Lenze i510 Cabinet Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze i510 Cabinet frequency inverter series. Search or filter through the complete fault code directory below.

Compact Inverter (IP20) Power: 0.25 to 15 kW (0.33 to 20 HP) Modular Book-Style Design
Power Range 0.25 – 15 kW (0.33 – 20 HP)
Supply Voltage 1~ 230V / 3~ 400–480V AC
Control Modes V/f (Linear/Square) & SLVC
Operator Interface Keypad / USB / WLAN Module

Complete Lenze i510 Cabinet Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type 0x2221, 0x3211, or Overcurrent).

Fault Code and MeaningCause and Remedy
8784 (0x2250)

CiA: Continuous over current (internal)
Display: PU over current

Cause:


  • Continuous overcurrent on the inverter/motor side.

  • DC bus relay has not been closed due to a malfunction.




Remedy:


  • Check motor and wiring for short circuits.

  • Note: The inverter is disabled immediately. The motor has no torque (is coasting).


8992 (0x2320)

Short circuit or earth leakage at the motor end
Display: Earth leak

Cause:


  • Short circuit/earth fault of motor cable.

  • Capacitive charging current of the motor cable too high.




Remedy:


  • Check motor cable.

  • Check length of the motor cable.

  • Use shorter or lower-capacitance motor cable.


9024 (0x2340)

Short circuit at the motor end
Display: Motor shorted

Cause:

Short circuit of motor cable.



Remedy:


  • Check motor cable for short circuit.


9040 (0x2350)

CiA: i²xt overload (thermal state)
Display: i2t motor

Cause:

Motor thermally overloaded, e.g. by an impermissible continuous current or by frequent or too long acceleration processes.



Remedy:


  • Check drive sizing.

  • Check machine/driven mechanics for excessive load.

  • Check settings of the motor data.

  • Reduce values for slip compensation (0x2B09) and oscillation damping (0x2B0A).


9090 (0x2382)

Fault - Device utilization (ixt) too high
Display: Ixt error

Cause:

Device utilisation (ixt) too high by frequent and too long acceleration processes.



Remedy:


  • Check drive sizing.

  • Reduce the maximum current of the inverter 0x6073 (P324.00).

  • In case of high mass inertias, reduce maximum current of the inverter to 150%.


9091 (0x2383)

Warning - Device utilization (ixt) too high
Display: Ixt warning

Cause:

Device utilisation (ixt) too high by frequent and too long acceleration processes.



Remedy:


  • Check drive dimensioning.


9095 (0x2387)

Clamp responded too often
Display: Clamp timeout

Cause:

Maximum current of the axis has been reached too often in succession.



Remedy:


  • Select a flatter speed ramp.

  • Reduce the load.

  • Set Imax controller more dynamically.


9096 (0x2388)

SL-PSM stall detection active
Display: SL-PSM stall det.

Cause:

Overload of the motor with sensorless control for synchronous motors (SL-PSM).



Remedy:


  • Reduce load at the axis.

  • Check settings of the SL-PSM parameters.


9098 (0x238A)

Maximum current reached
Display: Imax reached

Cause:

The actual current is equal to or higher than the max. current.



Remedy:


  • Reduce the load on the motor or change the settings for the maximum current.


12576 (0x3120)

Mains phase fault
Display: Mains Phase fail

Cause:

Mains phase failure.



Remedy:


  • Check wiring of the mains connection.

  • Check fuses.


12672 (0x3180)

UPS operation active
Display: UPS oper. active

Cause:

Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided.



Remedy:


  • Switch back to operation with regular mains voltage.


12816 (0x3210)

Fault - DC bus overvoltage
Display: DC Bus OV

Cause:

DC-bus voltage has exceeded the error threshold due to too high braking energy or too high mains voltage.



Remedy:


  • Reduce dynamic performance of the load profile.

  • Check mains voltage.

  • Check settings for brake energy management.


12817 (0x3211)

DC bus overvoltage warning
Display: Warn.DC Bus OV

Cause:

DC-bus voltage has exceeded the warning threshold.



Remedy:


  • Reduce dynamic performance of the load profile.

  • Check mains voltage.

  • Check settings for brake energy management.


12832 (0x3220)

Fault - DC bus undervoltage
Display: DC Bus UV

Cause:

DC-bus voltage has fallen below the error threshold for undervoltage.



Remedy:


  • Check mains voltage.

  • Check DC-bus voltage.

  • Check mains settings.

  • Check fuses.


12833 (0x3221)

DC bus undervoltage warning
Display: Warn.DC Bus UV

Cause:

DC-bus voltage has fallen below the warning threshold for undervoltage.



