Lenze SM Vector Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and actionable troubleshooting procedures for the Lenze / AC Tech SMVector (SMV) frequency inverter series. Search or filter through the complete fault code directory below.

Sensorless Vector Inverter Power: 0.25 to 45 kW (0.33 to 60 HP) IP31 (NEMA 1) & IP65 (NEMA 4X) Enclosures
Power Range 0.25 – 45 kW (0.33 – 60 HP)
Supply Voltage 120V / 240V / 480V / 600V AC
Control Modes Sensorless Vector & Enhanced V/Hz
Operator Interface 4-Digit LED Keypad with EPM

Complete Lenze SMVector Drive Fault Code Directory

Use the search box in the table below to quickly find your fault code (e.g., type F_OF, F_HF, F_AL, or EPM).

Fault Code and MeaningCause and Remedy
F_AF
High Temperature fault

Cause:

Drive is too hot inside



Remedy:


  • Reduce drive load

  • Improve cooling


F_AL
Assertion Level fault

Cause:


  • Assertion Level switch is changed during operation

  • P120 is changed during operation

  • P100 or P121...P124 are set to a value other than 0 and P120 does not match the Assertion Level Switch.





Remedy:

Make sure the Assertion Level switch and P120 are both set for the type of input devices being used, prior to setting P100 or P121...P124.

Refer to 3.2.3 and P120.
F_bF
Personality fault

Cause:

Drive Hardware



Remedy:


  • Cycle Power

  • Power down and install EPM with valid data

  • Reset the drive back to defaults (P199 = 3, 4) and then re-program

  • If problem persists, contact factory technical support


F_cF
Control fault

Cause:

An EPM has been installed that is either blank or corrupted



Remedy:


  • Power down and install EPM with valid data

  • Reset the drive back to defaults (P199 = 3, 4) and then re-program

  • If problem persists, contact factory technical support


F_cF
Incompatible EPM fault

Cause:

An EPM has been installed that contains data from an incompatible parameter version



Remedy:

If problem persists, contact factory technical support
F_dbF
Dynamic Braking fault

Cause:

Dynamic braking resistors are overheating



Remedy:


  • Increase active decel time (P105, P126, P127).

  • Check mains voltage and P107


F_EF
External fault

Cause:


  • P121…P124 = 21 and that digital input has been opened.

  • P121…P124 = 22 and that digital input has been closed.





Remedy:


  • Correct the external fault condition

  • Make sure digital input is set properly for NC or NO circuit


F_F1
EPM fault

Cause:

EPM missing or defective



Remedy:

Power down and replace EPM
F_F2 ... F_F12
Internal faults

Cause:

Internal faults



Remedy:

Contact factory technical support
F_Fnr
Control Configuration Fault

Cause:


  • The drive is setup for REMOTE KEYPAD control (P100=2 or 5) but is not setup to communicate with a remote keypad

  • The drive is setup for NETWORK ONLY control (P100=3) but is not setup for network communications





Remedy:


  • Set P400 = 1, or P600 = 1

  • Set P400 or P600 to a valid network communications protocol selection


F_FoL
Loss of 4-20 mA signal fault

Cause:

4-20 mA signal (at TB-25) is below 2 mA (P163 = 1)



Remedy:

Check signal/signal wire
F_GF
OEM Defaults data fault

Cause:

Drive is powered up with P199 =1 and OEM settings in the EPM are not valid.



Remedy:

Install an EPM containing valid OEM Defaults data or change P199 to 0.
F_HF
High DC Bus Voltage fault

Cause:


  • Mains voltage is too high

  • Decel time is too short, or too much regen from motor





Remedy:


  • Check mains voltage and P107

  • Increase active decel time (P105, P126, P127) or install Dynamic Braking option


F_IL
Digital Input Configuration fault (P121...P124)

Cause:


  • More than one digital input set for the same function

  • Only one digital input configured for MOP function (Up, Down)

  • PID mode is entered with setpoint reference and feedback source set to the same analog signal

  • One of the digital inputs (P121…P124) is set to 10 and another is set to 11…14.

  • One of the digital inputs (P121…P124) is set to 11 or 12 and another is set to 13 or 14.

