Lenze i550 Protec drive

Home / Lenze / Lenze i550 Protec drive

Lenze i550 Protec Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip error causes, and step-by-step troubleshooting procedures for the Lenze i550 Protec decentralized inverter series. Search or filter through the complete diagnostic directory below.

Decentralized Drive (IP66 / NEMA 4X) Power: 0.37 to 22 kW (0.5 to 30 HP) Integrated Safe Torque Off (STO)
Power Range 0.37 – 22 kW (0.5 – 30 HP)
Supply Voltage 1~ 120V / 1~/3~ 230V / 3~ 400–480V
Control Modes V/f, Sensorless Vector & PM Motor
Operator Interface Keypad / WLAN / USB Diagnostic

Complete Lenze i550 Protec Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type 0x2310, 0x3210, 0x4210, or Overcurrent).

Fault Code and MeaningCause and Remedy
8784 (0x2250)

CiA: Continuous over current (internal)

Cause:

  • Continuous overcurrent on the inverter/motor side.

  • Overcurrent at the brake chopper (brake transistor).

  • DC bus relay has not been closed due to a malfunction.




Remedy:

  • Check motor and wiring for short circuits.

  • Check brake resistor and wiring.

  • Check motor switching.

  • Check settings of the motor data.


8992 (0x2320)

Short circuit or earth leakage at the motor end

Cause:

  • Short circuit/earth fault of motor cable.

  • Capacitive charging current of the motor cable too high.




Remedy:

  • Check motor cable.

  • Check length of the motor cable.

  • Use shorter or lower-capacitance motor cable.


9024 (0x2340)

Short circuit at the motor end

Cause:

  • Short circuit of motor cable.




Remedy:

  • Check motor cable for short circuit.


9040 (0x2350)

CiA: i²xt overload (thermal state)

Cause:

  • Motor thermally overloaded, e.g. by an impermissible continuous current or by frequent or too long acceleration processes.




Remedy:

  • Check drive sizing.

  • Check machine/driven mechanics for excessive load.

  • Check settings of the motor data.

  • Reduce values for slip compensation (P315.01, P315.02) and oscillation damping (P318.01, P318.02).


9090 (0x2382)

Fault - Device utilization (ixt) too high

Cause:

  • Device utilisation (ixt) too high by frequent and too long acceleration processes.




Remedy:

  • Check drive sizing.

  • Reduce the maximum current of the inverter (P324.00).

  • In case of high mass inertias, reduce maximum current of the inverter (P324.00) to 150%.


9091 (0x2383)

Warning - Device utilization (ixt) too high

Cause:

  • Device utilisation (ixt) too high by frequent and too long acceleration processes.




Remedy:

  • Check drive dimensioning.


9095 (0x2387)

Clamp responded too often

Cause:

  • Maximum current of the axis has been reached too often in succession.




Remedy:

  • Select a flatter speed ramp.

  • Reduce the load.

  • Set Imax controller more dynamically.


9096 (0x2388)

SL-PSM stall detection active

Cause:

  • Overload of the motor with sensorless control for synchronous motors (SL-PSM).




Remedy:

  • Reduce load at the axis.

  • Check settings of the SL-PSM parameters.


9098 (0x238A)

Maximum current reached

Cause:

  • The actual current (P103.00) is equal to or higher than the max. current (P324.00).




Remedy:

  • Reduce the load on the motor or change the settings for the maximum current (P324.00).


12576 (0x3120)

Mains phase fault

Cause:

  • Mains phase failure.




Remedy:

  • Check wiring of the mains connection.

  • Check fuses.


12672 (0x3180)

UPS operation active

Cause:

  • Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided.




Remedy:

  • Switch back to operation with regular mains voltage.


12816 (0x3210)

Fault - DC bus overvoltage

Cause:

  • DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage.




Remedy:

  • Reduce dynamic performance of the load profile.

  • Check mains voltage.

  • Check settings for brake energy management.

  • Connect brake resistor to the power unit and activate the integrated brake chopper (P706.01 = 0).


