Lenze i700 Cabinet Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze i700 cabinet multi-axis servo inverter system. Search or filter through the complete fault code directory below.

Multi-Axis Servo System Rated Current: 2.5 A to 64 A (0.75 to 30 kW) EtherCAT CiA 402 & Integrated STO (SIL 3)
Axis Output Rating 2.5 A – 64 A (0.75 – 30 kW)
Supply Voltage 3-Ph 400/480V AC (565V DC Bus)
Control Modes Field-Oriented Servo & CiA 402
Bus & Safety EtherCAT & STO (SIL 3 / PL e)

Complete Lenze i700 Cabinet Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type 0x2310, 0x3210, Overcurrent, or Resolver Error).

Fault Code and MeaningCause and Remedy
EtherCAT_Master: Start master failed. Bus mismatch


Bus does not assume "Pre-Operational" state

Cause: Faulty bus configuration and bus structure.

  • Slaves are missing.

  • Slaves have been inverted or their configuration is faulty.

  • A wrong slave type has been configured or is at the fieldbus.

  • The inputs and outputs of the EtherCAT communication module are reversed (IN/OUT connections).

  • Faulty wiring.




Remedy:

  • Correct the bus configuration or the physical bus structure.

  • Afterwards, reload the »PLC Designer« application into the automation system.


EtherCAT_Master: Start master failed. EtherCAT cable disconnected


Wiring error

Cause: Wiring error: EtherCAT cable is not connected to the master.



Remedy:

  • Correct wiring.

  • Afterwards, reload the »PLC Designer« application into the automation system.


0x4000005
EtherCAT_Master: Set master 'Operational' failed


SDO Abort 'Object does not exist'

Cause: Start parameter could not be written.



Remedy:

  • Correct the start-up parameters in »PLC Designer« on the Configuration tab of the EtherCAT master.


EtherCAT_Master: Set master 'Operational' failed. DCM not in-sync


Wiring error (IN/OUT inverted)

Cause: Wiring error: The EtherCAT terminals (IN/OUT) of the slave were inverted. A fieldbus scan does not indicate this error!



Remedy:

  • Correct wiring.

  • Afterwards, reload the »PLC Designer« application into the automation system.


0x12 / 0x1E
AL Status Code: 'Invalid Input Configuration'


Structure mismatch (EPM-S130)

Cause: The real structure at an EPM-S130 head end does not correspond to the control configuration configured. This error can occur if I/O panels have been added manually.



Remedy:

  • Correct control configuration in the »PLC Designer«.

  • Note: In "data: ...", a coded information says which error has occurred in which slave device/module.


0x4000005 / 0x1A
AL Status Code: 'Synchronization error'


Inconsistent Sync settings

Cause: Synchronisation settings in the standard device (slave) and the »PLC Designer« configuration are inconsistent.



Remedy:

  • Adapt the synchronisation settings in the slave.


EtherCAT_Master: DC slaves 'out-of-sync'


Deviation xxxxxxxx ns

Cause: The first slave after the master has not been defined as DC master.



Remedy:

  • Declare the first slave after the master as DC master ("DC for Synchronization").


WKC Error / Not all slaves 'Operational'


Cyclical command WKC error

Cause:

  • The bus cable between two EtherCAT nodes has been unplugged.

  • The node at position X is deenergised.

  • A slave no longer receives cyclical frames so that the watchdog determined by the device description is triggered.




Remedy:

  • Correct bus topology.

  • Restart the EtherCAT fieldbus.


Invalid SyncManager Configuration


[DeviceName] (1001)

Cause:

  • One of the slaves does not support an LRW command (Logical Read/Write).

  • A slave is not written to correctly.




Remedy:

  • In the EtherCAT master tab, do not select the "Use LRW instead of LWR/LRD" checkbox.


Invalid Input/Output Configuration


AL state code: 0x1E or 0x1D

Cause: The process data configuration of a slave is not correct.

  • In case of a modular device (e.g., I/O system 1000), configuration in project does not comply with real assembly.

  • More process data than permissible are mapped for the device.




Remedy:

  • Correct the control configuration in the »PLC Designer« (adjustment with the real setup).

  • Reduction of the process data (maximum length must not be exceeded).