  • PID enabled in Vector Torque mode (P200 = 1 or 2 and P300 = 5)





Remedy:


  • Each setting can only be used once (except settings 0 and 3)

  • One input must be set to MOP Up, another must be set to MOP Down

  • Change PID setpoint reference (P121…P124) or feedback source (P201).

  • Reconfigure digital inputs

  • PID cannot be used in Vector Torque mode


F_JF
Remote keypad fault

Cause:

Remote keypad disconnected



Remedy:

Check remote keypad connections
F_LF
Low DC Bus Voltage fault

Cause:

Mains voltage too low



Remedy:

Check mains voltage
F_nId
No Motor ID fault

Cause:

An attempt was made to start the drive in Vector or Enhanced V/Hz mode prior to performing the Motor Auto-calibration



Remedy:

See P300…P399 for Drive Mode setup and calibration.
F_ntF
Module communication fault

Cause:

Communication failure between drive and Network Module.



Remedy:

Check module connections
F_nF1 ... F_nF9
Network Faults

Cause:

Refer to the module documentation for Causes and Remedies.



Remedy:

Refer to the module documentation.
F_OF
Output fault: Transistor fault

Cause:


  • Output short circuit

  • Acceleration time too short

  • Severe motor overload (Mechanical problem, Drive/motor too small)

  • Boost values too high

  • Excessive capacitive charging current of the motor cable

  • Failed output transistor





Remedy:


  • Check motor/motor cable

  • Increase P104, P125

  • Check machine / system

  • Verify drive/motor are proper size for application

  • Decrease P168, P169

  • Use shorter motor cables with lower charging current

  • Use low capacitance motor cables

  • Install reactor between motor and drive.

  • Contact factory technical support


F_OF1
Output fault: Ground fault

Cause:


  • Grounded motor phase

  • Excessive capacitive charging current of the motor cable





Remedy:


  • Check motor and motor cable

  • Use shorter motor cables with lower charging current


F_PF
Motor Overload fault

Cause:

Excessive motor load for too long



Remedy:


  • Verify proper setting of P108

  • Verify drive and motor are proper size for application


F_rF
Flying Restart fault

Cause:

Controller was unable to synchronize with the motor during restart attempt; (P110 = 5 or 6)



Remedy:

Check motor / load
F_SF
Single-Phase fault

Cause:

A mains phase has been lost



Remedy:

Check mains voltage
F_UF
Start fault

Cause:

Start command was present when power was applied (P110 = 0 or 2).



Remedy:


  • Must wait at least 2 seconds after power-up to apply Start command

  • Consider alternate starting method (refer to P110).


How to Clear & Reset Lenze SMVector Drive Faults

  1. Keypad Reset: Press the red STOP key on the front control panel. In a fault condition, pressing STOP clears the fault and places the drive into a STOP state. Note: If the drive trips on F_OF (Output Transistor Fault), an internal 30-second hardware lockout delay must expire before the reset is accepted.
  2. Digital Input Reset (Terminal 13A/B/C): If any control terminal (13A, 13B, or 13C) is assigned to Fault Reset via parameters P121, P122, or P123, toggle the assigned digital input to common (Terminal 4) to clear the fault.
  3. Fault Lockout (LC) Clearing: If the display shows LC (Fault Lockout due to 5 unsuccessful automatic restart attempts under parameter P110), the drive mandates an explicit manual keypad STOP command or digital reset signal.
  4. Fieldbus Communication Reset: When using an optional communication module (Modbus RTU, CANopen, DeviceNet, PROFIBUS DP, or EtherNet/IP), send a fault reset command or toggle the fault acknowledge bit in the network control word.
  5. Mains Power Disconnect: Disconnect AC line power, wait at least 3 to 5 minutes until the 4-digit LED display and internal bus charge indicators extinguish completely, and re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning: Hazardous residual electrical charge remains stored in the intermediate circuit capacitors after mains isolation. Always disconnect line supply voltage, wait a minimum of 5 minutes, and verify using a calibrated voltmeter that the DC bus voltage across terminals [+UG] and [-UG] (or across motor terminals U, V, and W) is strictly below 50V DC before undertaking any wiring, terminal inspection, or motor servicing.