Lenze 941 Servo drive

Home / Lenze / Lenze 941 Servo drive

Lenze 941 Servo Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze AC Tech PositionServo 941 resolver-based motion controller series. Search or filter through the complete fault code directory below.

Digital Servo Drive & Motion Controller Resolver Feedback (Model 941 / E94R) Output Current: 2 to 18 A Continuous
Power / Current 0.4 – 7.5 kW (2 – 18 A Cont.)
Supply Voltage 120V / 240V / 480V AC (1/3-Phase)
Control Modes Torque, Velocity & Position
Feedback / Comm Resolver / Onboard Ethernet

Complete Lenze 941 Servo Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F_OC, F_OU, F_FB, or F_OH).

Fault Code and MeaningCause and Remedy
F_OU

Over voltage

Cause:

Drive bus voltage reached the maximum level, typically due to motor regeneration.


Remedy:

Check deceleration time or install a braking resistor.
F_FB

Feedback error

Cause:

Invalid Hall sensors code; Resolver signal lost or at least one motor hall sensor is inoperable or not connected.


Remedy:

Check encoder/resolver wiring and Hall sensor connections.
F_OC

Over current

Cause:

Drive exceeded peak current limit. Software incapable of regulating current within 15% for more than 20mS.


Remedy:

Check for wrong motor data, poor tuning, or short circuit in motor cables.
F_Ot

Over temperature

Cause:

Drive heatsink temperature has reached maximum rating (100°C or 108°C depending on model).


Remedy:

Check ambient temperature, cooling fans, and cabinet ventilation.
F_OS

Over speed

Cause:

Motor has reached velocity above its specified limit.


Remedy:

Check speed loop tuning and commanded velocity limits.
F_PE

Position Error Excess

Cause:

Position error has exceeded maximum allowed value.


Remedy:

Check for mechanical jams, motor sizing, or increase position error tolerance.
F_bd

Bad motor data

Cause:

Motor profile data is invalid or no motor is selected.


Remedy:

Verify motor parameters in the configuration software.
F_EP

EPM failure

Cause:

EPM (Electronic Programming Module) failure on power up.


Remedy:

Replace the EPM module or try re-seating it.
-EP-

EPM missing

Cause:

EPM not recognized (connected) on power up.


Remedy:

Ensure the EPM is properly inserted into the slot.
F_09

Motor over temperature

Cause:

Motor over temperature switch activated or PTC indicates motor windings reached maximum temperature.


Remedy:

Allow motor to cool; check motor load and cooling.
F_10

Subprocessor failure

Cause:

Error in data exchange between processors. Usually occurs when EMI level is high.


Remedy:

Check for poor shielding and grounding of the system.
F_14

Under voltage

Cause:

Bus voltage level drops below 50% of nominal bus voltage while operating.


Remedy:

Check incoming AC line voltage and power supply stability.
F_15

Hardware overload protection

Cause:

Phase current becomes higher than 400% of total drive current capability for more than 5μs.


Remedy:

Check for short circuits or extreme mechanical overload.
F_18

Arithmetic Error / Division by zero

Cause:

Statement executed within Indexer Program results in division by zero.


Remedy:

Check and correct the drive source code logic.
F_19

Arithmetic Error / Register overflow

Cause:

Indexer Program generated a value too large for the requested register.


Remedy:

Review variable types and math operations in the program.
F_20

Subroutine stack overflow

Cause:

Exceeded 32 levels of subroutine stack depth (excessive calls without RETURN).


Remedy:

Verify program logic to ensure all calls have corresponding RETURN statements.
F_25

Unknown opcode

Cause:

Byte code interpreter error; missing END statement or corrupted EPM data.


Remedy:

Re-download the program or replace the EPM.
F_27

Drive disabled

Cause:

Attempt to execute motion while the drive is disabled.


Remedy:

Enable the drive before commanding motion in the program.
F_32

Positive Limit Switch

Cause:

Positive limit switch is activated.


Remedy:

Move the axis in the negative direction or check the switch wiring.
F_36

Drive Disabled by User at Enable Input

Cause:

Drive is disabled during operation or attempt to enable without deactivating "Inhibit".


Remedy:

Check the state of the hardware Enable and Inhibit inputs.
F_45

2nd Encoder Position Error

Cause:

Second encoder position error has exceeded maximum value.


Remedy:

Check the secondary encoder alignment and wiring.

How to Clear & Reset Lenze 941 Servo Drive Faults

  1. Keypad / Front Display Reset: If the 4-character front status display shows a flashing fault code (such as F_OC or F_OU), disable the drive enable signal (ENBL) and press the front toggle key to clear the latched fault once conditions normalize.
  2. Digital Input Reset (P3 Controller Interface): If a digital input on the P3 connector (pins 13–23) is programmed as a fault reset in MotionView, cycle a 24V DC input pulse to clear recorded alarms.
  3. MotionView OnBoard PC Tool: Connect your PC via the standard onboard Ethernet port (P2 connector), open the MotionView commissioning interface, view the active fault in the diagnostic pane, and click “Reset Fault”.
  4. Fieldbus / Modbus RTU Command: If operating over CANopen, DeviceNet, PROFIBUS-DP, or RS-485 Modbus RTU, write a logic `1` to the Fault Reset bit in the primary drive control word.
  5. Mains Line Power Cycle: Switch off the incoming AC power supply at connector P1. Wait at least 5 minutes for the internal DC bus capacitors to discharge and all diagnostic LEDs to extinguish completely, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous voltage remains present in the intermediate DC bus capacitors even after the AC supply is disconnected. Always wait a minimum of 5 minutes after power-down, and verify with a calibrated digital multimeter that voltage across connector P6 (DC Bus terminals [+DC] and [-DC]) is safely below 50VDC before inspecting motor output terminals (P7: U, V, W) or resolver feedback wiring (P4).