Remedy:


  • Check mains voltage.

  • Check DC-bus voltage.

  • Check mains settings.

  • Check fuses.


12834 (0x3222)

DC-bus voltage too low for power up
Display: DC-bus on-UV

Cause:

The input voltage is too low to switch on the inverter.



Remedy:


  • Check mains voltage.

  • Check mains settings.

  • Check fuses.


16912 (0x4210)

Fault - Power unit overtemperature
Display: PU Overtemp.

Cause:

The heatsink temperature has exceeded the error threshold (100 °C).

  • Ambient temperature too high.

  • Fan or ventilation slots are polluted.

  • Fan is defective.




Remedy:


  • Check mains voltage.

  • Provide for a sufficient cooling of the device.

  • Clean fan and ventilation slots. If required, replace fan.

  • Reduce switching frequency.


17024 (0x4280)

Fault - Heat sink temperature sensor
Display: Heatsink sensor

Cause:

Sensor for the temperature monitoring of the power unit is defective.



Remedy:


  • Hardware error: it is necessary to contact the manufacturer, since the device must be replaced.


17025 (0x4281)

Heat sink fan warning
Display: Heatsink fan

Cause:

Warning of the heatsink fan.



Remedy:


  • Clean fan and ventilation slots.

  • If required, replace fan.


17029 (0x4285)

PU overtemperature warning
Display: Warn.PU Overtemp

Cause:

The heatsink temperature of the power unit has exceeded the warning threshold.



Remedy:


  • Provide for a sufficient cooling of the device.

  • Clean fan and ventilation slots.

  • If required, replace fan.


20754 (0x5112)

External supply voltage critical
Display: Ext. supply low

Cause:

External supply voltage failed or too low.



Remedy:


  • Check optional external 24V voltage supply (terminal X3/24E), if connected.

  • Check mains voltage.


20864 (0x5180)

Overload 24 V supply
Display: Overload 24V

Cause:

Output current at the 24V output or at the digital outputs too high.



Remedy:


  • Check 24V output and digital outputs for earth fault or overload.


21376 (0x5380)

OEM hardware incompatible
Display: Incomp. OEM HW

Cause:

The control unit (OEM hardware) is not compatible with the power unit.



Remedy:


  • Use compatible hardware.

  • Contact the OEM.


24970 (0x618A)

Warning - Internal fan
Display: Internal fan

Cause:

Warning of the internal fan.



Remedy:


  • Check/replace internal fan.


25216 (0x6280)

Trigger/functions connected incorrectly
Display: P400 config err

Cause:

The assignment directives have not been observed.



Remedy:


  • Check and correct the assignment of the triggers to the functions.


25217 (0x6281)

User-defined fault 1
Display: User fault 1

Cause:

Flexible I/O configuration: "Activate fault 1" function was triggered.



Remedy:


  • Eliminate error cause and then reset error.


25218 (0x6282)

User-defined fault 2
Display: User fault 2

Cause:

Flexible I/O configuration: "Activate fault 2" function was triggered.



Remedy:


  • Eliminate error cause and then reset error.


25232 (0x6290)

Warning invert rotation
Display: Invert rotation

Cause:

Negative setpoint selection with an active limitation of rotation.



Remedy:


  • Check setpoint selection and trigger.

  • Check setting in 0x283A.


25233 (0x6291)

Maximum allowed troubles exceeded
Display: Trouble overflow

Cause:

The number of permitted restart attempts after a fault was exceeded. The fault occurred too frequently.



Remedy:


  • Check and eliminate the fault.


25248 (0x62A0)

User-defined fault (LECOM)
Display: UserFault(LECOM)

Cause:

The "Activate fault" function was triggered via LECOM control word.



Remedy:


  • Eliminate error cause and then reset error.


25249 (0x62A1)

Network: user fault 1
Display: Netw.UserFault 1

Cause:

The "Activate fault 1" function was triggered via NetWordIN1.



Remedy:


  • Eliminate error cause and then reset error.


25250 (0x62A2)

Network: user fault 2
Display: Netw.UserFault 2

Cause:

The "Activate fault 2" function was triggered via NetWordIN1.



Remedy:


  • Eliminate error cause and then reset error.


25265 (0x62B1)

NetWordIN1 configuration incorrect
Display: NetWordIN1 error

Cause:

Two bits of the NetWordIN1 data word were assigned to the same function.



Remedy:


  • Check and correct configuration of the NetWordIN1 data word.


25505 (0x63A1)

CU: load error ID tag
Display: CU ID tag error

Cause:

Calibration data of the control unit not compatible or faulty.



