Lenze 9300 Vector Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze 9300 Vector frequency inverter series. Search or filter through the complete fault code directory below.

High-Performance Vector Inverter Power: 0.37 to 90 kW (0.5 to 120 HP) Integrated Function Blocks & System Bus
Power Range 0.37 – 90 kW (0.5 – 120 HP)
Supply Voltage 380–480V AC (3-Phase)
Control Modes Vector Control, Closed-Loop & V/f
Operator Interface Keypad XT / Global Drive Control (GDC)

Complete Lenze 9300 Vector Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OU, OH, or Overcurrent).

Fault Code and MeaningCause and Remedy
0011 / OC1

Overcurrent in motor cable
(Ia > 2.25 x IN; Hardware monitoring)

Cause:
Short circuit; Capacitive charging current of motor cable too high; Acceleration/deceleration times too short; Drive connected to coasting machine; Encoder error; Missing mains phase.



Remedy:

  • Search for the cause of the short circuit.

  • Check the motor cable.

  • Use motor cable which is shorter or of lower capacitance.

  • Increase the gain (P component) of the Imax controller (C0075).

  • Reduce integral-action time of the Imax controller (C0076).

  • Activate flying restart circuit.

  • Check wiring of the encoder.

  • Check connections and supply cable; check mains voltage.


0012 / OC2

Motor cable earth fault

Cause:
One of the motor phases has earth contact.



Remedy:

  • Search for cause of short circuit.

  • Check motor cable.


0013 / OC3

Overload during acceleration

Cause:
Too short acceleration or deceleration times in proportion to the load (C0012, C0013, C0105).



Remedy:

  • Increase the gain (P component) of the current controller (C0075).

  • Reduce the reset time (integral action component) of the Imax controller (C0076).

  • Increase ramp times.

  • See manual 9.4-2 ("controller in clamp operation").


0015 / OC5

I x t overload

Cause:
Frequent and too long acceleration with overcurrent; Continuous overload with Imotor > 1.05 x Irx.



Remedy:

  • Check drive dimensioning.


0016 / OC6

I²xt overload

Cause:
Frequent and too long acceleration processes with motor overcurrent; Permanent motor overload with Imotor > Irmotor.



Remedy:

  • Check drive dimensioning.


x018 / OC8

I²xt overload advance warning

Cause:
Frequent and too long acceleration processes with motor overcurrent; Permanent motor overload.



Remedy:

  • Check drive dimensioning.


2020 / OU

Overvoltage in the DC bus

Cause:
Braking energy is too high (DC-bus voltage is higher than set in C0173).



Remedy:

  • Use a braking unit or regenerative module.

  • Check dimensioning of the brake resistor.


1030 / LU

Undervoltage in the DC bus

Cause:
DC bus voltage is lower than specified in C0173.



Remedy:

  • Check mains voltage.

  • Check supply cable.


x032 / LP1

Motor phase failure

Cause:
A current-carrying motor phase has failed; The current limit value is set too low.



Remedy:

  • Check motor.

  • Check motor cable.

  • Switch off monitoring (C0597 = 3).

  • Set higher current limit value via C0599.


0050 / OH

Heatsink temperature > +90 °C

Cause:
Ambient temperature Tu > +40 °C or > +50 °C; Heatsink is very dirty; Wrong mounting position.



Remedy:

  • Allow module to cool and ensure better ventilation.

  • Check ambient temperature in the control cabinet.

  • Clean heatsink.

  • Change mounting position.


x053 / OH3

Motor temperature > +150 °C threshold

Cause:
Motor is thermally overloaded due to impermissible continuous current or frequent acceleration; No PTC/temperature contact connected.



Remedy:

  • Check drive dimensioning.

  • Switch off monitoring (C0583 = 3).

  • Correct wiring.


x054 / OH4

Heatsink temperature > C0122

Cause:
Ambient temperature high; Heatsink dirty; Wrong mounting position; The value specified under C0122 is set too low.



Remedy:

  • Allow module to cool and ensure better ventilation.

