Lenze MC1000 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze AC Tech MC1000 industrial drive series. Search or filter through the complete fault code directory below.
Power Range
0.18 – 110 kW (0.25 – 150 HP)
Supply Voltage
120V / 240V / 480V / 590V AC
Control Modes
V/Hz Control & PID Loop
Operator Interface
16-Character LCD Keypad / Modbus
Complete Lenze MC1000 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OUTPUT, HIGH VOLTAGE, OVERLOAD, or HIGH TEMP).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OUTPUT Output transistor fault: Output current exceeded 200% of drive rating. | Cause:
Remedy: Check motor wiring and motor for shorts. Check drive settings. |
| LO VOLTS Low DC Bus Voltage fault: DC bus voltage below 60% of normal. | Cause: Low line voltage. Remedy: Check AC input power. |
| HI VOLTS High DC Bus Voltage fault: DC bus voltage above 120% of normal. | Cause:
Remedy: Check input voltage. Adjust deceleration time. |
| HI TEMP Temperature fault: Internal drive temperature too high. | Cause:
Remedy: Check cooling fans and cabinet ventilation. |
| OVERLOAD Current Overload fault: Output current rating exceeded for too long. | Cause:
Remedy: Check mechanical load and motor sizing. (Note: 3-minute delay before reset is possible). |
| PWR TRAN Power Transient fault: Low line voltage. | Cause: AC line dipped or sagged. Remedy: Check mains supply stability. |
| PWR SAG Power Sag fault: Control board voltage is below tolerance. | Cause:
Remedy: Perform a factory reset using Parameter 65-PROGRAM. This will update the software and allow the fault to be reset. |
| LANGUAGE Language fault: Selected language not present. | Cause:
Remedy: Replace or reinstall EEPROM. |
| EXTERNAL External fault: TB-13D is open or closed to TB-2, depending on the setting of Parameter 50 - TB13D. | Cause: External device triggered fault or wiring issue. Remedy:
|
| DB ERROR Dynamic Brake fault: DB circuit has sensed a resistor overload. | Cause: The DB duty cycle is too high, causing the resistors to overheat. Remedy: Reduce duty cycle or check resistor sizing. |
| CONTROL Control Board fault: New software has been installed that is different from the previous version. | Cause: Software/Hardware mismatch. Remedy: Perform a factory reset using Parameter 65-PROGRAM. This will update the software and allow the fault to be reset. |
| INTERNAL / INTERN (#) Internal fault: The micro-processor has sensed a problem. | Cause:
Remedy: Check control wiring shielding. |
| FOLLOWER Loss of Follower fault: 4-20 mA signal at TB-5B is below 2 mA. | Cause: Signal loss on input. Remedy: Parameter 55 - TB5B LOSS is set to FAULT. Check signal source. |
| Blank Display / TESTING The power supply has shut down. (Drive will not run). | Cause: This can be the result of clogged or failed heatsink fans. Remedy:
|
How to Clear & Reset Lenze MC1000 Drive Faults
- Keypad STOP Key Reset: Press the red STOP key on the front keypad. If an OUTPUT transistor fault has tripped the drive, an internal 30-second thermal safety delay must expire before the STOP key can successfully clear the message.
- Digital Terminal Strip Reset: If any terminal among TB-13A, TB-13B, TB-13C, or TB-13D is configured for external reset via Parameters 48–50, momentary contact closure to terminal TB-11 will reset the drive to a stopped state.
- RS-485 Serial Communication: Send a remote trip reset command across the built-in EIA-485 serial communications network using standard Modbus RTU protocol registers.
- Automatic Restart (Parameter 04): If enabled under Parameter 04, the inverter will automatically attempt to clear transient line sags and power dips and restart unattended equipment after an engineered time delay.
- Line Power Cycling: Disconnect AC input mains power, wait at least 5 minutes until the 16-character alphanumeric display is completely blank and the high-voltage bus bleeder circuit discharges, then re-apply line power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual electrical charge remains stored in internal intermediate DC bus capacitors even after incoming AC power is disconnected. Always wait a minimum of 5 minutes after de-energizing the unit, and verify with a calibrated DC voltmeter that voltage across DC bus/braking terminals is strictly below 50VDC before inspecting motor leads (TB-1, TB-2, TB-3) or touching internal chassis components.