Remedy:


  • Update firmware of the inverter to the most recent version.

  • If error persists, the control unit must be replaced.


25506 (0x63A2)

PU: load error ID tag
Display: PU ID tag error

Cause:

Calibration data of the power unit not compatible or faulty.



Remedy:


  • Update firmware of the inverter to the most recent version.

  • If error persists, the power unit must be replaced.


25507 (0x63A3)

Power unit unknown
Display: PU unknown

Cause:

The power unit installed is not supported by the software.



Remedy:


  • Update firmware of the inverter to the most recent version.


28800 (0x7080)

Assertion level monitoring (Low/High)
Display: Assertionlevel

Cause:

The last setting of the connection level differs from the saved setting.



Remedy:


  • Execute device command "Save user data".

  • Switch inverter off and on again.


28801 (0x7081)

Fault - Analog input 1
Display: AI1 fault

Cause:

The monitoring function of the input signal configured for analog input 1 has been triggered.



Remedy:


  • Check input signal at analog input 1.

  • Check configuration of the monitoring function.


28802 (0x7082)

Analog input 2 fault
Display: AI2 fault

Cause:

The monitoring function of the input signal configured for analog input 2 has been triggered.



Remedy:


  • Check input signal at analog input 2.

  • Check configuration of the monitoring function.


28833 (0x70A1)

Analog output 1 fault
Display: AO1 fault

Cause:

Open circuit or short circuit at analog output 1.



Remedy:


  • Check wiring of analog output 1.

  • Check definition of the output range.


28961 (0x7121)

Fault - Pole position identification
Display: Pole pos. error

Cause:


  • Too many deviations during the pole position identification.

  • Rated motor current too high or too low.




Remedy:


  • Check setting of the motor data.

  • Ensure that the motor is at a standstill during the identification process.

  • Ensure motor and inverter match in terms of power.


29056 (0x7180)

Motor overcurrent
Display: Mot max current

Cause:

The motor current has exceeded the warning/error threshold.



Remedy:


  • Check motor load.

  • Check drive dimensioning.

  • Check warning/error threshold settings.


30336 (0x7680)

Memory module is full
Display: EPM full

Cause:

The memory module contains too many parameter settings.



Remedy:


  • Execute "Save user data" device command again. This reinitialises the user memory.


30337 (0x7681)

Memory module not present
Display: EPM not present

Cause:

The inverter memory module was removed.



Remedy:


  • Switch off inverter. Plug in memory module. Switch on.


30338 (0x7682)

Invalid user data
Display: EPM invalid data

Cause:

The user parameter settings in the memory module are invalid.



Remedy:


  • Execute user parameter settings again.

  • Execute device command "Save user data".


30340 (0x7684)

Data not compl. saved before powerdown
Display: Save incomplete

Cause:

Saving of the parameter settings was interrupted by an unexpected disconnection.



Remedy:


  • Check user parameter settings (backup is older version).

  • If required, repeat changes.

  • Execute "Save user data".


30342 (0x7686)

Network - Configuration error
Display: Comm.error

Cause:

The configuration of the fieldbus is incorrect (switch position).



Remedy:


  • Switch off inverter.

  • Check and rectify the "CANopen/Modbus" change-over switch.

  • Switch on again.


30345 (0x7689)

Memory module: invalid OEM data
Display: OEM data invalid

Cause:

The OEM memory contains invalid parameter settings or is empty.



Remedy:


  • Execute device command "Save OEM data".


30346 (0x768A)

Memory module: wrong type
Display: Wrong EPM

Cause:

The memory module connected is not supported by the inverter.



Remedy:


  • Switch off inverter.

  • Replace memory module with matching type.

  • Switch on again.


30352 (0x7690)

EPM firmware version incompatible
Display: EPM-FW incomp.

Cause:

The parameter settings saved in the memory module are incompatible with the firmware version.



Remedy:


  • Execute "Load default settings".

  • Execute "Save user data" or "Save OEM data".


30353 (0x7691)

EPM data: firmware type incompatible
Display: EPM: FW incomp.

Cause:

The parameter settings saved in the memory module are incompatible with the firmware type.



Remedy:


  • Execute "Load default settings".

  • Execute "Save user data" or "Save OEM data".


30354 (0x7692)

EPM data: new firmware type detected
Display: UserCU not match

Cause:

The parameter settings saved in the memory module do not match the inverter hardware.



Remedy:


  • Check parameter settings.

  • Reset error.

  • Execute "Save user data" or "Save OEM data".