12817 (0x3211)

DC bus overvoltage warning

Cause:

  • DC-bus voltage has exceeded the warning threshold due to too high braking energy or too high mains voltage.




Remedy:

  • Reduce dynamic performance of the load profile.

  • Check mains voltage.

  • Check settings for brake energy management.

  • Connect brake resistor and activate integrated brake chopper.


12832 (0x3220)

Fault - DC bus undervoltage

Cause:

  • DC-bus voltage has fallen below the error threshold for undervoltage.




Remedy:

  • Check mains voltage.

  • Check DC-bus voltage (P105.00).

  • Check mains settings.

  • Check fuses.


12833 (0x3221)

DC bus undervoltage warning

Cause:

  • DC-bus voltage has fallen below the warning threshold for undervoltage.




Remedy:

  • Check mains voltage.

  • Check DC-bus voltage (P105.00).

  • Check mains settings.

  • Check fuses.


12834 (0x3222)

DC-bus voltage too low for power up

Cause:

  • The input voltage is too low to switch on the inverter.




Remedy:

  • Check mains voltage.

  • Check mains settings.

  • Check fuses.


16912 (0x4210)

Fault - Power unit overtemperature

Cause:

  • The heatsink temperature of the power unit has exceeded the fixed error threshold (100 °C).

  • Ambient temperature too high.

  • Fan or ventilation slots are polluted.

  • Fan is defective.




Remedy:

  • Provide for a sufficient cooling of the device.

  • Clean fan and ventilation slots. If required, replace fan.

  • Reduce switching frequency (P305.00).


17024 (0x4280)

Fault - Heat sink temperature sensor

Cause:

  • Sensor for the temperature monitoring of the power unit is defective. Risk of overheating.




Remedy:

  • Hardware error: it is necessary to contact the manufacturer, since the device must be replaced.


17025 (0x4281)

Heat sink fan warning

Cause:

  • Warning of the heatsink fan.




Remedy:

  • Clean fan and ventilation slots. If required, replace fan.


17029 (0x4285)

PU overtemperature warning

Cause:

  • The heatsink temperature has exceeded the warning threshold.

  • Ambient temperature too high.

  • Fan or ventilation slots are polluted or fan defective.




Remedy:

  • Provide for a sufficient cooling of the device.

  • Clean fan and ventilation slots.

  • If required, replace fan.


17168 (0x4310)

Motor overtemperature

Cause:

  • The motor temperature sensor measures a too high motor temperature.

  • Motor too hot by impermissibly high currents.

  • Motor too hot by frequent and too long acceleration processes.




Remedy:

  • Check drive dimensioning.

  • Check motor temperature sensor and wiring.


20754 (0x5112)

External supply voltage critical

Cause:

  • External supply voltage failed or too low.




Remedy:

  • Check optional external 24V voltage supply (terminal X3/24E), if connected.

  • Check mains voltage.


20864 (0x5180)

Overload 24 V supply

Cause:

  • Output current at the 24V output or at the digital outputs too high.




Remedy:

  • Check 24V output and digital outputs for earth fault or overload.


21376 (0x5380)

OEM hardware incompatible

Cause:

  • The control unit (OEM hardware) is not compatible with the power unit (OEM hardware).




Remedy:

  • Use compatible hardware.

  • Contact the OEM.


24970 (0x618A)

Warning - Internal fan

Cause:

  • Warning of the internal fan.




Remedy:

  • Check/replace internal fan.


25216 (0x6280)

Trigger/functions connected incorrectly

Cause:

  • The assignment directives have not been observed (e.g., Enable inverter or Run function missing in flexible I/O).

  • Conflict between start functions (CW/CCW).




Remedy:

  • Check and correct the assignment of the triggers to the functions.


25217 (0x6281)

User-defined fault 1

Cause:

  • "Activate fault 1" function was activated via the trigger selected.




Remedy:

  • Eliminate error cause and then reset error.


25232 (0x6290)

Warning invert rotation

Cause:

  • Negative setpoint selection with an active limitation of rotation.

  • "Reverse rotational direction" function requested with active limitation.




Remedy:

  • Check setpoint selection and trigger.