Logic Address Error


Error during process data transfer

Cause: Use of logic addresses directly (%Ixx, %Qxx) instead of symbolically. The bus structure or PDO selection may have changed.



Remedy:

  • In the »PLC Designer« application, input/output objects must be accessed via individual, non-ambiguous variables.

  • Variable names must comply with IEC 61131 syntax.


Manual definition of logic address


I/O mapping manipulation

Cause: Manual definition of the logic address in the EtherCAT I/O mapping (e.g. changing %QB70 to %QB1000).



Remedy:

  • It is not permissible to manually manipulate the I/O addresses for the EtherCAT bus!


Missing or incorrect I/O mapping


Servo Drives 9400 / Inverter 8400

Cause: Ports in »Engineer« are displayed incorrectly or not at all.



Remedy:

  • Check and correct the mapping settings in the control configuration and in the inverter.

  • Note: When Lenze Controller starts, mapping entries from »Engineer« are overwritten by the configuration/PDO mapping.


Variables not used in »PLC Designer«


Process image update issue

Cause: I/O variables not used in »PLC Designer« are not copied into the process image, so they are not updated.



Remedy:

  • With the slave, go to the EtherCAT I/O Mapping tab and set a checkmark at Always update variables.


EtherCAT_Master: EtherCAT cable not connected


Timeout / Safe-Operational

Cause: The bus cable between the Lenze Controller and the first node has been unplugged and plugged back in. The slaves sync managers timed out.



Remedy:

  • After the bus cable has been plugged in again, Restart the EtherCAT fieldbus.


EtherCAT_Master: Frame response error


Repeated 1/10/100 times

Cause: A frame sent by the master does not return until the next cycle.

  • Task utilisation too high.

  • EtherCAT bus cycle task does not have the highest IEC task priority.

  • Slave error forwarding frames.

  • Only a switch or ET2000 connected but no slave.




Remedy:

  • Reduce the program code or increase the bus task cycle time.

  • Assign the sole and highest IEC task priority to the EtherCAT bus cycle task.

  • Correct the slave error or bus structure.


Shafts make clicking noises


Cycle time mismatch

Cause: The task and DC cycle times set in the logic/motion system differ.



Remedy:

  • Adjust the task cycle time and DC cycle time.


Shafts make clicking noises


"out-of-sync" re-synchronisation

Cause: If due to a fault, the preset DC deviation limit is exceeded, a re-synchronisation is carried out. Currently not synchronised.



Remedy:

  • Restart the EtherCAT fieldbus so that the DC slaves and DC master synchronise again.


Sync Source Error


9400 HighLine CiA402

Cause: Wrong selection of the device sync source (C01120). After change, download may fail.



Remedy:

  • Manual setting of code C01120 to MXI1 or MXI2.

  • Repeated download with PLC start.

  • Restarting the EtherCAT fieldbus with reset of the SoftMotion drive.


Shafts do not rotate


Faulty SoftMotion scaling

Cause: Faulty SoftMotion scaling/mapping; increments per revolution are not set.



Remedy:

  • Check Gearbox ratio in the »PLC Designer« application.

  • Check Mapping settings in the master configuration.

  • Tip: In the case of Servo Drive 9400 HighLine CiA402, 65536 increments per revolution are correct.


0x0000

No error

Cause:

No error pending.



Remedy:

None.
0x2320

Short circuit or earth leakage at the motor end

Cause:


  • Earth fault in motor cable.

  • Excessive capacitive charging current in the motor cable.




Remedy:


  • Check motor cable.

  • Use motor cable that is shorter or has a lower capacitance.


Note: Error reset only possible after 5 s.
0x2340

Short circuit at the motor end

Cause:


  • Short circuit/earth fault in motor cable.

  • Excessive capacitive charging current in the motor cable.




Remedy:


  • Check motor cable.

  • Use motor cable that is shorter or has a lower capacitance.


Note: Error reset only possible after 5 s.
0x2351

Motor utilisation (I²xt) > [value] %

Cause:

Motor is thermally overloaded, e.g. due to:

  • Impermissible continuous current.

  • Frequent or too long acceleration processes.




Remedy:


  • Check drive dimensioning.

  • Check setting or the warning or error threshold.