30355 (0x7693)

EPM data: PU size incompatible
Display: EPM PU size inco

Cause:

The parameter settings saved in the memory module are incompatible with the inverter.



Remedy:


  • Execute "Load default settings".

  • Execute "Save user data" or "Save OEM data".


30356 (0x7694)

EPM data: new PU size detected
Display: EPM new PU size

Cause:

The parameter settings saved in the memory module comply with a different hardware.



Remedy:


  • Check parameter settings.

  • Reset error.

  • Execute "Save user data" or "Save OEM data".


30357 (0x7695)

Invalid parameter changeover configuration
Display: InvalidChgovrCfg

Cause:

One or more parameters can no longer be used for the "Parameter change-over" function.



Remedy:


  • Check error message for parameter change-over.

  • Correct the list entry.


30358 (0x7696)

EPM data: unknown parameter found
Display: Unkn. Par in EPM

Cause:

The memory module contains parameter settings for one or several parameters that are not known to the inverter.



Remedy:


  • Execute the "Save user data" device command. This reinitialises the user memory.


30359 (0x7697)

Parameter changes lost
Display: Parameter loss

Cause:

A voltage failure has occurred and changed parameter settings that had not been saved yet were available.



Remedy:


  • Execute parameter settings again.

  • Execute device command "Save user data".


33045 (0x8115)

Time-out (PAM)
Display: Time-out (PAM)

Cause:

The parameter access monitoring (PAM) function has been activated.



Remedy:


  • Check communication.

  • Check settings of the parameter access monitoring (PAM) function.


33050 (0x811A)

BACnet time-out
Display: BACnet time-out

Cause:

BACnet MS/TP communication timeout.



Remedy:


  • Check communication.

  • Restore communication or change the "Network" control mode.


33154 (0x8182)

CAN: bus off
Display: CAN: bus off

Cause:

Too many faulty frames have been received.

  • Defective cable.

  • Two nodes with same node address.




Remedy:


  • Check wiring of the network.

  • Check bus terminating resistor.

  • Set identical baud rate for each node.

  • Assign unique node address.

  • Eliminate EMC interferences.


33155 (0x8183)

CAN: warning
Display: CAN bus warning

Cause:

Too many faulty frames have been received.



Remedy:


  • Check wiring of the network.

  • Check bus terminating resistor.

  • Check baud rates and addresses.

  • Eliminate EMC interferences.


33156 (0x8184)

CAN: heartbeat time-out consumer 1
Display: CAN heartb. C1

Cause:

No heartbeat telegram was received by node 1.



Remedy:


  • Check communication with the heartbeat producer.

  • Reactivate heartbeat producer.


33185 (0x81A1)

Modbus: network time-out
Display: Modbus time-out

Cause:

No valid messages have been received via the Modbus for a longer time than the time-out time set.



Remedy:


  • Check communication with the master.

  • Check wiring.

  • Check bus termination.


33186 (0x81A2)

Modbus: incorrect request by master
Display: Modbus request

Cause:

The request by the master is invalid (e.g. CRC checksum, non-supported function, impermissible data).



Remedy:


  • Check request by the master (valid range, function code, write access).


33425 (0x8291)

CAN: RPDO1 time-out
Display: Timeout RPDO1

Cause:

RPDO1 was not received within the time-out period.



Remedy:


  • Check Process data transfer.


33553 (0x8311)

Torque limit reached
Display: Torque limit

Cause:

Motor has reached the torque limit.



Remedy:


  • Observe load requirements.

  • Reduce motor load.

  • Check set torque limits.


33664 (0x8380)

Function not allowed in selected operating mode
Display: Func. n. allowed

Cause:

The selected function is not permissible in the chosen operating mode.



Remedy:


  • Check settings of operation modes.

  • Selection of torque mode with incompatible motor control.


36992 (0x9080)

Keypad removed
Display: Keypad removed

Cause:

The keypad was removed while the keypad control was activated.



Remedy:


  • Plug keypad back in or activate another control source.


65285 (0xFF05)

Safety option - Internal error
Display: Safety int.Error

Cause:

The integrated safety technology is defective.



Remedy:


  • The inverter must be replaced.

  • The safety module must not be removed.


65286 (0xFF06)

Motor overspeed
Display: Motor overspeed

Cause:

The motor speed has reached the error threshold for overspeed.



Remedy:


  • Adapt the maximum motor speed and the warning/error threshold.


65289 (0xFF09)

Motor phase missing
Display: Mot.Phase miss.

Cause:

A failure of several motor phases has been detected.



Remedy:


  • Check wiring between inverter and motor.

  • In case of a false tripping, adapt the settings for the motor phase failure detection.