  • Switch off monitoring (C0582 = 3).

  • Clean heatsink or change mounting position.

  • Enter a higher value under C0122.


x057 / OH7

Motor temperature > C0121

Cause:
Motor is thermally overloaded; No PTC connected; The value specified under C0121 is set too low.



Remedy:

  • Check drive dimensioning.

  • Switch off monitoring (C0584 = 3).

  • Correct wiring.

  • Enter a higher value in C0121.


x058 / OH8

Motor temperature via inputs T1 and T2 is too high

Cause:
Motor is thermally overloaded; Terminals T1 and T2 are not connected.



Remedy:

  • Check drive dimensioning.

  • Switch off monitoring (C0585 = 3).

  • Connect PTC/temperature contact.


x061 / CE0

Automation interface (AIF) communication error

Cause:
Faulty transfer of control commands via AIF.



Remedy:

  • Plug in the communication module/keypad XT firmly, screw down if necessary.

  • Switch off monitoring (C0126 = 3).


x062 / CE1

Communication error on CAN1_IN

Cause:
CAN1_IN object receives faulty data or communication is interrupted.



Remedy:

  • Check wiring at X4.

  • Check sender.

  • Increase monitoring time under C0357/1 if necessary.

  • Switch off monitoring (C0591 = 3).


x063 / CE2

Communication error on CAN2_IN

Cause:
CAN2_IN object receives faulty data or communication is interrupted.



Remedy:

  • Check wiring at X4.

  • Check sender.

  • Increase monitoring time under C0357/2 if necessary.

  • Switch off monitoring (C0592 = 3).


x064 / CE3

Communication error on CAN3_IN

Cause:
CAN3_IN object receives faulty data or communication is interrupted.



Remedy:

  • Check wiring at X4.

  • Check sender.

  • Increase monitoring time under C0357/3 if necessary.

  • Switch off monitoring (C0593 = 3).


x065 / CE4

BUS-OFF state of system bus (CAN)

Cause:
Controller received too many faulty telegrams and disconnected from the bus.



Remedy:

  • Check wiring at X4 (termination).

  • Check shield connection of cables.

  • Check PE connection.

  • Check bus load / baud rate.

  • Switch off monitoring (C0595 = 3).


0071 / CCr

System failure

Cause:
Strong interference injection on control cables; Ground or earth loops in wiring.



Remedy:

  • Screen control cables.

  • Check wiring.

  • Check PE connection.

  • After troubleshooting: Deenergise the device completely (disconnect 24 V, discharge DC bus)!


0072 / PR1

Checksum error in parameter set 1

Cause:
Fault when loading parameter set; Interruption while transmitting; Stored parameters incompatible with software.



Remedy:

  • Set required parameters and store under C0003 = 1.

  • Store parameter set under C0003 = 1 first to allow for a faults reset.


0073 / PR2

Checksum error in parameter set 2

Cause:
Fault while loading parameter set; Interruption during transfer; Incompatible parameters.



Remedy:

  • Set the required parameters and save them with C0003 = 2.

  • First save the parameter set with C0003 = 2 to acknowledge error.


0074 / PEr

Program error

Cause:
Error in the program flow.



Remedy:

  • Send parameter set with detailed description to Lenze.

  • Deenergise device completely after troubleshooting.


0075 / PR0

Error in parameter set

Cause:
The operating system software has been updated.



Remedy:

  • Storage of the Lenze setting C0003 = 1.

  • Deenergise device completely after troubleshooting.


0077 / PR3

Checksum error in parameter set 3

Cause:
Fault while loading/transferring parameters; Saved parameters do not comply with software.



Remedy:

  • Set required parameters and save with C0003 = 3.


0078 / PR4

Checksum error in parameter set 4

Cause:
Fault while loading/transferring parameters; Saved parameters do not comply with software.



Remedy:

  • Set required parameters and save with C0003 = 4.


0079 / PI

Fault during parameter initialisation

Cause:
Error during transfer between devices; Data does not match controller (e.g. higher power to lower power).



