Lenze i550 motec drive

Home / Lenze / Lenze i550 motec drive

Lenze i550 motec Inverter Fault Codes & Diagnostic Guide

Complete fault code reference directory, CiA 402 error classifications, LED status indications, and step-by-step diagnostic procedures for the Lenze i550 motec decentralized frequency inverter. Search or filter through the complete fault code directory below.

Decentralized Inverter (IP66 / NEMA 4X) Power: 0.37 to 45 kW (0.5 to 60 HP) Wall or Motor Mounting
Power Range 0.37 – 45 kW (0.5 – 60 HP)
Supply Voltage 1-ph 230V / 3-ph 230–480V AC
Control Modes V/f, Sensorless Vector & Sync
Commissioning & Tools EASY Starter / Micro-USB / WLAN

Complete Lenze i550 motec Drive Fault Code Directory

Use the search box in the table below to quickly find your error code (e.g., type 2250, 2320, 3210, or Overcurrent).

Fault Code and MeaningCause and Remedy
2250
CiA: Continuous overcurrent (inside the device)

Cause: Classification: Error



Remedy:

  • Check motor and wiring for short circuits.

  • Check brake resistor and wiring.

  • Check motor circuit (delta connection, star connection).

  • Check setting of the motor data.


2320
Short circuit or earth leakage on motor side

Cause: Classification: Error



Remedy:

  • Check motor cable.

  • Check the length of the motor cable.

  • Use shorter or lower-capacitance motor cable.


2340
CiA: Short circuit (inside the device)

Cause: Classification: Error



Remedy:

  • Check motor cable for short circuit.


2350
CiA: i²*t overload (thermal state)

Cause: Classification: Error



Remedy:

  • Check drive sizing.

  • Check machine/driven mechanics for excessive load.

  • Check setting of the motor data.

  • Reduce values for slip compensation (0x2B09:001, 0x2B09:002) and oscillation damping (0x2B0A:001, 0x2B0A:002).


2382
Error - device utilization (Ixt) too high

Cause: Classification: Error



Remedy:

  • Check drive sizing.

  • Reduce maximum overload current of the inverter (0x6073).

  • In case of high mass inertias, reduce maximum overload current of the inverter (0x6073) to 150 %.


2383
Warning - device utilization (Ixt) too high

Cause: Classification: Warning



Remedy:

  • Check drive sizing.


3120
Mains phase fault

Cause: Classification: Error



Remedy:

  • Check mains connection wiring.

  • Check fuses.


3210
Error - DC bus overvoltage

Cause: Classification: Error



Remedy:

  • Reduce dynamic performance of the load profile.

  • Check mains voltage.

  • Check settings for the brake energy management.


3211
Warning: DC-bus overvoltage

Cause: Classification: Warning



Remedy:

  • (See Error 3210 for typical checks)


3220
Error - DC-bus undervoltage

Cause: Classification: Trouble



Remedy:

  • Check mains voltage.

  • Check fuses.

  • Check DC-bus voltage (0x2D87).

  • Check mains settings.


3221
Warning: DC bus undervoltage

Cause: Classification: Warning



Remedy:

  • (See Error 3220 for typical checks)


3222
DC-bus voltage too low for switch-on

Cause: Classification: Warning



Remedy:

  • Check mains voltage.

  • Check fuses.

  • Check mains settings.


4210
Error - power section overtemperature

Cause: Classification: Error



Remedy:

  • Check mains voltage.

  • Ensure sufficient cooling of the device (display of heatsink temperature in 0x2D84:001).

  • Clean fan and ventilation slots. If required, replace fan.

  • Reduce switching frequency (0x2939).


4281
Warning - heatsink fan

Cause: Classification: Warning



Remedy:

  • Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can then be removed.


4310
Motor overtemperature

Cause: Classification: Error



Remedy:

  • Check drive sizing.

  • Check motor temperature sensor and wiring at X105/T1+T2 or X109/T1+T2.


5112
24 V supply critical

Cause: Classification: Warning



Remedy:

  • Check optional external auxiliary supply on X100.1/24E.1, if connected.

  • Check mains voltage.


5180
24 V supply overload

Cause: Classification: Warning



Remedy:

  • Check 24 V output and digital outputs for earth fault or overload.


6280
Trigger/functions connected incorrectly

Cause: Classification: Trouble



Remedy:

  • Check and correct the assignment of the triggers to the functions.

  • In network control, the two functions "Inverter enable" (0x2631:001) and “Start" (0x2631:002) can also be set to "Constant TRUE [1]" to start the motor.


7180
Motor overcurrent

Cause: Classification: Error



Remedy:

  • Check motor load.

  • Check drive sizing.

  • Adapt set error threshold (0x2D46:001).


FF06
Motor overspeed

Cause: Classification: Error



Remedy:

  • Adapt the maximum motor speed (0x6080) and the error threshold (0x2D44:001).


FF37
Automatic start disabled

Cause: Classification: Error



Remedy:

  • Deactivate start command and reset error.


How to Clear & Reset Lenze i550 motec Drive Faults

  1. Digital Input Reset (DI2 / DI1): By default, an active error can be reset by applying a HIGH signal to digital input 2 (parameter 0x2631:004 – Error reset). Alternatively, drop and re-apply the start signal on digital input 1 (parameter 0x2631:002) once the fault root cause is resolved and any parameter-defined blocking time has elapsed.
  2. Lenze EASY Starter Engineering Tool: Connect your PC via the integrated micro-USB diagnostic interface or optional WLAN module. Open Lenze EASY Starter, navigate to the Diagnostics tab, and click the “Reset” button to clear the fault buffer.
  3. Lenze SMART Keypad Mobile App: If equipped with the external WLAN diagnostic module, open the Lenze SMART Keypad app on your iOS or Android mobile device, connect to the drive’s local network, and trigger a fault reset directly from the diagnostics screen.
  4. Ethernet / Fieldbus Control Word: Set bit 7 (Fault Reset / Acknowledge) from `0` to `1` in the CiA 402 control word over PROFINET, EtherCAT, EtherNet/IP, Modbus TCP, or IO-Link.
  5. Mains Power Cycle: Switch off incoming AC supply power. Wait at least 3 minutes until the DRIVE status LEDs (blue RDY and red ERR) completely turn off and internal DC bus capacitors discharge, then re-energize the inverter.
⚠️ High-Voltage Electrical Safety Warning: Although the Lenze i550 motec features a rugged IP66 / NEMA 4X decentralized housing, dangerous intermediate DC bus voltage remains present after mains disconnection. Always isolate the AC mains line, wait at least 3 minutes, and verify using a calibrated multimeter that DC bus voltage is below 50V DC before opening connection covers, disconnecting plug-and-play connectors, or servicing motor leads.