Lenze MC 3000 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, display status explanations, and step-by-step diagnostic procedures for the Lenze / AC Tech MC 3000 series industrial frequency inverter. Search or filter through the complete fault directory below.

Enclosed AC Motor Control Power: 0.18 to 110 kW (0.25 to 150 HP) Local / Remote Process Control
Power Range 0.18 – 110 kW (0.25 – 150 HP)
Supply Voltage 120V / 208–240V / 400–480V / 590V
Control Modes V/Hz (Constant & Variable Torque)
Operator Interface 16-Char LCD w/ Local/Remote Key

Complete Lenze MC 3000 Drive Fault Code Directory

Use the search box in the table below to quickly find your fault message (e.g., type OVERLOAD, HIGH VOLTS, OUTPUT FAULT, or EPM FAULT).

Fault Code and MeaningCause and Remedy
OUTPUT

Output transistor fault: Output current exceeded 200% of drive rating

Cause:

  • Phase to ground short.

  • Phase to phase short.

  • FX BOOST set too high.

  • Bad transistor module (IPM).




Remedy:

  • Check motor and cabling for shorts.

  • Check drive rating against application.


LO VOLTS

Low DC Bus Voltage fault: DC bus voltage below 60% of normal.

Cause:

  • Low line voltage.




Remedy:

  • Check incoming AC power supply.


HI VOLTS

High DC Bus Voltage fault: DC bus voltage above 120% of normal.

Cause:

  • High line voltage.

  • Overhauling load.

  • DECEL rate is set too fast.




Remedy:

  • Check incoming AC line voltage.

  • Increase deceleration time.

  • Install dynamic braking resistor if necessary.


HI TEMP

Temperature fault: Internal drive temperature too high.

Cause:

  • Ambient temperature too high.

  • Fan failure (if equipped).




Remedy:

  • Check cabinet ventilation and ambient temperature.

  • Inspect cooling fans.


OVERLOAD

Current Overload fault: Output current rating exceeded for too long.

Cause:

  • Drive undersized for the application.

  • Problem with motor and/or driven equipment.




Remedy:

  • Check motor sizing.

  • Check for mechanical binding or load issues.

  • Wait 3 minutes for cool down (UL508C requirement).


PWR TRAN

Power Transient fault: Low line voltage.

Cause:

  • AC line dipped or sagged.




Remedy:

  • Check AC power supply stability.


PWR SAG

Power Sag fault: Control board voltage is below tolerance.

Cause:

  • Erratic AC line.

  • A new control board has been installed that is different from the previous version.




Remedy:

  • Perform a factory reset using Parameter 65-PROGRAM. (This will update the software and allow the fault to be reset).


LANGUAGE

Language fault: Selected language not present.

Cause:

  • Defective language EEPROM.

  • Language EEPROM (U11) removed after programming.




Remedy:

  • Check EEPROM installation.


EXTERNAL

External fault: TB-13D is open or closed to TB-2, depending on setting of Parameter 50 - TB13D.

Cause:

  • External device triggered.

  • Wiring issue on terminal inputs.




Remedy:

  • Check setting of Parameter 50.

  • Check devices wired between TB13D and TB-2.


DB ERROR

Dynamic Brake fault: DB circuit has sensed a resistor overload.

Cause:

  • The DB duty cycle is too high, causing the resistors to overheat.




Remedy:

  • Reduce braking requirements or cycle time.

  • Check resistor sizing.


CONTROL

Control Board fault: New software has been installed that is different from the previous version.

Cause:

  • Software version mismatch.




Remedy:

  • Perform a factory reset using Parameter 65-PROGRAM.

  • This will update the software and allow the fault to be reset.


INTERNAL / INTERN (#)

Internal fault: The micro-processor has sensed a problem.

Cause:

  • Electrical noise on control wiring.

  • Defective microprocessor.




Remedy:

  • Check control wiring shielding and grounding.

  • Cycle power.


FOLLOWER

Loss of Follower fault: 4-20 mA signal at TB-5B is below 2 mA.

Cause:

  • Parameter 55 - TB5B LOSS is set to FAULT.

  • Signal wire break or source failure.




Remedy:

  • Check signal wiring at TB-5B.

  • Check source signal generator.


Blank Display or repeatedly flashes TESTING

The power supply has shut down.

Cause:

  • This can be the result of clogged or failed heatsink fans.




Remedy:

  • Check heatsink fans (if equipped).

  • Clear any obstructions.

  • If heatsinks are not clogged, contact the Lenze AC Tech Service Department.


How to Clear & Reset Lenze MC 3000 Drive Faults

  1. Keypad Reset: Press the red STOP key on the front keypad. When in FAULT mode, pressing STOP clears the fault and returns the inverter to a STOP state. Note: If an OUTPUT FAULT occurs, the drive activates an intentional 30-second lockout delay before the STOP key can clear the alarm.
  2. Control Terminal Reset (TB-13): If a digital input terminal (such as terminal TB-13D) is programmed to CLEAR / FAULT RESET, momentary connection across TB-13D and circuit common TB-2 will reset the active fault.
  3. Serial Fieldbus Reset (Modbus RTU): Send a fault clear command across the 2-wire RS-485 serial communication port to clear fault registers remotely.
  4. EPM Fault Handling: If the unit trips on an EPM FAULT, verify that the Electronic Programming Module is firmly inserted into its socket on the control board before clearing or power cycling.
  5. Mains Power Cycle: Switch off the main AC supply disconnect. Wait at least 3 to 5 minutes until the LCD screen completely turns off and the internal DC bus capacitors discharge, then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning: Dangerous residual DC bus energy remains present within the drive capacitors after switching off line power. Always disconnect the main AC supply, wait a minimum of 5 minutes, and verify using a calibrated voltmeter that intermediate circuit DC bus voltage measures below 50V DC before servicing motor terminals (U/T1, V/T2, W/T3) or inspecting internal chassis wiring.