Lenze SMD Series Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip error causes, and step-by-step troubleshooting procedures for the Lenze AC Tech SMD Series sub-micro inverter. Search or filter through the complete diagnostic directory below.
Power Range
0.25 – 22 kW (0.33 – 30 HP)
Supply Voltage
120V / 208–240V / 400–480V AC
Control Modes
V/Hz (Linear & Quadratic)
Operator Interface
3-Digit LED / Keypad & EPM Chip
Complete Lenze SMD Series Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OF, HF, PF, or cF).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 50.0 (e.g.) Present output frequency | Cause: Trouble free operation. Remedy: (None required) |
| OFF Stop (outputs U, V, W inhibited) | Cause: LOW signal at terminal 28. Remedy: Set terminal 28 to HIGH. |
| StP Output frequency = 0 Hz (outputs U, V, W inhibited) | Cause:
Remedy:
|
| br DC-injection brake active | Cause: DC-injection brake activated:
Remedy: Deactivate DC-injection brake:
|
| CL Current limit reached | Cause: Controllable overload. Remedy: Automatically (see C22). |
| LU Undervoltage on DC bus | Cause: Mains voltage too low. Remedy: Check mains voltage. |
| dEC Overvoltage on DC bus during deceleration (warning) | Cause: Excessively short deceleration time (C13, c03). Remedy: Automatically if overvoltage < 1 s, OU if overvoltage > 1 s. |
| nEd No access to code | Cause: Can only be changed when the controller is in OFF. Remedy: Set terminal 28 to LOW. |
| cF / GF Data on EPM not valid | Cause:
Remedy:
|
| F1 EPM error | Cause: EPM missing or defective. Remedy: Power down and replace EPM. |
| CFG Digital inputs not uniquely assigned | Cause:
Remedy:
|
| EEr External error | Cause: Digital input “TRIP set” is active. Remedy: Remove external error. |
| F2...F0, JF Internal fault | Cause: Internal drive fault. Remedy: Please contact Lenze. |
| LC Automatic start inhibited | Cause: c42 = 0. Remedy: LOW-HIGH signal change at terminal 28. |
| OC1 Short-circuit or overload | Cause:
Remedy:
|
| OC2 Earth fault | Cause:
Remedy:
|
| OC6 Motor overload (I²t overload) | Cause: Motor is thermally overloaded, due to:
Remedy:
|
| OH Controller overtemperature | Cause: Controller too hot inside. Remedy:
|
| OU Overvoltage on DC bus | Cause:
Remedy:
|
| rSt Faulty auto-TRIP reset | Cause: More than 8 errors in 10 minutes. Remedy: Depends on the error. |
| Sd5 Loss of 4-20 mA reference | Cause: 4-20 mA signal is below 2 mA (C34 = 4). Remedy: Check signal/signal wire. |
| SF Single phase fault | Cause: A mains phase has been lost. Remedy: Check mains voltage. |
How to Clear & Reset Lenze SMD Series Drive Faults
- Terminal Enable / Stop Reset: Deactivate the start or enable signal by opening the circuit at digital control terminal 28 (or terminal E1 / E2 depending on terminal mode). Once the fault cause is cleared, removing the run enable signal resets the drive trip state.
- Front Panel Keypad: If configured for keypad control (Parameter P02 = 1 or 2), press the STOP button on the integrated keypad faceplate to clear an active fault message.
- Clearing Fault Lockout (LC): If the drive enters LC (Fault Lockout) after exhausting automatic restart attempts (configured in Parameter P03), rectify the root trip cause and open terminal 28 to reset the lockout counter.
- EPM Module Reseat / Re-copy: For persistent cF (Control Fault) or F1 codes, turn off power, verify that the blue Electronic Programmable Module (EPM) is securely seated in its front slot, or reload parameter data using the EPM programmer.
- Power Cycle: Disconnect AC line power completely. Wait at least 3 minutes until the 3-digit LED display completely shuts off and the internal DC bus capacitors discharge, then re-energize the unit.
⚠️ High-Voltage Electrical Safety Warning:
Always disconnect incoming mains AC power and wait a minimum of 3 minutes for internal DC filter capacitors to safely discharge. Verify with a calibrated multimeter that DC bus voltage measures strictly below 50VDC before inspecting wiring or touching terminals L1, L2, L3, U, V, and W on the Lenze SMD drive.