Remedy:

  • Correct parameter set.

  • Send parameter set and description to Lenze.


x083 / Sd3

Encoder error at X9

Cause:
Cable interrupted; Pin X9/8 not connected.



Remedy:

  • Check cable for open circuit.

  • Apply 5 V to pin X9/8 or switch off monitoring (C0587 = 3).


x085 / Sd5

Encoder error at X6/1 and X6/2

Cause:
Current signal at X6/1 X6/2 < 2mA.



Remedy:

  • Check cable for open circuit.

  • Check current signal encoder.

  • Switch off monitoring (C0598 = 3).


x086 / Sd6

Motor temperature sensor error (X7 or X8)

Cause:
Encoder for detecting motor temperature indicates undefined values.



Remedy:

  • Check cable for firm connection.

  • Switch off the monitoring (C0594 = 3).


x091 / EEr

External monitoring triggered via DCTRL

Cause:
A digital signal assigned to the TRIP-SET function has been activated.



Remedy:

  • Check external encoder.

  • Switch off the monitoring (C0581 = 3).


0105 / H05

Internal fault (memory)

Cause:
Internal memory fault.



Remedy:

  • Contact Lenze.


0107 / H07

Internal fault (power stage)

Cause:
During initialisation, an incorrect power stage was detected.



Remedy:

  • Contact Lenze.


x110 / H10

Heatsink temperature sensor error

Cause:
Sensor indicates undefined values.



Remedy:

  • Contact Lenze.

  • Switch off the monitoring (C0588 = 3).


x111 / H11

Temperature sensor error (internal)

Cause:
Sensor for internal temperature indicates undefined values.



Remedy:

  • Contact Lenze.

  • Switch off the monitoring (C0588 = 3).


0140 / ID1

Error during motor data identification

Cause:
No motor connected; Stator resistance too high; Controller inhibited externally.



Remedy:

  • Check motor connection.

  • Check entered motor data.

  • Enable controller and repeat identification (pending continuously until end of process).


0141 / ID2

Error during motor data identification

Cause:
Motor too small; Controller inhibited externally.



Remedy:

  • Check entered motor data (use Global Drive Control input assistant).

  • Enable controller and repeat identification.


x200 / NMAX

Maximum system speed exceeded

Cause:
Active load (e.g. hoists) too high; Drive not speed-controlled, torque excessively limited.



Remedy:

  • Check drive dimensioning.

  • Increase torque limit if necessary.

  • Switch off monitoring (C0607 = 3).


How to Clear & Reset Lenze 9300 Vector Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key on the front-mounted Keypad XT (EMZ9371BB). Ensure controller enable (terminal 28 / RFR) is deasserted before issuing manual reset.
  2. Digital Input Reset (TRIP-RESET): Send a low-to-high signal transition (0 → 1 rising edge) to the control terminal configured for TRIP-RESET (by default assigned to terminal E4 / terminal 31 or set in code C0168 / C0410).
  3. Global Drive Control (GDC) PC Tool: Connect your PC via the diagnostics LECOM interface (RS232/RS485 adapter), open Lenze GDC software, navigate to the diagnostic window, and trigger the “Reset TRIP” function (or write parameter C0043).
  4. CAN / Fieldbus Control Word: Write Bit 11 (TRIP-RESET) from 0 to 1 in Control Word 1 via CAN system bus (CAN-IN) or communication modules (PROFIBUS-DP, INTERBUS, DeviceNet).
  5. Mains Power Cycle: Switch off the 3-phase AC main line power supply, wait at least 3 to 5 minutes until all internal DC bus capacitors discharge and LED indicators extinguish completely, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect mains supply power and wait at least 3 to 5 minutes for intermediate circuit DC capacitors to completely discharge. Verify that intermediate DC bus voltage measures strictly below 50V DC across terminals [+UG] and [−UG] with a calibrated multimeter before touching supply terminals (L1, L2, L3), brake resistor terminals, or motor terminals (U, V, W, PE).