  • Check setting in P304.00.


25233 (0x6291)

Maximum allowed troubles exceeded

Cause:

  • The number of permitted restart attempts after a fault was exceeded.




Remedy:

  • Check and eliminate the fault.


25249 (0x62A1)

Network: user fault 1

Cause:

  • The "Activate fault 1" function was triggered via the NetWordIN1 data word.




Remedy:

  • Eliminate error cause and then reset error.


25265 (0x62B1)

NetWordIN1 configuration incorrect

Cause:

  • Two bits of the NetWordIN1 data word were assigned to the same function.




Remedy:

  • Check and correct configuration of the NetWordIN1 data word.


25266 (0x62B2)

Changed device ID not yet active

Cause:

  • The device ID of the device was changed manually.




Remedy:

  • Execute device command "Save user data" (P700.03).

  • Switch inverter off and on again.


25505 (0x63A1)

CU: load error ID tag

Cause:

  • Calibration data of the control unit not compatible or faulty.




Remedy:

  • Update firmware of the inverter to the most recent version.

  • If error persists, replace control unit or device.


25507 (0x63A3)

Power unit unknown

Cause:

  • The power unit installed is not supported by the software.




Remedy:

  • Update firmware of the inverter to the most recent version.


28800 (0x7080)

Assertion level monitoring (Low/High)

Cause:

  • The last setting of the connection level differs from the saved setting.




Remedy:

  • Execute device command "Save user data".

  • Switch inverter off and on again.


28801 (0x7081)

Fault - Analog input 1

Cause:

  • The monitoring function of the input signal configured for analog input 1 has been triggered.




Remedy:

  • Check input signal at analog input 1.

  • Check configuration of the monitoring function.


28833 (0x70A1)

Analog output 1 fault

Cause:

  • Open circuit or short circuit at analog output 1.




Remedy:

  • Check wiring of analog output 1.

  • Check definition of the output range.


28961 (0x7121)

Fault - Pole position identification

Cause:

  • Too many deviations during the pole position identification.

  • Rated motor current too high or too low.




Remedy:

  • Check setting of the motor data.

  • Ensure that the motor is at a standstill during the process.

  • Ensure motor and inverter match in terms of power.


29056 (0x7180)

Motor overcurrent

Cause:

  • The motor current has exceeded the warning/error threshold monitoring set.




Remedy:

  • Check motor load.

  • Check drive dimensioning.

  • Check warning/error threshold settings.


29445 (0x7305)

Encoder open circuit

Cause:

  • The encoder signal loss monitoring function has detected a failure of the encoder signal.




Remedy:

  • Check the encoder connection.

  • Check encoder cable for wire breakage.

  • Check encoder current supply.


30336 (0x7680)

Memory module is full

Cause:

  • The memory module contains too many parameter settings.




Remedy:

  • Execute "Save user data" again to reinitialise.


30337 (0x7681)

Memory module not present

Cause:

  • The inverter memory module was removed.




Remedy:

  • Switch off inverter.

  • Plug the memory module into the inverter.

  • Switch the inverter on again.


30352 (0x7690)

EPM firmware version incompatible

Cause:

  • The parameter settings saved in the memory module are incompatible with the firmware version.




Remedy:

  • Execute device command "Load default settings".

  • Or execute "Save user data" to overwrite.


30354 (0x7692)

EPM data: new firmware type detected

Cause:

  • The parameter settings saved in the memory module do not match the inverter hardware.




Remedy:

  • Check parameter settings.

  • Reset error.

  • Execute "Save user data".


33042 (0x8112)

Network - Time-out explicit message

Cause:

  • Within the time-out period for explicit messages, no "explicit message" was received.

  • Connection to scanner interrupted.




Remedy:

  • Check cables and terminals.

  • Check requested package interval (RPI).

  • Increase time limit for explicit messages in the scanner.


33044 (0x8114)

Network - Overall communication time-out

Cause:

  • EtherNet/IP or Modbus TCP/IP communication time-out exceeded.




Remedy:

  • Check cables and terminals.

  • Connect network cable.


