Lenze MC1000 drive

Home / Lenze / Lenze MC1000 drive

Lenze MC1000 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Lenze AC Tech MC1000 industrial drive series. Search or filter through the complete fault code directory below.

Constant Horsepower AC Drive Power: 0.18 to 110 kW (0.25 to 150 HP) NEMA 1, 12, 4 & 4X Enclosure Series
Power Range 0.18 – 110 kW (0.25 – 150 HP)
Supply Voltage 120V / 240V / 480V / 590V AC
Control Modes V/Hz Control & PID Loop
Operator Interface 16-Character LCD Keypad / Modbus

Complete Lenze MC1000 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OUTPUT, HIGH VOLTAGE, OVERLOAD, or HIGH TEMP).

Fault Code and MeaningCause and Remedy
OUTPUT

Output transistor fault:
Output current exceeded 200% of drive rating.

Cause:


  • Phase to ground short.

  • Phase to phase short.

  • FX or AC BOOST set too high.

  • Bad transistor module (IPM).




Remedy:

Check motor wiring and motor for shorts. Check drive settings.
LO VOLTS

Low DC Bus Voltage fault:
DC bus voltage below 60% of normal.

Cause:

Low line voltage.



Remedy:

Check AC input power.
HI VOLTS

High DC Bus Voltage fault:
DC bus voltage above 120% of normal.

Cause:


  • High line voltage.

  • Overhauling load.

  • DECEL rate is set too fast.




Remedy:

Check input voltage. Adjust deceleration time.
HI TEMP

Temperature fault:
Internal drive temperature too high.

Cause:


  • Ambient temperature too high.

  • Fan failure (if equipped).




Remedy:

Check cooling fans and cabinet ventilation.
OVERLOAD

Current Overload fault:
Output current rating exceeded for too long.

Cause:


  • Drive undersized for the application.

  • Problem with motor and/or driven equipment.




Remedy:

Check mechanical load and motor sizing. (Note: 3-minute delay before reset is possible).
PWR TRAN

Power Transient fault:
Low line voltage.

Cause:

AC line dipped or sagged.



Remedy:

Check mains supply stability.
PWR SAG

Power Sag fault:
Control board voltage is below tolerance.

Cause:


  • Erratic AC line.

  • A new control board has been installed that is different from the previous version.




Remedy:

Perform a factory reset using Parameter 65-PROGRAM. This will update the software and allow the fault to be reset.
LANGUAGE

Language fault:
Selected language not present.

Cause:


  • Defective language EEPROM.

  • Language EEPROM (U11) removed after programming.




Remedy:

Replace or reinstall EEPROM.
EXTERNAL

External fault:
TB-13D is open or closed to TB-2, depending on the setting of Parameter 50 - TB13D.

Cause:

External device triggered fault or wiring issue.



Remedy:


  • Check setting of Parameter 50 - TB 13D.

  • Check devices wired between TB13D and TB-2.


DB ERROR

Dynamic Brake fault:
DB circuit has sensed a resistor overload.

Cause:

The DB duty cycle is too high, causing the resistors to overheat.



Remedy:

Reduce duty cycle or check resistor sizing.
CONTROL

Control Board fault:
New software has been installed that is different from the previous version.

Cause:

Software/Hardware mismatch.



Remedy:

Perform a factory reset using Parameter 65-PROGRAM. This will update the software and allow the fault to be reset.
INTERNAL / INTERN (#)

Internal fault:
The micro-processor has sensed a problem.

Cause:


  • Electrical noise on control wiring.

  • Defective microprocessor.




Remedy:

Check control wiring shielding.
FOLLOWER

Loss of Follower fault:
4-20 mA signal at TB-5B is below 2 mA.

Cause:

Signal loss on input.



Remedy:

Parameter 55 - TB5B LOSS is set to FAULT. Check signal source.
Blank Display / TESTING

The power supply has shut down.
(Drive will not run).

Cause:

This can be the result of clogged or failed heatsink fans.



Remedy:


  • Check heatsink fans (if equipped).

  • Clear any obstructions.

  • If they are not clogged, contact the Lenze AC Tech Service Department.


How to Clear & Reset Lenze MC1000 Drive Faults

  1. Keypad STOP Key Reset: Press the red STOP key on the front keypad. If an OUTPUT transistor fault has tripped the drive, an internal 30-second thermal safety delay must expire before the STOP key can successfully clear the message.
  2. Digital Terminal Strip Reset: If any terminal among TB-13A, TB-13B, TB-13C, or TB-13D is configured for external reset via Parameters 48–50, momentary contact closure to terminal TB-11 will reset the drive to a stopped state.
  3. RS-485 Serial Communication: Send a remote trip reset command across the built-in EIA-485 serial communications network using standard Modbus RTU protocol registers.
  4. Automatic Restart (Parameter 04): If enabled under Parameter 04, the inverter will automatically attempt to clear transient line sags and power dips and restart unattended equipment after an engineered time delay.
  5. Line Power Cycling: Disconnect AC input mains power, wait at least 5 minutes until the 16-character alphanumeric display is completely blank and the high-voltage bus bleeder circuit discharges, then re-apply line power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous residual electrical charge remains stored in internal intermediate DC bus capacitors even after incoming AC power is disconnected. Always wait a minimum of 5 minutes after de-energizing the unit, and verify with a calibrated DC voltmeter that voltage across DC bus/braking terminals is strictly below 50VDC before inspecting motor leads (TB-1, TB-2, TB-3) or touching internal chassis components.