0x2380

Fault - utilisation of the power section (Ixt) too high

Cause:

Frequent and too long acceleration processes with overcurrent.



Remedy:


  • Check drive dimensioning.


0x2381

Warning - utilisation of the power section (Ixt) too high

Cause:

Frequent and too long acceleration processes with overcurrent.



Remedy:


  • Check drive dimensioning.


0x2382

Fault - device utilisation (Ixt) too high

Cause:

Frequent and too long acceleration processes with overcurrent.



Remedy:


  • Check drive dimensioning.


0x2383

Warning - device utilisation (Ixt) too high

Cause:

Frequent and too long acceleration processes with overcurrent.



Remedy:


  • Check drive dimensioning.


0x2384

Ultimate motor current reached

Cause:

The motor current has exceeded the "ultimate" motor current. The "ultimate" motor current corresponds to the current level at which the permanent magnets of a synchronous motor suffer permanent damage.



Remedy:


  • Reduce maximum current (0x6073 | 0x6873) and/or adjust the current controller (0x2942 | 0x3142) in order to reduce the current overshoot.


0x2385

Output current > [value] A (maximum device current)

Cause:

The desired maximum current (0x6073 | 0x6873) is higher than the maximum current of the axis (display in 0x2DDF:2 | 0x35DF:2).



Remedy:

The permissible maximum current (0x6073 | 0x6873) is: Maximum axis current / Rated motor current.

  • Check setting of rated motor current in 0x6075 | 0x6875.


0x2386

Clamp is active

Cause:

Maximum current of the axis (display in 0x2DDF:2 | 0x35DF:2) has been reached.



Remedy:


  • Select a flatter speed ramp.

  • Reduce the load.

  • Set the Imax controller (0x2B08 | 0x3308) more dynamically.


0x2387

Clamp responded too often

Cause:

Maximum current of the axis (display in 0x2DDF:2 | 0x35DF:2) was reached too often in a row.



Remedy:


  • Select a flatter speed ramp.

  • Reduce the load.

  • Set the Imax controller (0x2B08 | 0x3308) more dynamically.


0x2390

Fault - utilisation of the power section (Ixt) too high

Cause:

Frequent and too long acceleration processes with overcurrent in combination of both axes.



Remedy:


  • Check drive sizing of both axes.


0x2391

Warning - utilisation of the power section (Ixt) too high

Cause:

Frequent and too long acceleration processes with overcurrent in combination of both axes.



Remedy:


  • Check drive sizing of both axes.


0x2392

Fault - device utilisation (Ixt) too high

Cause:

Frequent and too long acceleration processes with overcurrent in combination of both axes.



Remedy:


  • Check drive sizing of both axes.


0x2393

Warning - device utilisation (Ixt) too high

Cause:

Frequent and too long acceleration processes with overcurrent in combination of both axes.



Remedy:


  • Check drive sizing of both axes.


0x3210

DC bus - overvoltage [value] V

Cause:

Due to a too high braking energy, the DC-bus voltage exceeds the overvoltage threshold which results from the mains voltage setting.



Remedy:


  • Connect brake resistor to power supply module or use regenerative module.

  • Check mains setting.

  • Check drive profile.


0x3220

DC bus - undervoltage [value] V

Cause:

DC bus voltage is lower than the undervoltage threshold resulting from the mains setting.



Remedy:


  • Check mains voltage.

  • Check DC-bus voltage.

  • Check mains settings.


0x4210

Module temperature too high, [value]

Cause:

Heatsink temperature higher than fixed temperature limit (100 °C):

  • i700 servo inverters ambient temperature too high.

  • Dirty fan or ventilation slots.

  • Fan defective.

  • Warning threshold set too low.




Remedy:


  • Check control cabinet temperature.

  • Clean filter.

  • Clean i700 servo inverters.

  • Replace fan.


0x4280
Internal fault - module temperature monitoring

Cause: Thermal sensor error.



Remedy:

  • 24 V mains switching required.

  • If the error occurs frequently, please contact Lenze.


0x4310
Motor temperature too high, [value]

Cause: Motor temperature higher than variable temperature limit:

  • Motor too hot due to impermissibly high currents or frequent and too long acceleration processes.

  • No KTY connected.

