Omron 3G3MX2-V1 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Omron 3G3MX2-V1 multi-function compact inverter series. Search or filter through the complete fault code directory below.

Multi-Function Compact Inverter Power: 0.1 to 15 kW (1/8 to 20 HP) Built-in Safe Torque Off (STO – Cat 3 / SIL2)
Power Range 0.1 – 15 kW (1/8 – 20 HP)
Supply Voltage 1-Ph 200V / 3-Ph 200V & 400V
Control Modes Sensorless Vector & V/f Control
Operator Interface Integrated LED Keypad / CX-Drive

Complete Omron 3G3MX2-V1 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E01, E07, or Overcurrent).

Fault Code and MeaningCause and Remedy
E01
Overcurrent protection (Constant speed)

Cause:

The inverter output current exceeded approximately 200% of the rated output current during constant speed operation. Possible causes include rapid load fluctuation, output short-circuit, or ground fault.



Remedy:


  • Eliminate load fluctuation.

  • Check the output wiring.

  • Check the output wiring and the motor for ground faults.


E02
Overcurrent protection (Deceleration)

Cause:

The inverter output current exceeded approximately 200% of the rated output current during deceleration.



Remedy:


  • Increase the deceleration time.


E03
Overcurrent protection (Acceleration)

Cause:

The inverter output current exceeded approximately 200% of the rated output current during acceleration.



Remedy:


  • Increase the acceleration time.

  • Check if the motor is locked (check motor and wiring).

  • Decrease the torque boost setting (if too high).

  • If a PM motor is in use, check if the motor is set and adjusted properly.


E04
Overcurrent protection (Others)

Cause:

Overcurrent detected during other states (e.g., DC injection braking power too high).



Remedy:


  • Decrease the braking power.


E05
Overload protection

Cause:

The internal electronic thermal function detected a motor overload.



Remedy:


  • Reduce the load rate (load is too heavy).

  • Adjust the thermal level setting (b012/b212) to an appropriate level.


E06
Braking resistor overload protection

Cause:

The usage rate of the regenerative braking circuit exceeded the value set in b090.



Remedy:


  • Increase the deceleration time.

  • Increase the operation cycle time.


E07
Overvoltage protection

Cause:

Extremely high DC voltage between P/+2 and N/- (approx 400 VDC for 200-V class or 800 VDC for 400-V class). Caused by regenerative energy or increased incoming voltage.



Remedy:


  • Increase the deceleration time.

  • Check the output wiring and motor for ground faults.

  • Decrease the amount of regeneration (if motor is rotated from load side).

  • Lower the incoming voltage or install an AC reactor to suppress fluctuation.


E08
EEPROM error

Cause:

Error in the built-in EEPROM due to external noise or abnormal temperature rise.



Remedy:


  • Take measures against noise (large noise source nearby).

  • Check the cooling fin for clogging and clean it.

  • Turn off power supply. If error persists, memory may be corrupt (perform initialization).


E09
Undervoltage

Cause:

Incoming voltage dropped below specified level, causing DC voltage to drop (approx 173 VDC for 200-V class or 345 VDC for 400-V class).



Remedy:


  • Check the power supply voltage.

  • Check the power supply capacity.

  • Check if the thyristor in the inrush current protection circuit is broken.


E10
Current detector error

Cause:

An error occurred in the current detector.



Remedy:


  • The inverter has a defect. Repair it.


E11
CPU error

Cause:

Malfunction or error in the built-in CPU.



Remedy:


  • Take measures against noise (large noise source nearby).

  • The inverter has a defect. Repair it.


E12
External trip

Cause:

The multi-function input terminal allocated to the External trip (12: EXT) function turned ON.



Remedy:


  • The external equipment has a defect. Check the external equipment.


E13
USP error

Cause:

The power supply was turned on while the RUN signal was ON (only when USP function is selected).



Remedy:


  • Check the RUN command (ensure it is off before power on).


E14
Grounding protection

Cause:

A ground fault was detected between the inverter output unit and the motor when power was turned on.



Remedy:


  • Check the output wiring and the motor for ground faults.

  • Disconnect output wiring and check the inverter itself.

  • Check the main circuit.


E15
Incoming overvoltage protection

Cause:

Incoming voltage remained in an overload state for 100 seconds (DC voltage approx 390 VDC for 200-V class or 780 VDC for 400-V class).



Remedy:


  • Lower the incoming voltage.

  • Suppress power supply fluctuation.

  • Install the AC reactor in the input power circuit.


E21
Abnormal temperature

Cause:

The temperature in the main circuit exceeded the specified value due to high ambient temperature or improper installation.



Remedy:


  • Check the installation (is inverter installed vertically?).

  • Decrease the ambient temperature.


E22
CPU communication error

Cause:

Malfunction or error in the built-in CPU during communications.



