Lenze 940 Servo Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze PositionServo 940 series servo controllers. Search or filter through the complete fault code directory below.

Digital Servo Drive & Controller Power: 0.88 to 7.5 kW (2 to 18 A Continuous) Encoder-Based Feedback & MotionView OnBoard
Rated Output Current 2 – 18 A RMS (Up to 54 A Peak)
Supply Voltage 115V / 230V / 460V AC
Control Modes Position, Velocity & Torque
Operator Interface LED Display / MotionView Software

Complete Lenze 940 Servo Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F_OU, F_OC, F_FB, or Feedback).

Fault Code and MeaningCause and Remedy
F_OU

Over voltage

Cause:

Drive bus voltage reached the maximum level, typically due to motor regeneration.


Remedy:

Check deceleration time or install a braking resistor.
F_FB

Feedback error

Cause:

Invalid Hall sensors code; Resolver signal lost or at least one motor hall sensor is inoperable or not connected.


Remedy:

Check encoder/resolver wiring and Hall sensor connections.
F_OC

Over current

Cause:

Drive exceeded peak current limit. Software incapable of regulating current within 15% for more than 20mS.


Remedy:

Check for wrong motor data, poor tuning, or short circuit in motor cables.
F_Ot

Over temperature

Cause:

Drive heatsink temperature has reached maximum rating (100°C or 108°C depending on model).


Remedy:

Check ambient temperature, cooling fans, and cabinet ventilation.
F_OS

Over speed

Cause:

Motor has reached velocity above its specified limit.


Remedy:

Check speed loop tuning and commanded velocity limits.
F_PE

Position Error Excess

Cause:

Position error has exceeded maximum allowed value.


Remedy:

Check for mechanical jams, motor sizing, or increase position error tolerance.
F_bd

Bad motor data

Cause:

Motor profile data is invalid or no motor is selected.


Remedy:

Verify motor parameters in the configuration software.
F_EP

EPM failure

Cause:

EPM (Electronic Programming Module) failure on power up.


Remedy:

Replace the EPM module or try re-seating it.
-EP-

EPM missing

Cause:

EPM not recognized (connected) on power up.


Remedy:

Ensure the EPM is properly inserted into the slot.
F_09

Motor over temperature

Cause:

Motor over temperature switch activated or PTC indicates motor windings reached maximum temperature.


Remedy:

Allow motor to cool; check motor load and cooling.
F_10

Subprocessor failure

Cause:

Error in data exchange between processors. Usually occurs when EMI level is high.


Remedy:

Check for poor shielding and grounding of the system.
F_14

Under voltage

Cause:

Bus voltage level drops below 50% of nominal bus voltage while operating.


Remedy:

Check incoming AC line voltage and power supply stability.
F_15

Hardware overload protection

Cause:

Phase current becomes higher than 400% of total drive current capability for more than 5μs.


Remedy:

Check for short circuits or extreme mechanical overload.
F_18

Arithmetic Error / Division by zero

Cause:

Statement executed within Indexer Program results in division by zero.


Remedy:

Check and correct the drive source code logic.
F_19

Arithmetic Error / Register overflow

Cause:

Indexer Program generated a value too large for the requested register.


Remedy:

Review variable types and math operations in the program.
F_20

Subroutine stack overflow

Cause:

Exceeded 32 levels of subroutine stack depth (excessive calls without RETURN).


Remedy:

Verify program logic to ensure all calls have corresponding RETURN statements.
F_25

Unknown opcode

Cause:

Byte code interpreter error; missing END statement or corrupted EPM data.


Remedy:

Re-download the program or replace the EPM.
F_27

Drive disabled

Cause:

Attempt to execute motion while the drive is disabled.


Remedy:

Enable the drive before commanding motion in the program.
F_32

Positive Limit Switch

Cause:

Positive limit switch is activated.


Remedy:

Move the axis in the negative direction or check the switch wiring.
F_36

Drive Disabled by User at Enable Input

Cause:

Drive is disabled during operation or attempt to enable without deactivating "Inhibit".


Remedy:

Check the state of the hardware Enable and Inhibit inputs.
F_45

2nd Encoder Position Error

Cause:

Second encoder position error has exceeded maximum value.


Remedy:

Check the secondary encoder alignment and wiring.

How to Clear & Reset Lenze 940 Servo Drive Faults

  1. Front Reset Button: Press and hold the reset push button on the front face of the PositionServo 940 drive for 2 to 3 seconds. The drive will re-initialize and clear inactive faults.
  2. MotionView PC / OnBoard Interface: Connect your PC via Ethernet or RS-232/RS-485 serial port, open the MotionView software (or web-based MotionView OnBoard), go to the Diagnostic/Status monitor window, and click “Clear Faults” or “Reset”.
  3. Enable / Inhibit Input Cycling: Depending on the configured Fault Reset Option (ON DISABLE or ON ENABLE in drive parameters), toggle the hardware Enable / Inhibit line (Terminal A3) to clear latched trip conditions.
  4. Fieldbus / Network Reset: Transmit a fault reset command or clear the error register across your active communication network (CANopen, Ethernet/IP, Modbus TCP/IP, Modbus RTU, or PROFIBUS DP).
  5. Mains Line Power Cycle: Switch off the incoming AC supply power, wait at least 5 minutes for the internal DC bus capacitors to discharge and all display LEDs to turn off completely, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect the main AC supply and wait at least 5 minutes for intermediate DC bus capacitors to completely discharge. Verify with a calibrated DC voltmeter that voltage across intermediate DC bus terminals measures strictly below 50V DC before touching motor cables (U, V, W), encoder feedback lines, or terminal wiring.