  • Error or warning threshold set too low.





Remedy:

  • Check drive dimensioning.

  • Connect KTY or switch off monitoring.

  • Set a higher warning or error threshold.


0x4380
Motor temperature sensor

Cause: Motor temperature sensor.



Remedy:

  • Connect KTY or switch off monitoring.

  • Set a higher warning or error threshold.


0x5112
24 V supply

Cause: 24 V supply has failed or has fallen below the warning threshold (21.45 V) or error threshold (18.15 V).



Remedy:

  • Check 24 V voltage supply.


0x6010
Watchdog reset

Cause:

  • Reset was triggered via device command 1100.

  • Internal error.





Remedy:

  • If the reset was not triggered via the device command, consult Lenze if the error occurs frequently.


0x6080
The new firmware is incompatible

Cause:

  • The redownloaded firmware is incompatible to the one on the device.

  • The new firmware has not been accepted.





Remedy:

  • Download a compatible firmware version (same major version).

  • If the current firmware shall be maintained, the error can simply be acknowledged.


0x6310
Incorrect parameter set download

Cause: Error when downloading a parameter set:

  • CRC error in the parameter set detected.

  • Vendor, product code or revision of the object directory are different.

  • Unknown parameter set.





Remedy:

  • Repeat parameter set download.

  • Recreate parameter set.


0x6320
Parameter error in object [value]

Cause: Unknown index in the parameter set.



Remedy:

  • Recreate parameter set.


0x7121
PLI - motor blocked

Cause: An error occurred during the pole position identification. The pole position identification could not be completed successfully:

  • Too many deviations during the identification.

  • Motor is blocked.





Remedy:

  • Check whether all requirements for an identification of the pole position are fulfilled.

  • Ensure that the machine is not braked or blocked during the pole position identification.

  • Repeat the pole position identification.


0x7303
Error in feedback system

Cause:

  • Encoder cable interrupted.

  • Encoder defective.





Remedy:

  • Check encoder cable.

  • Check encoder.

  • Switch off monitoring if feedback is not used.


0x7380
Hiperface communication error

Cause: Communication with HIPERFACE® absolute value encoder is disturbed.



Remedy:

  • Check the supply voltage of the encoder (0x2C42:2 | 0x3442:2).

  • Check wiring to the encoder.


0x7381
Hiperface: Wrong absolute value - motor speed too high

Cause: The absolute position of the HIPERFACE® absolute value encoder cannot be accepted as the motor rotates too fast.



Remedy:

  • Let the motor coast.


0x8180
ECAT DC - synchronisation required

Cause: EtherCAT DC mode not activated. (DC = Distributed Clock).



Remedy:

  • Activate DC mode.


0x8181
EtherCAT communication

Cause: EtherCAT communication error.



Remedy:

  • Check EtherCAT bus cabling.

  • Select a longer PDI watchdog time.


0x8280
Sync Manager - address [value]

Cause: Incorrect Sync Manager setting of the EtherCAT master.



Remedy:

  • Check the devices on the bus.

  • Check cabling or sequence of the devices on the bus.

  • Remove the i700 servo inverter from the project tree and rescan the bus.

  • Check the device description of the i700 servo inverter.


0x8281
Sync Manager - current size [value]

Cause: Incorrect Sync Manager setting of the EtherCAT master.



Remedy:

  • Check the devices on the bus.

  • Check cabling or sequence of the devices on the bus.

  • Remove the i700 servo inverter from the project tree and rescan the bus.

  • Check the device description of the i700 servo inverter.


0x8282
Sync Manager - settings [value]

Cause: Incorrect Sync Manager setting of the EtherCAT master.



Remedy:

  • Check the devices on the bus.

  • Check cabling or sequence of the devices on the bus.

  • Remove the i700 servo inverter from the project tree and rescan the bus.

  • Check the device description of the i700 servo inverter.


0x8283
PDO mapping: Object unknown (index [value])

Cause: Unknown index in the PDO mapping.



Remedy:

  • Check PDO mapping.


0x8284
No PDO mapping object (index [value])

Cause: Index cannot be mapped as PDO.



Remedy:

  • Check PDO mapping.


0x8285
Too many objects mapped (max. number = [value])

Cause: Max. number of PDO mapping objects has been exceeded (> 64).



