Lenze 9300 Vector Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze 9300 Vector frequency inverter series. Search or filter through the complete fault code directory below.
Power Range
0.37 – 90 kW (0.5 – 120 HP)
Supply Voltage
380–480V AC (3-Phase)
Control Modes
Vector Control, Closed-Loop & V/f
Operator Interface
Keypad XT / Global Drive Control (GDC)
Complete Lenze 9300 Vector Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC1, OU, OH, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 0011 / OC1 Overcurrent in motor cable (Ia > 2.25 x IN; Hardware monitoring) | Cause: Short circuit; Capacitive charging current of motor cable too high; Acceleration/deceleration times too short; Drive connected to coasting machine; Encoder error; Missing mains phase. Remedy:
|
| 0012 / OC2 Motor cable earth fault | Cause: One of the motor phases has earth contact. Remedy:
|
| 0013 / OC3 Overload during acceleration | Cause: Too short acceleration or deceleration times in proportion to the load (C0012, C0013, C0105). Remedy:
|
| 0015 / OC5 I x t overload | Cause: Frequent and too long acceleration with overcurrent; Continuous overload with Imotor > 1.05 x Irx. Remedy:
|
| 0016 / OC6 I²xt overload | Cause: Frequent and too long acceleration processes with motor overcurrent; Permanent motor overload with Imotor > Irmotor. Remedy:
|
| x018 / OC8 I²xt overload advance warning | Cause: Frequent and too long acceleration processes with motor overcurrent; Permanent motor overload. Remedy:
|
| 2020 / OU Overvoltage in the DC bus | Cause: Braking energy is too high (DC-bus voltage is higher than set in C0173). Remedy:
|
| 1030 / LU Undervoltage in the DC bus | Cause: DC bus voltage is lower than specified in C0173. Remedy:
|
| x032 / LP1 Motor phase failure | Cause: A current-carrying motor phase has failed; The current limit value is set too low. Remedy:
|
| 0050 / OH Heatsink temperature > +90 °C | Cause: Ambient temperature Tu > +40 °C or > +50 °C; Heatsink is very dirty; Wrong mounting position. Remedy:
|
| x053 / OH3 Motor temperature > +150 °C threshold | Cause: Motor is thermally overloaded due to impermissible continuous current or frequent acceleration; No PTC/temperature contact connected. Remedy:
|
| x054 / OH4 Heatsink temperature > C0122 | Cause: Ambient temperature high; Heatsink dirty; Wrong mounting position; The value specified under C0122 is set too low. Remedy:
|
| x057 / OH7 Motor temperature > C0121 | Cause: Motor is thermally overloaded; No PTC connected; The value specified under C0121 is set too low. Remedy:
|
| x058 / OH8 Motor temperature via inputs T1 and T2 is too high | Cause: Motor is thermally overloaded; Terminals T1 and T2 are not connected. Remedy:
|
| x061 / CE0 Automation interface (AIF) communication error | Cause: Faulty transfer of control commands via AIF. Remedy:
|
| x062 / CE1 Communication error on CAN1_IN | Cause: CAN1_IN object receives faulty data or communication is interrupted. Remedy:
|
| x063 / CE2 Communication error on CAN2_IN | Cause: CAN2_IN object receives faulty data or communication is interrupted. Remedy:
|
| x064 / CE3 Communication error on CAN3_IN | Cause: CAN3_IN object receives faulty data or communication is interrupted. Remedy:
|
| x065 / CE4 BUS-OFF state of system bus (CAN) | Cause: Controller received too many faulty telegrams and disconnected from the bus. Remedy:
|
| 0071 / CCr System failure | Cause: Strong interference injection on control cables; Ground or earth loops in wiring. Remedy:
|
| 0072 / PR1 Checksum error in parameter set 1 | Cause: Fault when loading parameter set; Interruption while transmitting; Stored parameters incompatible with software. Remedy:
|
| 0073 / PR2 Checksum error in parameter set 2 | Cause: Fault while loading parameter set; Interruption during transfer; Incompatible parameters. Remedy:
|
| 0074 / PEr Program error | Cause: Error in the program flow. Remedy:
|
| 0075 / PR0 Error in parameter set | Cause: The operating system software has been updated. Remedy:
|
| 0077 / PR3 Checksum error in parameter set 3 | Cause: Fault while loading/transferring parameters; Saved parameters do not comply with software. Remedy:
|
| 0078 / PR4 Checksum error in parameter set 4 | Cause: Fault while loading/transferring parameters; Saved parameters do not comply with software. Remedy:
|
| 0079 / PI Fault during parameter initialisation | Cause: Error during transfer between devices; Data does not match controller (e.g. higher power to lower power). Remedy:
|
| x083 / Sd3 Encoder error at X9 | Cause: Cable interrupted; Pin X9/8 not connected. Remedy:
|
| x085 / Sd5 Encoder error at X6/1 and X6/2 | Cause: Current signal at X6/1 X6/2 < 2mA. Remedy:
|
| x086 / Sd6 Motor temperature sensor error (X7 or X8) | Cause: Encoder for detecting motor temperature indicates undefined values. Remedy:
|
| x091 / EEr External monitoring triggered via DCTRL | Cause: A digital signal assigned to the TRIP-SET function has been activated. Remedy:
|
| 0105 / H05 Internal fault (memory) | Cause: Internal memory fault. Remedy:
|
| 0107 / H07 Internal fault (power stage) | Cause: During initialisation, an incorrect power stage was detected. Remedy:
|
| x110 / H10 Heatsink temperature sensor error | Cause: Sensor indicates undefined values. Remedy:
|
| x111 / H11 Temperature sensor error (internal) | Cause: Sensor for internal temperature indicates undefined values. Remedy:
|
| 0140 / ID1 Error during motor data identification | Cause: No motor connected; Stator resistance too high; Controller inhibited externally. Remedy:
|
| 0141 / ID2 Error during motor data identification | Cause: Motor too small; Controller inhibited externally. Remedy:
|
| x200 / NMAX Maximum system speed exceeded | Cause: Active load (e.g. hoists) too high; Drive not speed-controlled, torque excessively limited. Remedy:
|
How to Clear & Reset Lenze 9300 Vector Drive Faults
- Keypad Reset: Press the red STOP / RESET key on the front-mounted Keypad XT (EMZ9371BB). Ensure controller enable (terminal 28 / RFR) is deasserted before issuing manual reset.
- Digital Input Reset (TRIP-RESET): Send a low-to-high signal transition (0 → 1 rising edge) to the control terminal configured for TRIP-RESET (by default assigned to terminal E4 / terminal 31 or set in code C0168 / C0410).
- Global Drive Control (GDC) PC Tool: Connect your PC via the diagnostics LECOM interface (RS232/RS485 adapter), open Lenze GDC software, navigate to the diagnostic window, and trigger the “Reset TRIP” function (or write parameter C0043).
- CAN / Fieldbus Control Word: Write Bit 11 (TRIP-RESET) from
0to1in Control Word 1 via CAN system bus (CAN-IN) or communication modules (PROFIBUS-DP, INTERBUS, DeviceNet). - Mains Power Cycle: Switch off the 3-phase AC main line power supply, wait at least 3 to 5 minutes until all internal DC bus capacitors discharge and LED indicators extinguish completely, then reapply power.
⚠️ High-Voltage Electrical Safety Warning:
Always disconnect mains supply power and wait at least 3 to 5 minutes for intermediate circuit DC capacitors to completely discharge. Verify that intermediate DC bus voltage measures strictly below 50V DC across terminals [+UG] and [−UG] with a calibrated multimeter before touching supply terminals (L1, L2, L3), brake resistor terminals, or motor terminals (U, V, W, PE).