Lenze SCL Series Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, LED display diagnostic messages, and step-by-step troubleshooting procedures for the Lenze AC Tech SCL sub-micro inverter series. Search or filter through the complete fault code directory below.

Sub-Micro Inverter (IP20) Power: 0.25 to 2.2 kW (0.33 to 3 HP) Integrated EMC / RFI Line Filter
Power Range 0.25 – 2.2 kW (0.33 – 3 HP)
Supply Voltage 208–240V AC (1-Phase)
Control Modes V/f (Volts per Hertz) Control
Operator Interface LED Display & Keypad / EPM

Complete Lenze SCL Series Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type HF, OF, PF, or Overcurrent).

Fault Code and MeaningCause and Remedy
AF
High Temp. Fault

Cause: Ambient temperature is too high; Cooling fan has failed (if equipped).



Remedy:

  • Check ventilation and ambient temperature.

  • Check cooling fan operation.


CF
Control Fault

Cause: A blank EPM, or an EPM with corrupted data has been installed.



Remedy:

  • Perform a factory reset using Parameter 48 - PROGRAM SELECTION.


cF
Incompatibility Fault

Cause: An EPM with an incompatible parameter version has been installed.



Remedy:

  • Remove the EPM.

  • Or perform a factory reset (Parameter 48) to change the parameter version of the EPM to match the drive.


dF
Dynamic Braking Fault

Cause: The drive has sensed that the dynamic braking resistors are overheating and shuts down to protect the resistors.



Remedy:

  • Check load and braking cycle requirements.


EF
External Fault

Cause: One of the TB-13 terminals is set as an External Fault input and that terminal is open with respect to TB-11.



Remedy:

  • Refer to Parameters 10, 11 and 12.

  • Check external wiring/interlocks.


GF
Data Fault

Cause: User data and OEM defaults in the EPM are corrupted.



Remedy:

  • Attempt factory reset.

  • Replace EPM if necessary.


HF
High DC Bus Voltage Fault

Cause: Line voltage is too high; Deceleration rate is too fast; Over-hauling load.



Remedy:

  • Check input line voltage.

  • Decrease deceleration rate.

  • Dynamic braking may be required for fast deceleration or overhauling loads.


JF
Remote Keypad Fault

Cause: The communication link between the drive and the optional Remote Keypad has been lost.



Remedy:

  • Check for proper wiring and/or noise.


LF
Low DC Bus Voltage Fault

Cause: Line voltage is too low.



Remedy:

  • Check input line voltage.

  • Wait for voltage to return to normal level (Fault cannot be cleared until voltage is normal).


OF
Output Transistor Fault

Cause: Phase to phase or phase to ground short circuit on the output; Boost settings are too high; Acceleration rate is too fast; Failed output transistor.



Remedy:

  • Check motor and cabling for shorts.

  • Adjust Boost settings.

  • Reduce acceleration rate.


PF
Current Overload Fault

Cause: VFD is undersized for the application; Mechanical problem with the driven equipment.



Remedy:

  • Verify drive sizing vs motor load.

  • Check driven equipment for mechanical binding or issues.


UF
Start Fault

Cause: Start command was present when the drive was powered up.



Remedy:

  • Must wait 2 seconds after power-up to apply Start command if START METHOD is set to NORMAL.


F1
EPM Fault

Cause: The EPM is missing or damaged.



Remedy:

  • Install valid EPM.


FC, F2-F9, Fo
Internal Faults

Cause: The control board has sensed a problem.



Remedy:

  • Consult factory.


br
DC Braking

Cause: The DC braking circuit is activated.



Remedy:

  • Status indication only.


cE
Parameter Version Warning

Cause: An EPM with a different parameter version is installed and an attempt is made to change parameter settings without performing the TRANSLATE function.



Remedy:

  • Refer to PROGRAM SELECTION (Parameter 48).


CL
Current Limit

Cause: The output current has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive is reducing output frequency.



Remedy:

  • If drive remains in CURRENT LIMIT too long, it can trip into PF fault.

  • Check load conditions.


Er
Error

Cause: Invalid data has been entered or an invalid command was attempted.



Remedy:

  • Check data range and retry.


GE
OEM Mode Warning

Cause: Attempt made to change OEM default settings when the drive is operating in the OEM mode.



Remedy:

  • Refer to Parameter 48.


GF
OEM Data Corruption

Cause: If displayed when RESET OEM attempted: OEM defaults in EPM corrupted. If displayed upon power-up: OEM defaults and user settings in EPM corrupted.



Remedy:

  • Refer to Section 13.2 of manual.


LC
Fault Lockout

Cause: The drive has failed three restart attempts.



Remedy:

  • Requires a manual reset.


SE
Serial Active

Cause: The optional remote keypad is active as the user interface instead of the buttons on front of the drive.



Remedy:

  • Refer to Parameter 14 (CONTROL).


SP
Start Pending

Cause: Blinks during the interval between restart attempts.



Remedy:

  • Wait for restart sequence.


(Blinking Decimals)
Decel Override

Cause: Both upper decimal points blinking. Drive stopped decelerating to avoid tripping into HF fault due to regenerative energy.



Remedy:

  • Status indication; drive is protecting itself.


CP
Control Pad

Cause: Speed is set using the up and down buttons on the front of the drive.



Remedy:

  • Normal Operation.


EI
External Current

Cause: Speed is controlled by a 4-20 mA signal wired to TB-25 and TB-2.



Remedy:

  • Normal Operation.


EU
External Voltage

Cause: Speed is controlled by a 0-10 VDC signal wired to TB-5 and TB-2.



Remedy:

  • Normal Operation.


JG
Jog Mode

Cause: The drive is in Jog mode, and the speed is set by Preset Speed #2 (Parameter 32).



Remedy:

  • Normal Operation.


OP
MOP (Motor Operated Pot)

Cause: Contacts wired to TB-13B and TB-13E are used to increase and decrease the drive speed.



Remedy:

  • Normal Operation.


Pr1 - Pr7
Preset Speeds

Cause: Speed is set by the indicated Preset Speed (Parameters 31-37).



Remedy:

  • Normal Operation.


How to Clear & Reset Lenze SCL Series Drive Faults

  1. Keypad Stop/Reset: Press the red STOP key on the front keypad faceplate. If configured for keypad stop, this clears latched trips provided the error cause is resolved.
  2. Digital Input Reset: If one of the digital terminal inputs (TB-13A, TB-13B, or TB-13C) is configured for external reset in parameters 10, 11, or 12, assert a contact closure to clear the fault.
  3. Start/Stop Command Cycling: For certain overload (PF) or line fault conditions, open the run enable contact (terminal TB-1 or configured start circuit) and reclose after fault correction.
  4. Electronic Programming Module (EPM): If an F1 or GF memory corruption code occurs, power off the unit, reseat or replace the removable blue EPM chip, or reflash parameters using the EPM programmer.
  5. Mains Line Power Cycle: Disconnect AC line input power, wait at least 3 minutes until the LED display extinguishes completely (allowing internal capacitor discharge), and reapply AC power.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect incoming AC line power and wait at least 3 minutes for internal filter and DC bus capacitors to completely discharge. Verify that intermediate DC bus voltage measures strictly below 50V DC with a calibrated voltmeter before removing wiring covers, touching terminal blocks (L1, L2, PE), or servicing motor output terminals (U, V, W).