Remedy:

  • Reduce the number of mapping objects in the "free mapping".


0x8286

PDO mapping - error

Cause:

Incorrect PDO mapping.



Remedy:

Check PDO mapping.
Response: Interference

0x8700

Sync controller

Cause:

  • EtherCAT Sync0 signal has failed.

  • PDO transmitted or received too late.




Remedy:

  • Check in EtherCAT master configuration whether DC mode is set.

  • Restart EtherCAT configuration.

  • Select a later instant of reception, outside the user shift time.

  • Sync Error Counter - increase monitoring limit (0x10F1:2).


Response: Class II fault. The response set in 0x605E | 0x685E takes place.

0x8701

Time-out during synchronisation with EtherCAT sync signal

Cause:

During the EtherCAT state change from "Pre-Operational" to "Safe-Operational":

  • EtherCAT Sync0 signal has failed.

  • Jitter of the EtherCAT Sync0 signal is too high.




Remedy:

  • Check EtherCAT master configuration for DC deviation.

  • Restart EtherCAT configuration.


Response: Interference

0xFF00

Fatal internal error

Cause:

Internal error.



Remedy:

  • 24 V mains switching required.

  • If the error occurs frequently, please contact Lenze.


Response: Interference

0xFF01

Fatal internal communication error, cycle [value]

Cause:

Internal error.



Remedy:

  • 24 V mains switching required.

  • If the error occurs frequently, please contact Lenze.


Response: Interference

0xFF02

Brake

Cause:

Brake error due to short circuit or cable break.



Remedy:

Check brake cable or brake.
Response: Warning in "manual control" mode. Otherwise class II fault. If "fault" is set, the response set in 0x605E | 0x685E takes place.

0xFF03

Fatal internal error overflow task

Cause:

Internal error.



Remedy:

  • 24 V mains switching required.

  • If the error occurs frequently, please contact Lenze.


Response: Interference

0xFF04

PLI - motor movement too large

Cause:

Motor moved too much during pole position identification.



Remedy:

  • Check settings of the pole position identification in 0x2C62 | 0x3462.

  • If this error takes place in pole position identification without any motion, the motor has to be stalled.


Response: Fault (adjustable in 0x2C60 | 0x3460)

0xFF05

STO inhibited

Cause:

The servo inverter is inhibited via STO terminals, despite controller enable via the control word.



Remedy:

  • Deactivate STO or inhibit the servo inverter.

  • Check the cabling of the STO terminals.


Response: Warning with change to the "Switch on disabled" device status.

0xFF06

Max. speed reached

Cause:

Motor speed too high.



Remedy:

  • Reduce motor speed.

  • Check resolver or cabling.


Response: Fault (adjustable in 0x2D44:2 | 0x3544:2). Threshold can be adapted in 0x2D44:1 | 0x3544:1.

0xFF07

Impermissible during identification or in test mode

Cause:

A parameter was attempted to change which influences the identification in progress or the currently activated test mode.



Remedy:

Postpone changing the parameter until the identification is completed or the test mode is deactivated again.
Response: Warning

0xFF08

Impossible during identification

Cause:

A parameter was attempted to change which influences the identification in progress.



Remedy:

Postpone changing the parameter until the identification is completed.
Response: Warning

0xFF09

Motor phase failure

Cause:

Multiple motor phases are not connected.



Remedy:

  • Correct the wiring between the servo inverter and the motor.

  • In the case of a false alarm, increase the threshold values for monitoring in 0x2D45 | 0x3545.


Response: Default setting: No response. Monitoring takes place before and during operation.

0xFF0A

Motor phase failure phase U

Cause:

Motor phase U is not connected.



Remedy:

  • Correct the wiring between the servo inverter and the motor.

  • In the case of a false alarm, increase the threshold values for monitoring in 0x2D45 | 0x3545.


Response: Default setting: No response.

0xFF0B

Motor phase failure phase V

Cause:

Motor phase V is not connected.



Remedy:

  • Correct the wiring between the servo inverter and the motor.

  • In the case of a false alarm, increase the threshold values for monitoring in 0x2D45 | 0x3545.


Response: Default setting: No response.