65290 (0xFF0A)

Motor phase failure phase U
Display: Phase U failure

Cause:

A failure of the motor phase U has been detected.



Remedy:


  • Check wiring between inverter and motor.

  • In case of a false tripping, adapt the settings for the motor phase failure detection.


65305 (0xFF19)

Motor parameter identification fault
Display: Motor ID fault

Cause:

During the automatic identification of the motor, an error has occurred.



Remedy:


  • Set motor data so that they comply with the data on the motor nameplate.

  • Check wiring of the motor.


65311 (0xFF1F)

FMF Error
Display: FMF Error

Cause:

Configuration or runtime error.



Remedy:


  • Check configuration.

  • Check FMF error code 0x4050:002 to determine the error cause.


65317 (0xFF25)

Cascading overload
Display: Cascad. overload

Cause:

Cascade function for pumps and fans: The maximum frequency has been reached and no free additional pump is available.



Remedy:


  • Check configuration of the cascade function.

  • Check drive sizing.


65335 (0xFF37)

Automatic start disabled
Display: Auto start disab

Cause:

At mains connection, a start command was already available and the automatic start at power-up is set to "Off".



Remedy:


  • Deactivate starting command and reset error.


65336 (0xFF38)

Load loss detected
Display: Load loss

Cause:

When the motor load falls below the threshold value specified in Load loss detection.



Remedy:


  • Check utilisation.


65337 (0xFF39)

Motor overload
Display: Motor overload

Cause:

If the apparent motor current exceeds a defined threshold value for a certain amount of time.



Remedy:


  • Check the motor load.


65366 (0xFF56)

Maximum motor frequency reached
Display: Max. motor freq.

Cause:

The maximum output frequency of the inverter has been reached.



Remedy:


  • Check application.


65370 (0xFF5A)

Manual mode disabled
Display: Man. mode disabl

Cause:

Indicates the deactivation of the manual speed control.



Remedy:


  • (Warning only)


65371 (0xFF5B)

Manual mode activated
Display: Man. mode act.

Cause:

Indicates the activation of the manual speed control.



Remedy:


  • (Warning only)


65372 (0xFF5C)

Manual mode time-out
Display: ManMode time-out

Cause:

If "manual operation" is active, an error is generated in case the communication links get lost.



Remedy:


  • The error can only be reset if the connection is restored or the control mode is changed.


65393 (0xFF71)

Wrong password
Display: Wrong password

Cause:

A wrong password has been entered several times.



Remedy:


  • Wait until the blocking time has elapsed and then enter the correct password.


65394 (0xFF72)

Warning
Display: Warning

Cause:

Inverter is not compatible with the Controller/PLC.



Remedy:


  • Use corresponding (compatible) OEM components.


65395 (0xFF73)

Fatal Error
Display: Fatal Error

Cause:

Error when reading the data from the control unit.



Remedy:


  • Switch inverter off and on again.

  • If error recurs, the manufacturer must be contacted.


65413 (0xFF85)

Keypad full control active
Display: Keypad full ctrl

Cause:

If the "Keypad Full Control" control mode is active.



Remedy:


  • To exit the control mode, press the keypad key CTRL.


How to Clear & Reset Lenze i510 Cabinet Drive Faults

  1. Keypad Reset: Press the red Stop / Reset key on the plug-in keypad. If running under remote control, verify the active start command is removed before executing the reset.
  2. Digital Input Reset: Apply a low-to-high signal transition (0 → 1 edge pulse) on the digital terminal configured for fault reset (assigned in parameter 0x2631:004 / P400.04; default DI4 on terminal strip).
  3. EASY Starter / WLAN Module: Connect a PC using the USB diagnostic module via Lenze EASY Starter, or connect wirelessly using the WLAN module via the Lenze Smart Flight app, then click the “Reset fault” command button.
  4. Fieldbus Control Word: Write Bit 7 (Fault Reset) from 0 to 1 in Control Word 1 over your network interface (CANopen, Modbus RTU, or IO-Link).
  5. Mains Power Cycle: Switch off the incoming AC supply power, wait at least 3 to 5 minutes until the LED status indicators turn off completely (ensuring DC bus capacitors have discharged), then re-energize the unit.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect incoming mains power and wait at least 3 to 5 minutes for intermediate circuit DC bus capacitors to discharge. Verify with a calibrated DC multimeter that intermediate bus terminals measure strictly below 50V DC across terminals [+UG] and [−UG] before opening enclosure covers, inspecting motor wiring, or servicing terminals (L1, L2, L3, U, V, W, PE).