Lenze 8200 Motec drive

Home / Lenze / Lenze 8200 Motec drive

Lenze 8200 Motec Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip error messages, and step-by-step troubleshooting procedures for the Lenze 8200 Motec decentralized frequency inverter series. Search or filter through the complete fault code directory below.

Decentralized Drive (IP65 / NEMA 4X) Power: 0.25 to 7.5 kW (0.33 to 10 HP) Motor & Wall Mountable
Power Range 0.25 – 7.5 kW (0.33 – 10 HP)
Supply Voltage 1~ 230V / 3~ 400–500V AC
Control Modes V/f (Linear/Quad) & SLVC
Operator Interface Keypad XT / GDC Software

Complete Lenze 8200 Motec Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OU, OH, or Overcurrent).

Fault Code and MeaningCause and Remedy
nDEr (0)
No fault

Cause: -


Remedy: -
CCr (71)
System failure

Cause:

  • Strong interference injections on the control cables.

  • Earth loops in the wiring.


Remedy:

  • Shield control cable.


CE0 (61)
Communication error on AIF

Cause: Faulty transmission of control commands via AIF.


Remedy:

  • Insert the communication module properly into the diagnosis terminal.


CE1 (62)
Communication error on CAN-IN1 (sync control)

Cause: CAN-IN1 object receives faulty data or communication is interrupted.


Remedy:

  • Check plug connection of bus module ↔ FIF.

  • Check sender.

  • Increase monitoring time in C0357/1, if necessary.


CE4 (65)
BUS-OFF

Cause: Controller has received too many faulty telegrams via the system bus and has been disconnected.


Remedy:

  • Check whether bus termination is available.

  • Check shielding of the cables.

  • Check PE connection.

  • Check bus load, reduce the baud rate if necessary.


LP1 (32/182)
Error in motor phase

Cause:

  • Failure of one/several motor phases.

  • Motor current too low.


Remedy:

  • Check motor supply cables.

  • Check Umin boost.

  • Connect motor with a corresponding power or adapt motor with C0599.


LU (-)
DC bus undervoltage

Cause:

  • Mains voltage too low.

  • Voltage in DC-bus connection too low.

  • 400 V controller is connected to 240 V mains.


Remedy:

  • Check mains voltage.

  • Check power supply module.

  • Connect controller to correct mains voltage.


OC1 (11)
Short circuit

Cause:

  • Short circuit.

  • Capacitive charging current of the motor cable too high.


Remedy:

  • Search for cause of short circuit; check motor cable.

  • Check brake resistor and cable to brake resistor.

  • Use shorter/low-capacitance motor cable.


OH (50)
Heatsink temperature > +85 °C

Cause: Ambient temperature is too high.


Remedy:

  • Allow controller to cool and provide better ventilation.


OH4 (54)
Controller overtemperature

Cause: Controller too hot inside.


Remedy:

  • Reduce controller load.

  • Improve cooling.

  • Check fan in the controller.


Pr5 (79)
Internal fault

Cause: EEPROM is defective.


Remedy:

  • Contact Lenze.


Sd5 (85)
Open circuit - analog input 1

Cause: Current at analog input < 4 mA at setpoint range 4 ... 20 mA.


Remedy:

  • Close circuit at analog input.


How to Clear & Reset Lenze 8200 Motec Drive Faults

  1. Keypad Reset: Press the STOP / RESET key on the plug-in Keypad XT (or diagnostic handheld terminal). If the drive is operating in local manual mode, ensure the start/run condition is inactive before executing the reset.
  2. Terminal Input Reset (TRIP-RESET): Apply a low-to-high signal transition (0 → 1 edge pulse) on the digital input terminal assigned to the TRIP-RESET function (configured via code C0410 on input terminals E1 through E4).
  3. Global Drive Control (GDC) PC Tool: Connect your PC to the drive via the diagnostic interface / LECOM optical or RS232/RS485 adapter, open Lenze Global Drive Control (GDC / GDC easy), and click “TRIP-Reset” in the drive status window.
  4. Fieldbus Control Word: Write Bit 11 (TRIP-RESET) from 0 to 1 in the automation control word across connected fieldbus modules (PROFIBUS-DP, CANopen, DeviceNet, or AS-Interface).
  5. Mains Power Cycle: Switch off the main AC line power, wait until all diagnostic LEDs on the unit turn off completely (approx. 3 to 5 minutes to permit internal capacitor discharge), and reapply power.
⚠️ High-Voltage Electrical Safety Warning: After switching off the mains power supply, wait at least 3 minutes for intermediate DC bus capacitors to discharge. Verify with a calibrated DC voltmeter that voltage across DC bus terminals (+UG and -UG) is below 50V DC before loosening housing screws, opening the IP65 enclosure cover, or touching power terminals (L1, L2, L3, PE, U, V, W).