0xFF0C

Motor phase failure phase W

Cause:

Motor phase W is not connected.



Remedy:

  • Correct the wiring between i700 servo inverters and motor.

  • In the case of a false alarm, increase the threshold values for monitoring in 0x2D45 | 0x3545.


Response: Default setting: No response.

0xFF0E

Speed too low --> command cannot be executed

Cause:

The actual speed is too low for the resolver error to be identified.



Remedy:

Repeat identification at higher speed.
Response: Warning

0xFF0F

No resolver connected --> command cannot be executed

Cause:

The identification of a resolver error was attempted but an encoder is used as feedback system.



Remedy:

Identification is only possible with devices with resolver feedback.
Response: Warning

0xFF10

Time-out

Cause:

The actual speed is too low for the resolver error to be identified.



Remedy:

Repeat identification at higher speed.
Response: Warning

0xFF11

Numerical problem

Cause:

The actual speed is too low for the resolver error to be identified.



Remedy:

Repeat identification at higher speed.
Response: Warning

0xFF12

Inverter error too big

Cause:

The results of the inverter error identification are not plausible.



Remedy:

Check shielding of the motor cable. Connect the shield with a surface as large as possible.
Response: Warning

0xFF13

Identification aborted

Cause:

A started identification was aborted due to an error or a controller inhibit.



Remedy:

Repeat the identification and avoid the cause of the abort.
Response: Faulty pole position identification (adjustable in 0x2C60 | 0x3460). Otherwise warning.

0xFF14

Impossible in the 'operation enabled' or 'quick stop active' state

Cause:

Reading out and accepting the hiperface data is only permitted when the controller is inhibited.



Remedy:

Inhibit controller.
Response: Warning

0xFF15

No Hiperface absolute value encoder connected --> command cannot be executed

Cause:

When the "resolver" device version or the sin/cos encoder has been selected, an attempt is being made to read the data from a HIPERFACE® absolute value encoder.



Remedy:

The command is only possible with the "encoder" device version. Moreover, the "2: Hiperface absolute value encoder" selection has to be set in 0x2C40 | 0x3440.
Response: Warning

0xFF16

Connected Hiperface absolute value encoder is not supported

Cause:

The HIPERFACE® absolute value encoder has a type code which is neither stored in the firmware nor corresponds to the type code set in 0x2C41:2 | 0x3441:2.



Remedy:

Set type code in 0x2C41:2 | 0x3441:2.
Response: Fault (adjustable in 0x2C41:4 | 0x3441:4)

0xFF17

Connected Hiperface absolute value encoder is not supported --> Command cannot be executed

Cause:

The HIPERFACE® absolute value encoder is not supported by the device. Hence, no data can be detected.



Remedy:

Connect a HIPERFACE® absolute value encoder which is supported by the device.
Response: Warning

0xFF18

Communication time-out in manual control mode

Cause:

In the "manual control" mode, writing the setpoint data failed to appear for a longer period of time than set in 0x2836:5 | 0x3036:5.



Remedy:

  • Check connection between device, Controller and »EASY Starter« or »PLC Designer«.

  • Increase the time period in 0x2836:5 | 0x3036:5.

  • Restart manual jog dialog.


Response: Interference

0xFF19

Internal error during identification

Cause:

Internal error during identification.



Remedy:

Please contact Lenze.
Response: Warning

0xFF20

The check of the Replacement Protection has failed

Cause:

The check of the Replacement Protection has failed.



Remedy:

  • Enter correct Replacement Protection ID.

  • Replace device by an OEM device.

  • Reprogram Replacement Protection ID.


0xFF21

Time-out - holding brake feedforward control

Cause:

The given feedforward control torque could not be built up within one second.



Remedy:

-
0xFF22

Speed error occurred

Cause:

The speed error exceeds the limit from 0x2D51:1 / 0x3551:1 for a time period > 0x2D51:2 / 0x3551:2.



Remedy:

  • Increase time-out in 0x2D51:2 or 0x3551:2.

  • Increase limit in 0x2D51:1 or 0x3551:1.

  • Increase speed controller gain.

  • Increase torque and/or current limit.


0xFF23

Position error occurred

Cause:

The check of the Replacement Protection has failed.