Remedy:


  • Take measures against noise.

  • The inverter is faulty. Repair it.


E25
Main circuit error

Cause:

An error occurred in the main circuit board.



Remedy:


  • Take measures against noise.

  • The inverter is faulty. Repair it.


E30
Driver error

Cause:

Momentary overcurrent (350% of rated), abnormal temperature in main element, or voltage drop detected by driver IC.



Remedy:


  • Check the output wiring for short-circuits.

  • Check output wiring and motor for ground faults.

  • Check the IGBT (is main element damaged?).

  • Clean the cooling fin if clogged.


E35
Thermistor error

Cause:

Abnormal temperature detected from external thermistor resistance value.



Remedy:


  • Check if motor temperature is too high.

  • Check if the thermistor is damaged.

  • Separate the wiring (noise in thermistor signal).


E36
Brake error

Cause:

Inverter cannot recognize ON/OFF status of brake within Brake Error Detection Time (b124).



Remedy:


  • Check the brake ON/OFF function.

  • Increase the b124 value (time set is too short).

  • Check the wiring for the brake confirmation signal input.


E37
Emergency shutoff

Cause:

The safety input terminals GS1/GS2 are active.



Remedy:


  • Check the wiring and sequence of GS1/GS2 signals.

  • Check the GS Input Operation Selection (b145) setting.


E38
Overload protection (Low speed)

Cause:

Overload detected in extremely low speed range (0.2 Hz or lower).



Remedy:


  • Reduce the load rate.


E40
Digital Operator connection failure

Cause:

Error or disconnection communicating with external Digital Operator.



Remedy:


  • Check/replace the cable.


E41
Modbus communication error

Cause:

Timeout occurs when Operation Selection on Communication Error (C076) is set to 00.



Remedy:


  • Check the communication speed setting.

  • Check the communications wires and wiring distance.

  • Check for any disconnected wires.


E43 - E45
DriveProgramming error

Cause:

Program error in DriveProgramming.



Remedy:


  • Refer to the DriveProgramming User's Manual.


E50 - E59
User trip

Cause:

User trip initiated by DriveProgramming.



Remedy:


  • Refer to the DriveProgramming User's Manual.


E60 - E68
Option error

Cause:

Error received from the mounted option unit (e.g., EtherCAT or CompoNet fatal fault).



Remedy:


  • Refer to the manual for the specific option unit.


E69
Option timeout

Cause:

Timeout in communications between the inverter and the option unit.



Remedy:


  • Check that the housing of the option unit is mounted properly.

  • Check that fixation screws are not loosened.

  • The option unit may be faulty.


E80
Encoder disconnection

Cause:

The encoder wiring is disconnected, or motor rotation speed detected is lower than Starting Frequency for the set duration.



Remedy:


  • Check the encoder wiring.

  • Adjust parameter values (set longer time in P077, higher value in P015).


E81
Overspeed

Cause:

Motor rotation speed exceeds Maximum Frequency × Overspeed Error Detection Level.



Remedy:


  • Check the encoder wiring.

  • Check the number of encoder pulses (P011).

  • Adjust the Overspeed Error Detection Level (P026).


E83
Position control range trip

Cause:

Current position is out of the range set in Position Limit Setting (P072, P073) during simple position control.



Remedy:


  • Check the current position.

  • Check the parameter settings (P072, P073).

  • Check the origin.


How to Clear & Reset Omron 3G3MX2-V1 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET key on the front digital operator panel while the trip code (e.g., E01, E12) is displayed. Ensure run commands are disabled before resetting to prevent unintended motor starts.
  2. Digital Input Reset (RS): Pulse the digital input terminal assigned to function 18 [RS] (Reset) (configured on terminals 1 to 7 via parameters C001 through C007). Maintain the signal for at least 12 ms and then release.
  3. CX-Drive PC Software: Connect a mini-USB cable to the inverter’s front USB port, establish an online connection using Omron CX-Drive, open the status monitoring window, and execute the Trip Reset command.
  4. Fieldbus / Modbus RTU: Send a reset command over RS-485 Modbus RTU (Modbus control word command register) or via an optional communication unit such as EtherCAT (3G3AX-MX2-ECT), DeviceNet, or CompoNet.
  5. Power Cycle: Disconnect the primary AC input power, wait until the front POWER / CHARGE indicator LED is completely unlit (allow at least 10 minutes for full DC bus capacitor discharge), and then restore main power.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect primary power and wait at least 10 minutes until the CHARGE lamp is completely turned off. Verify with a calibrated digital multimeter that the DC intermediate circuit voltage measures strictly below 50VDC across terminals [+1]/[+] and [-] before touching terminals (R/L1, S/L2, T/L3, U/T1, V/T2, W/T3) or working inside the Omron 3G3MX2-V1 inverter enclosure.