Lenze SM Vector Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and actionable troubleshooting procedures for the Lenze / AC Tech SMVector (SMV) frequency inverter series. Search or filter through the complete fault code directory below.
Power Range
0.25 – 45 kW (0.33 – 60 HP)
Supply Voltage
120V / 240V / 480V / 600V AC
Control Modes
Sensorless Vector & Enhanced V/Hz
Operator Interface
4-Digit LED Keypad with EPM
Complete Lenze SMVector Drive Fault Code Directory
Use the search box in the table below to quickly find your fault code (e.g., type F_OF, F_HF, F_AL, or EPM).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| F_AF High Temperature fault | Cause: Drive is too hot inside Remedy:
|
| F_AL Assertion Level fault | Cause:
Remedy: Make sure the Assertion Level switch and P120 are both set for the type of input devices being used, prior to setting P100 or P121...P124. Refer to 3.2.3 and P120. |
| F_bF Personality fault | Cause: Drive Hardware Remedy:
|
| F_cF Control fault | Cause: An EPM has been installed that is either blank or corrupted Remedy:
|
| F_cF Incompatible EPM fault | Cause: An EPM has been installed that contains data from an incompatible parameter version Remedy: If problem persists, contact factory technical support |
| F_dbF Dynamic Braking fault | Cause: Dynamic braking resistors are overheating Remedy:
|
| F_EF External fault | Cause:
Remedy:
|
| F_F1 EPM fault | Cause: EPM missing or defective Remedy: Power down and replace EPM |
| F_F2 ... F_F12 Internal faults | Cause: Internal faults Remedy: Contact factory technical support |
| F_Fnr Control Configuration Fault | Cause:
Remedy:
|
| F_FoL Loss of 4-20 mA signal fault | Cause: 4-20 mA signal (at TB-25) is below 2 mA (P163 = 1) Remedy: Check signal/signal wire |
| F_GF OEM Defaults data fault | Cause: Drive is powered up with P199 =1 and OEM settings in the EPM are not valid. Remedy: Install an EPM containing valid OEM Defaults data or change P199 to 0. |
| F_HF High DC Bus Voltage fault | Cause:
Remedy:
|
| F_IL Digital Input Configuration fault (P121...P124) | Cause:
Remedy:
|
| F_JF Remote keypad fault | Cause: Remote keypad disconnected Remedy: Check remote keypad connections |
| F_LF Low DC Bus Voltage fault | Cause: Mains voltage too low Remedy: Check mains voltage |
| F_nId No Motor ID fault | Cause: An attempt was made to start the drive in Vector or Enhanced V/Hz mode prior to performing the Motor Auto-calibration Remedy: See P300…P399 for Drive Mode setup and calibration. |
| F_ntF Module communication fault | Cause: Communication failure between drive and Network Module. Remedy: Check module connections |
| F_nF1 ... F_nF9 Network Faults | Cause: Refer to the module documentation for Causes and Remedies. Remedy: Refer to the module documentation. |
| F_OF Output fault: Transistor fault | Cause:
Remedy:
|
| F_OF1 Output fault: Ground fault | Cause:
Remedy:
|
| F_PF Motor Overload fault | Cause: Excessive motor load for too long Remedy:
|
| F_rF Flying Restart fault | Cause: Controller was unable to synchronize with the motor during restart attempt; (P110 = 5 or 6) Remedy: Check motor / load |
| F_SF Single-Phase fault | Cause: A mains phase has been lost Remedy: Check mains voltage |
| F_UF Start fault | Cause: Start command was present when power was applied (P110 = 0 or 2). Remedy:
|
How to Clear & Reset Lenze SMVector Drive Faults
- Keypad Reset: Press the red STOP key on the front control panel. In a fault condition, pressing STOP clears the fault and places the drive into a STOP state. Note: If the drive trips on F_OF (Output Transistor Fault), an internal 30-second hardware lockout delay must expire before the reset is accepted.
- Digital Input Reset (Terminal 13A/B/C): If any control terminal (13A, 13B, or 13C) is assigned to
Fault Resetvia parameters P121, P122, or P123, toggle the assigned digital input to common (Terminal 4) to clear the fault. - Fault Lockout (LC) Clearing: If the display shows LC (Fault Lockout due to 5 unsuccessful automatic restart attempts under parameter P110), the drive mandates an explicit manual keypad STOP command or digital reset signal.
- Fieldbus Communication Reset: When using an optional communication module (Modbus RTU, CANopen, DeviceNet, PROFIBUS DP, or EtherNet/IP), send a fault reset command or toggle the fault acknowledge bit in the network control word.
- Mains Power Disconnect: Disconnect AC line power, wait at least 3 to 5 minutes until the 4-digit LED display and internal bus charge indicators extinguish completely, and re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual electrical charge remains stored in the intermediate circuit capacitors after mains isolation. Always disconnect line supply voltage, wait a minimum of 5 minutes, and verify using a calibrated voltmeter that the DC bus voltage across terminals [+UG] and [-UG] (or across motor terminals U, V, and W) is strictly below 50V DC before undertaking any wiring, terminal inspection, or motor servicing.