33154 (0x8182)

CAN: bus off

Cause:

  • Too many faulty frames have been received.

  • Defective cable (loose contact).

  • Two nodes with the same node address.




Remedy:

  • Check wiring of the network.

  • Check bus terminating resistor.

  • Assign a unique node address to each node.

  • Eliminate EMC interferences.


33414 (0x8286)

Network - PDO mapping error

Cause:

  • Invalid PDO assignment by the master.

  • Internal PDO assignment was changed and does not comply with configuration.




Remedy:

  • Check data mapping in the master and slave.


33553 (0x8311)

Torque limit reached

Cause:

  • Motor has reached the torque limit (positive or negative).




Remedy:

  • Observe load requirements.

  • Reduce motor load.

  • Check set torque limits and sources.


65282 (0xFF02)

Fault - Brake resistor overload

Cause:

  • The calculated thermal load of the brake resistor has reached the error threshold.




Remedy:

  • Check drive dimensioning.

  • Check settings for the brake energy management.


65285 (0xFF05)

Safety option - Internal error

Cause:

  • The safety module or safety circuit was detected as defective.




Remedy:

  • Hardware error: contact manufacturer. Device must be replaced.

  • Note: The safety module must not be removed or repaired by the user.


65286 (0xFF06)

Motor overspeed

Cause:

  • The motor speed has reached the error threshold for overspeed.




Remedy:

  • Adapt the maximum motor speed (P322.00) and the warning threshold.


65289 (0xFF09)

Motor phase missing

Cause:

  • A failure of several motor phases has been detected.




Remedy:

  • Check wiring between inverter and motor.

  • Adapt settings for motor phase failure detection if false tripping occurs.


65305 (0xFF19)

Motor parameter identification fault

Cause:

  • During automatic identification of the motor, an error has occurred.




Remedy:

  • Set motor data so that they comply with data on the motor nameplate.

  • Check wiring of the motor.


65366 (0xFF56)

Maximum motor frequency reached

Cause:

  • The limitation of the maximum motor speed is active.

  • Maximum output frequency of inverter reached.




Remedy:

  • Check application.


65393 (0xFF71)

Wrong password

Cause:

  • A wrong password has been entered several times.




Remedy:

  • Wait until the blocking time has elapsed and then enter the correct password.


65395 (0xFF73)

Fatal Error

Cause:

  • Error when reading the data from the control unit.




Remedy:

  • Switch inverter off and on again.

  • If error persists, contact manufacturer (replace device).


65413 (0xFF85)

Keypad full control active

Cause:

  • If the "Keypad Full Control" control mode is active.




Remedy:

  • To exit the control mode, press the keypad key CTRL.


How to Clear & Reset Lenze i550 Protec Drive Faults

  1. Keypad Reset: Press the red Stop / Reset key on the optional pluggable keypad or front diagnostic unit. Ensure the drive run command is withdrawn before attempting manual reset.
  2. Digital Input Reset (DI): If mapped in parameter 0x2631:004 (Fault reset / P400.04), apply a positive edge trigger (0 → 1 pulse) to the assigned digital input terminal (DI1–DI5).
  3. Lenze EASY Starter / Mobile App: Connect via the USB diagnostic interface module or plug-in WLAN module, launch EASY Starter or the Lenze Smart App, view the active fault history in the Diagnostics tab, and click “Reset Error”.
  4. Fieldbus Control Word: Set Bit 7 (Fault Reset) in the standard control word from 0 to 1 via IO-Link, CANopen, Modbus RTU, PROFIBUS, PROFINET, or EtherCAT networks.
  5. Power Cycle: Disconnect AC line power, wait at least 3 to 5 minutes until internal LEDs go dark and DC bus capacitors safely discharge, then reclose incoming power.
⚠️ High-Voltage Electrical Safety Warning: Before loosening housing screws or opening the IP66 / NEMA 4X connection chamber of the Lenze i550 Protec drive, disconnect main power and wait a minimum of 3 to 5 minutes. Always use a calibrated digital multimeter to verify that intermediate DC bus voltage has dropped below 50VDC before inspecting power terminals or motor leads (U, V, W).