Remedy:

  • Increase time-out in 0x2D51:4 or 0x3551:4.

  • Increase limit in 0x2D51:2 or 0x3551:2.

  • Increase position controller gain.


0xFF24

Sync0 cycle time is invalid

Cause:

The requested Sync0 cycle on the Ethercat is not within the limits 125 µs ≤ x ≤ 10 ms anymore supported by this device.



Remedy:

Select another Sync0 cycle in the control for this bus interconnection that is within the limits 125 µs ≤ x ≤ 10 ms.
0xFF25

The hardware is not supported

Cause:

Internal error.



Remedy:

Exchange software with older version (< 1.10.xx).
0xFF26

Cable Check - motor movement too great

Cause:

During the Cable Check, the motor "jumps" to a new position.



Remedy:

  • Phase shifter in the motor cable: Swap two phases of the motor cable.

  • Axis was moved manually: Stop axis.

  • Motor parameters (number of pole pairs, motor type) are not set correctly: Set motor parameters correctly.

  • Synchronous machine - the pole position is set incorrectly: Set pole position correctly.

  • Motor with brake - the brake was released early by an external source: Prevent the brake to be released by an external source.


0xFF27

Cable Check - incorrect direction of rotation

Cause:

During the wiring test, the motor cannot follow the specified angle.



Remedy:


  • Motor and encoder cable do not lead to the same motor:

    • Up to Softwarestand V02.10.xx: Identify a common motor and encoder cable.

    • From V02.11.xx: Switch off current supply, correct wiring, then switch on and execute Cable Check again.




  • Phase shifter in the motor cable:

    • Up to Softwarestand V02.10.xx: Switch off current supply, swap two phases of motor cable.

    • From V02.11.xx: Switch off current supply, swap two phases, then switch on and execute Cable Check again.



  • Missing motor phase(s): Check motor phase(s).

  • Motor without brake: Test current is not high enough or machine is blocked. Check mechanics.

  • Motor with brake: Brake is so strong no movement is detected. Ensure motor can rotate freely.

  • Incorrect pole position: Switch off current supply, correct wiring. Switch on, carry out pole position identification, then execute Cable Check again.

  • Motor and encoder data possibly incorrect: Compare parameter data with nameplate and correct if necessary.


0xFF28

Master password entered incorrectly 4 times

Cause:

An incorrect master password was used for the log-in too frequently.



Remedy:

  • Use the correct master password for the log-in.

  • Switch mains to delete the warning.


How to Clear & Reset Lenze i700 Cabinet Drive Faults

  1. EtherCAT CiA 402 Controlword Reset: From the central machine motion controller (e.g., Lenze Controller 3200 C, c300, or external EtherCAT master), pulse Bit 7 (Fault Reset) from `0` to `1` in the CiA 402 Controlword (object 0x6040) for the affected axis.
  2. Lenze EASY Starter Engineering Tool: Connect your engineering PC to the drive line via Ethernet/EtherCAT, launch Lenze EASY Starter, navigate to the diagnostic/error history menu, and click “Reset Error” on the axis in trip status.
  3. Safe Torque Off (STO) Interlock Check: If an STO safety interlock trip is triggered, verify dual-channel 24V DC signals at terminals STO-A and STO-B (X6 terminal strip). Once the safety circuit is closed and healthy, issue a fault reset command.
  4. PLC Application Routine: Initiate an automated axis reset command through your PLC motion control function blocks (e.g., MC_Reset). Ensure the motion profile command is aborted before resetting axis faults.
  5. Complete DC Bus & 24V Logic Power Cycle: Switch off the main 400V/480V line feed to the power supply module and 24V control supply. Wait at least 5 to 10 minutes for all shared DC intermediate bus capacitors across the interconnected rack to discharge completely before re-energizing.
⚠️ High-Voltage Electrical Safety Warning: The Lenze i700 multi-axis system shares a high-capacity common DC intermediate busbar (+UG, -UG) across all connected power supply and axis modules. Dangerous voltages up to 800V DC remain stored long after AC power is disconnected. Always wait at least 5 to 10 minutes and measure with a calibrated multimeter to verify DC bus voltage is strictly below 50V DC across bus links and motor terminals (U, V, W) before touching wiring or removing axis modules.