor cable too high.


Remedy:

  • Search for cause of short circuit; check motor cable.

  • Check brake resistor and cable.

  • Use shorter/low-capacitance motor cable.


OC5
Controller overload
(PC: 15)

Cause: Frequent and too long overload periods during steady-state operation.


Remedy:

  • Check drive dimensioning.


OH
Heatsink temperature > 85 °C
(PC: 50)

Cause: Ambient temperature too high; Heatsink very dirty.


Remedy:

  • Allow controller to cool; provide better ventilation.

  • Clean heatsink.


OH4
Controller overtemperature
(PC: 54)

Cause: Controller is too hot inside.


Remedy:

  • Reduce controller load.

  • Improve cooling.

  • Check fan in the controller.


OU
DC-bus overvoltage

Cause: Mains voltage too high; Braking operation (deceleration too fast).


Remedy:

  • Check supply voltage.

  • Increase deceleration times.

  • Check dimensioning of external brake resistor.


Pr
Faulty parameter transfer
(PC: 75)

Cause: All parameter sets are defective.


Remedy:

  • Repeat data transfer or load Lenze setting before enabling controller.


sd5 / sd7
Wire breakage, analog input
(PC: 85 / 87)

Cause: Current on analog input < 4 mA for setpoint range 4...20 mA.


Remedy:

  • Close the circuit at the analog input.


rSt
Error during Auto-TRIP reset
(PC: 76)

Cause: More than 8 error messages within 10 minutes.


Remedy:

  • Dependent on the specific error message causing the trips.


How to Clear & Reset Lenze 8200 Vector Drive Faults

  1. Keypad XT Reset: When using the pluggable XT keypad (EMZ8201BB) or operating module, note the TRIP message shown on the display. Inhibit the inverter controller, then press the red STOP key (or acknowledge the trip under parameter code C0043).
  2. Digital Terminal Reset (TRIP-RESET): Apply a LOW-to-HIGH signal edge (positive voltage pulse) to the digital input terminal assigned to the TRIP-RESET function (configured in parameter code C0410 / C0412, such as terminals E1, E2, E3, or E4 on the function module).
  3. Global Drive Control (GDC) PC Tool: Connect your PC to the drive via the front diagnostic/communication interface (LECOM-A/B RS232/RS485 or optical module), launch Lenze Global Drive Control, and execute the TRIP-Reset command.
  4. Fieldbus Control Word: Write Bit 7 (TRIP Reset) from `0` to `1` in the automation control word across CANopen, PROFIBUS-DP, or INTERBUS communication modules.
  5. Power Cycle: Disconnect main incoming AC line power, wait 3 to 10 minutes until internal DC bus discharge is complete and all LEDs are off, then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning: Hazardous residual voltage remains inside intermediate DC bus capacitors after mains supply disconnection. Always wait a minimum of 3 to 10 minutes (depending on inverter power frame) after powering down, and verify with a calibrated digital multimeter that the voltage across DC terminals [+UG] and [-UG] measures strictly below 50VDC before inspecting motor terminals U, V, and W or handling external braking resistor wiring.