Lenze SCF Series Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip error causes, and step-by-step troubleshooting procedures for the Lenze AC Tech SCF Series sub-micro inverter. Search or filter through the complete diagnostic directory below.

Sub-Micro AC Drive Power: 0.18 to 22 kW (0.25 to 30 HP) Removable EPM Architecture
Power Range 0.18 – 22 kW (0.25 – 30 HP)
Supply Voltage 120V / 208–240V / 400–590V AC
Control Modes V/Hz (Volts/Hertz) Control
Operator Interface 3-Digit LED / Remote Keypad / EPM

Complete Lenze SCF Series Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OF, HF, PF, or Overcurrent).

Fault Code and MeaningCause and Remedy
AF
High Temperature Fault

Cause: Ambient temperature is too high; Cooling fan has failed (if equipped).



Remedy: Check installation environment and cooling fans.
CF
Control Fault

Cause: A blank EPM, or an EPM with corrupted data has been installed.



Remedy: Perform a factory reset using Parameter 48 - PROGRAM SELECTION.
cF
Incompatibility Fault

Cause: An EPM with an incompatible parameter version has been installed.



Remedy: Either exchange the EPM, or perform a factory reset (Parameter 48) to change the parameter version of the EPM to match the parameter version of the drive.
dF
Dynamic Braking Fault

Cause: The drive has sensed that the dynamic braking resistors are overheating and shuts down to protect the resistors.



Remedy: Allow resistors to cool. Check sizing of braking resistors or duty cycle.
EF
External Fault

Cause: TB-13A and/or TB-13C is set as an External Fault input and TB-13A and/or TB-13C is open with respect to TB-2.



Remedy: Refer to Parameter 10 or 12. Check external wiring.
GF
Data Fault

Cause: User data and OEM defaults in the EPM are corrupted.



Remedy: Perform a factory reset or replace EPM.
HF
High DC Bus Voltage Fault

Cause: Line voltage is too high; Deceleration rate is too fast; Overhauling load.



Remedy: Check line voltage. For fast deceleration or overhauling loads, dynamic braking may be required.
JF
Serial Fault

Cause: The watchdog timer has timed out, indicating that the serial link has been lost.



Remedy: Check serial communication wiring and master controller.
LF
Low DC Bus Voltage Fault

Cause: Line voltage is too low.



Remedy: Check input power source and fuses. (Fault clears when voltage returns to normal).
OF
Output Transistor Fault

Cause: Phase to phase or phase to ground short circuit on the output; Failed output transistor; Boost settings are too high; Acceleration rate is too fast.



Remedy: Check motor wiring and insulation. Check boost settings (P11) and acceleration time (P01).
PF
Current Overload Fault

Cause: VFD is undersized for the application; Mechanical problem with the driven equipment.



Remedy: Check drive sizing vs motor load. Inspect driven machinery for jams or friction.
SF
Single-phase Fault

Cause: Single-phase input power has been applied to a three-phase drive.



Remedy: Check input power connections. Ensure three-phase power is applied.
UF
Start Fault

Cause: Start command was present when the drive was powered up.



Remedy: Must wait 2 seconds after power-up to apply Start command if START METHOD is set to NORMAL.
F1
EPM Fault

Cause: The EPM is missing or damaged.



Remedy: Install or replace the EPM.
F2 - F9, Fo
Internal Faults

Cause: The control board has sensed a problem.



Remedy: Consult factory.
br
DC BRAKING

Cause: The DC braking circuit is activated.



Remedy: Status message only. Normal operation during DC injection braking.
cE
Configuration Error

Cause: An EPM from a drive with a previous parameter version is installed into a new drive, and an attempt is made to change any parameter settings.



Remedy: The parameters cannot be changed until the Translate function is performed (parameter 48, setting 06).
CL
CURRENT LIMIT

Cause: The output current has exceeded the CURRENT LIMIT setting (Parameter P25) and the drive is reducing the output frequency to reduce the output current.



Remedy: Reduce load. If the drive remains in CURRENT LIMIT for too long, it can trip into a CURRENT OVERLOAD fault (PF).
Er
ERROR

Cause: Invalid data has been entered or an invalid command was attempted.



Remedy: Check range of parameter being entered or command sequence.
GE
OEM Settings Error

Cause: Attempt made to change the OEM default settings when the drive is operating in the OEM mode (see Parameter 48).



Remedy: Disable OEM mode if changes are required.
GF
OEM Data Corruption

Cause: OEM defaults in the EPM are corrupted (displayed when RESET OEM is attempted or upon power-up).



Remedy: Refer to Section 13.1 (Manual Reset/Troubleshooting).
LC
FAULT LOCKOUT

Cause: The drive has failed three restart attempts.



Remedy: Requires a manual reset (STOP command).
SE
SERIAL

Cause: The optional remote keypad is active as the user interface instead of the buttons on the front of the drive.



Remedy: See Parameter 14 - CONTROL to change control source.
SP
START PENDING

Cause: “SP” blinks during the interval between restart attempts.



Remedy: Wait for restart timer to complete.
(Symbol)
DECEL OVERRIDE

Cause: The drive has stopped decelerating to avoid tripping into an HF fault due to regenerative energy from the motor.



Remedy: Drive will resume deceleration once DC bus voltage drops.

How to Clear & Reset Lenze SCF Series Drive Faults

  1. Terminal Strip Reset: Issue a STOP command by opening the run/start circuit on terminal strip TB-2 (e.g., opening terminal 1 to terminal 2 / 12 on standard 2-wire or 3-wire wiring). The fault clears once the cause is resolved and a stop state is asserted.
  2. Remote Keypad Reset: If using the optional NEMA 4X remote keypad, press the red STOP / RESET push button to clear the latched error code.
  3. Clearing Fault Lockout (LC): If the drive trips into LC (Fault Lockout) following three unsuccessful auto-restart cycles (Parameter 03), clear the cause and remove and reapply the start/run command to reset the lockout state.
  4. Modbus RTU Control Word: Write a reset bit command to Register #24 via the 2-wire RS-485 serial communication link to clear active trips remotely.
  5. Power Cycle: Disconnect AC input power, wait at least 3 to 5 minutes until the 3-digit LED display completely powers down and internal DC capacitors discharge, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always allow internal filter capacitors at least 3 to 5 minutes to discharge after disconnecting AC power. Before touching terminal connections, opening covers, or checking motor cables on terminals U, V, and W, verify with a calibrated multimeter that DC bus voltage is strictly below 50VDC.