Lenze SCM Series Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze AC Tech SCM sub-micro inverter series. Search or filter through the complete fault code directory below.

Sub-Micro AC Inverter Power: 0.25 to 15 kW (0.33 to 20 HP) Pluggable EPM Memory Module
Power Range 0.25 – 15 kW (0.33 – 20 HP)
Supply Voltage 120V / 240V / 480V / 590V AC
Control Modes Volts/Hertz (V/Hz) Scalar
Operator Interface 3-Digit LED & Integrated Keypad

Complete Lenze SCM Series Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F_OC, F_OU, F_LU, or F_OH).

Fault Code and MeaningCause and Remedy
AF
High Temp. Fault

Cause: Ambient temperature is too high; Cooling fan has failed (if equipped).



Remedy:

  • Check ventilation and ambient temperature.

  • Check cooling fan operation.


CF
Control Fault

Cause: A blank EPM, or an EPM with corrupted data has been installed.



Remedy:

  • Perform a factory reset using Parameter 48 - PROGRAM SELECTION.


cF
Incompatibility Fault

Cause: An EPM with an incompatible parameter version has been installed.



Remedy:

  • Remove the EPM.

  • Or perform a factory reset (Parameter 48) to change the parameter version of the EPM to match the drive.


dF
Dynamic Braking Fault

Cause: The drive has sensed that the dynamic braking resistors are overheating and shuts down to protect the resistors.



Remedy:

  • Check load and braking cycle requirements.


EF
External Fault

Cause: One of the TB-13 terminals is set as an External Fault input and that terminal is open with respect to TB-11.



Remedy:

  • Refer to Parameters 10, 11 and 12.

  • Check external wiring/interlocks.


GF
Data Fault

Cause: User data and OEM defaults in the EPM are corrupted.



Remedy:

  • Attempt factory reset.

  • Replace EPM if necessary.


HF
High DC Bus Voltage Fault

Cause: Line voltage is too high; Deceleration rate is too fast; Over-hauling load.



Remedy:

  • Check input line voltage.

  • Decrease deceleration rate.

  • Dynamic braking may be required for fast deceleration or overhauling loads.


JF
Remote Keypad Fault

Cause: The communication link between the drive and the optional Remote Keypad has been lost.



Remedy:

  • Check for proper wiring and/or noise.


LF
Low DC Bus Voltage Fault

Cause: Line voltage is too low.



Remedy:

  • Check input line voltage.

  • Wait for voltage to return to normal level (Fault cannot be cleared until voltage is normal).


OF
Output Transistor Fault

Cause: Phase to phase or phase to ground short circuit on the output; Boost settings are too high; Acceleration rate is too fast; Failed output transistor.



Remedy:

  • Check motor and cabling for shorts.

  • Adjust Boost settings.

  • Reduce acceleration rate.


PF
Current Overload Fault

Cause: VFD is undersized for the application; Mechanical problem with the driven equipment.



Remedy:

  • Verify drive sizing vs motor load.

  • Check driven equipment for mechanical binding or issues.


UF
Start Fault

Cause: Start command was present when the drive was powered up.



Remedy:

  • Must wait 2 seconds after power-up to apply Start command if START METHOD is set to NORMAL.


F1
EPM Fault

Cause: The EPM is missing or damaged.



Remedy:

  • Install valid EPM.


FC, F2-F9, Fo
Internal Faults

Cause: The control board has sensed a problem.



Remedy:

  • Consult factory.


br
DC Braking

Cause: The DC braking circuit is activated.



Remedy:

  • Status indication only.


cE
Parameter Version Warning

Cause: An EPM with a different parameter version is installed and an attempt is made to change parameter settings without performing the TRANSLATE function.



Remedy:

  • Refer to PROGRAM SELECTION (Parameter 48).


CL
Current Limit

Cause: The output current has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive is reducing output frequency.



Remedy:

  • If drive remains in CURRENT LIMIT too long, it can trip into PF fault.

  • Check load conditions.


Er
Error

Cause: Invalid data has been entered or an invalid command was attempted.



Remedy:

  • Check data range and retry.


GE
OEM Mode Warning

Cause: Attempt made to change OEM default settings when the drive is operating in the OEM mode.



Remedy:

  • Refer to Parameter 48.


GF
OEM Data Corruption

Cause: If displayed when RESET OEM attempted: OEM defaults in EPM corrupted. If displayed upon power-up: OEM defaults and user settings in EPM corrupted.



Remedy:

  • Refer to Section 13.2 of manual.


LC
Fault Lockout

Cause: The drive has failed three restart attempts.



Remedy:

  • Requires a manual reset.


SE
Serial Active

Cause: The optional remote keypad is active as the user interface instead of the buttons on front of the drive.



Remedy:

  • Refer to Parameter 14 (CONTROL).


SP
Start Pending

Cause: Blinks during the interval between restart attempts.



Remedy:

  • Wait for restart sequence.


(Blinking Decimals)
Decel Override

Cause: Both upper decimal points blinking. Drive stopped decelerating to avoid tripping into HF fault due to regenerative energy.



Remedy:

  • Status indication; drive is protecting itself.


CP
Control Pad

Cause: Speed is set using the up and down buttons on the front of the drive.



Remedy:

  • Normal Operation.


EI
External Current

Cause: Speed is controlled by a 4-20 mA signal wired to TB-25 and TB-2.



Remedy:

  • Normal Operation.


EU
External Voltage

Cause: Speed is controlled by a 0-10 VDC signal wired to TB-5 and TB-2.



Remedy:

  • Normal Operation.


JG
Jog Mode

Cause: The drive is in Jog mode, and the speed is set by Preset Speed #2 (Parameter 32).



Remedy:

  • Normal Operation.


OP
MOP (Motor Operated Pot)

Cause: Contacts wired to TB-13B and TB-13E are used to increase and decrease the drive speed.



Remedy:

  • Normal Operation.


Pr1 - Pr7
Preset Speeds

Cause: Speed is set by the indicated Preset Speed (Parameters 31-37).



Remedy:

  • Normal Operation.


How to Clear & Reset Lenze SCM Series Drive Faults

  1. Keypad Stop/Reset Key: Press the red STOP key on the integrated front keypad. If an overcurrent trip (F_OC) was triggered by a severe short or ground fault, ensure the motor has stopped completely before attempting to reset.
  2. Control Terminal Reset: If a digital input terminal (terminals 1, 2, 3A, or 3B) is programmed for external stop/reset via parameters P10–P12, toggle the external contact to clear the fault.
  3. EPM Module Verification: If receiving an EPM error (F_EP) or checksum error, power down the unit, verify that the blue Electronic Programming Module (EPM) is firmly seated in its front socket, and power up again.
  4. Serial Communication Interface: If equipped with the optional RS-485 serial communication module, send a software reset command via Modbus RTU control registers.
  5. Mains Line Power Cycle: Disconnect AC input mains power, wait at least 3 to 5 minutes until the 3-digit LED display turns off completely and internal intermediate capacitors discharge, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous residual electrical charge remains in the DC bus capacitors after disconnecting the AC supply line. Always wait at least 3 to 5 minutes after switching off power, and verify with a calibrated digital multimeter that the DC bus voltage measures safely below 50VDC before inspecting terminal screws, motor terminals (U, V, W), or dynamic braking resistors.